Inim ELECTORINICS EM322AC 2 Relay Output 230 Vac Rated Module Instruction Manual

June 12, 2024
Inim ELECTORINICS

Inim ELECTORINICS EM322AC 2 Relay Output 230 Vac Rated Module

Product Information

Product Name: EM322AC
Product Type: 230 V module
Certifications: EN 54-17, EN 54-18
Manufacturer: Inim Electronics S.r.l.
Address: Centobuchi, via Dei Lavoratori 10, 63076 Monteprandone (AP), Italy
Contact: +39 0735 705007, +39 0735 734912
Email: info@inim.biz
Website: www.inim.biz

Product Usage Instructions

Description: The EM322AC modules are certified according to EN54-17 Short Circuit Isolators and EN54-18 Input/Output Devices.

Parts Description

  • Morsettiera: Terminal for connection with the loop.
  • Loop IN1: Input terminal for the loop.
  • IN2 OUT1 OUT2: Output terminals for connecting devices such as electromagnets for fire doors, etc.
  • Segnalazioni LED: LED indicators for ALARM, FAULT, and OUT.

A Loop terminals
B Input terminals 1
C Input terminals 2
D Red 8ALARM9 LED
E Yellow 8FAULT9 LED
F Green 8OUT9 LED
G Connectors for enabling/disabling monitoring on output 1
H Connectors for enabling/disabling monitoring on output 2
I Relay 1 output terminals
J Relay 2 output terminals
K Mounting holes with knockouts

LED Indicator Descriptions:

  • ALARM: Indicates input alarm.
  • FAULT: Indicates fault on supervised outputs (voltage less than 7V or current consumption higher than 2mA).
  • OUT: Indicates active output.

Monitor Contacts:

You can enable or disable the supervision of each output by changing the position of the jumper on the Monitor contacts:

  • ENABLED: Supervision enabled.
  • DISABLED: Supervision disabled.

Technical Specifications

  • Input Voltage Range: 19V to 30V
  • Standby Power Consumption: Alarm
  • Input Balance Resistance: 22k Ohm
  • Input Alarm Resistance: 2k2 Ohm
  • Weight: 130g
  • Isolator Specifications (EN 54-17): Vloop, VSO, VSC, IC, IS, IL, ZC
  • Insulation Class (EN IEC 62368-1): Class d’isolamento
  • Terminal Type: LOOP IN1/IN2, OUT1/OUT2, PS1/ES1, PS3/ES3

Power supply

range from 19 to 30 V
nominal 24 V

Current draw

in standby 80 µA
in alarm 10 mA
Input balancing resistance 22 KOhm
Alarm input resistance 2.2 KOhm
Relay contact rating MAX 5 A / 30 V MAX 5 A / 230 V ~ (with resistive

load)

Environmental conditions

Temperature from -10 to +40 °C
Relative humidity f 95 % without condensation

Dimensions

Height|
---|---
Width (with anchor locations)|
Width (without anchor locations)|
Height (with anchor locations)| 113 mm
Height (without anchor locations)| 90 mm
Width| 71 mm
Depth (with terminal boards)| 43 mm
Depth (without terminal boards)| 40.5 mm
Weight| 130 g
Isolator specifications (EN 54-17)| min| max
---|---|---
V loop| 19 V| 30 V
V SO| 10.5 V| 11.9 V
V SC| 2.95 V| 8.04 V
I C| 400 mA| 600 mA
I S| 400 mA| 600 mA
I L| –| 10.91 mA
Z C| 0.1 «| 0.223 «

(EN IEC 62368-1)

Insulation class|
---|---
Type of terminals| LOOP| PS1, ES1
IN1/IN2| PS1, ES1
OUT1/OUT2| PS3, ES3

Installation

The module should be connected to the detection control panel using a 2-wire twisted and shielded conductor. This conductor is used for both power supply and bidirectional digital communication. Refer to the control panel’s manual for installation details and wiring instructions.
The module must be connected to the control panel via a 2 pole twisted- shielded cable. This cable carries both the power supply and the two-way digital communications data (refer to the control panel installation manual, section for the wiring diagram).

Attention
The installation must be carried out in accordance with the national regulations governing installations and the power source to be switched to the output must be provided through a bipolar protection device.
The wire used for wiring of the product must have an adequate section and comply with the IEC 60332-1-2 or IEC 60332-2-2 standards. The module has a short-circuit isolator which, in the event of short-circuit between the two poles of the control panel loop cable, is capable of interrupting the negative pole and thus isolating the sec-tion involved in the short-circuit. For the isolator specification, please refer to the <ILP Specification= document. The plastic box can be fitted on a standard 35mm DIN bar or in any electrical box by means of the flanges with the fixing holes. The module occupies 2 addresses on loops with protocol INIM.

