BIOGENESIS EPD 0356 6 Kg D Powder Fire Extinguisher User Manual
- June 12, 2024
- BIOGENESIS
Table of Contents
6 Kg D Powder FIRE EXTINGUISHER
User Manual
EPD 0356 6 Kg D Powder Fire Extinguisher
-
CYLINDER
Alloy steel, 3 pieces drawing, epoxypolyestere powder painting, Red Ral 3000. -
EXTINGUISHING