Attention
The device must be installed inside a fireproof enclosure.
The two removable serial number stickers should be taken off the module; one should be attached to the box where the device is to be housed, the other to the installation layout. Once all the loop devices have been properly connected, refer to the control panel installation and programming manual for instructions regarding the configuration and addressing procedures.
Product Code: DCMIIN4AEM322AC-101-20221108

Product description
The module EM322AC allows the interfacing of external devices to an analogue- addressed control panel by means of two monitored inputs and two relay outputs (which can be activated independently) capable of switching 24V or 230V loads.

Note
The EM322AC are certified and approved in accordance with EN54-17 Short- circuit isolators and EN54-18 3 Input/Output devices.

Terminals

Loop| Terminals for the connection to the loop.|
---|---|---
IN1| Supervised input terminals: allow you to obtain the status of one or more contacts and report it to the control panel. It is used to connect external devices such as linear smoke detectors with output relays or any type of device equipped with one or more output relays to the control panel.| Stand-by resistor: 22k Ohm Alarm resistor: 2k2 Ohm
IN2
OUT1| Supervised dry-contact output terminals: allow activation of devices such as electromagnets for fire doors, etc.| Bistable relay, maintains the switching status sent by the control panel
OUT2

Inim -ELECTORINICS- EM322AC- 2- Relay -Output -230 -Vac- Rated- Module-
02

LED signallings

ALARM red Input in alarm status
FAULT yellow Fault on monitored outputs (voltage less than 7V or

current absorption greater than 2mA) Input fault Isolator fault
OUT| green| Output activated

Monitor Contacts
The module can monitor each output by checking the voltage across the 8NO9 contact.  It is possible to enable or disable the monitoring of each output after changing the position of the jumper on the 8Monitor9 contacts:

Inim -ELECTORINICS- EM322AC- 2- Relay -Output -230 -Vac- Rated- Module-
05

Attention
The jumper connectors are connected directly to the output voltage.

Using the EDRV2000 driver
The EDRV2000 driver allows you to change the operating parameters of the detectors, check the contamination level of the smoke chambers and also obtain accurate diagnostic data. It can operate through the USB port of a computer furnished with the relative software programme, or can function autonomously by way of the battery housed inside. Each detector is capable of retaining memory (smoke and/or temperature depending on the model) of the 5 minutes prior to an alarm. Therefore, if an alarm occurs, it will be possible to obtain information regarding the onset of the fire by simply connecting the EDRV2000 driver to the detection line. For further information and details regarding use of the EDRV2000 driver, refer to the respective handbook.

Testing and maintenance
The functionality of the module should be tested immediately after installation and periodically during maintenance inspections, in accordance with the established standard regulations and codes in force.

CE mark


Documents for the users
Declarations of Performance, Declarations of Conformity and Certificates concerning to Inim Electronics S.r.l. pro-ducts may be downloaded free of charge from the web address www.inim.biz, getting access to Extended Access and then selecting “Certifications” or requested to the e-mail address info@inim.biz or requested by ordinary mail to the address shown in this manual. Manuals may be downloaded free of charge from the web address www.inim.biz, getting access to Extended Access and then selecting “Manuals”.

Warnings and limitations
The EM322AC module must be used exclusively with control panels that operate on Inim Electronics Open Loop protocol. This product is not suitable for outdoor installation. However, if outdoor installation is necessary, ensure that the device is housed inside a suitable enclosure with the required protection grade.

Manufacturer’s details
Manufacturer: Inim Electronics S.r.l.
Production plant: Centobuchi, via Dei Lavoratori 10 63076 Monteprandone (AP), Italy
Tel: +39 0735 705007
Fax: +39 0735 734912
e-mail: info@inim.biz
Web: www.inim.biz
The persons authorized by the manufacturer to repair or replace the parts of this system, hold authorization to work on Inim Electronics brand devices only.

About this manual
Manual code: DCMIIN4AEM322AC
Revision: 101
Copyright: the information contained in this document is the sole property of Inim Electronics S.r.l. No part may be copied without written authorization from Inim Electronics S.r.l.. All rights reserved.

WEEE

lnformative notice regarding the disposal of electrical and electronic equipment (applicable in countries with differentiated waste collection systems) The crossed-out bin symbol on the equipment or on its packaging indicates that the product must be disposed of correctly at the end of its working life and should never be disposed of together with general household waste. The user, therefore, must take the equipment that has reached the end of its working life to the appropriate civic amenities site designated to the differentiated collection of electrical and electronic waste. As an alternative to the autonomous-management of electrical and electronic waste, you can hand over the equipment you wish to dispose of to a dealer when purchasing new equipment of the same type. You are also entitled to convey for disposal small electronic-waste products with dimensions of less than 25cm to the premises of electronic retail outlets with sales areas of at least 400m2, free of charge and without any obligation to buy. Appropriate differentiated waste collection for the subsequent recycling of the discarded equipment, its treatment and its environmentally compatible disposal helps to avoid possible negative effects on the envi-ronment and on health and favours the re-use and/or recycling of the materials it is made of.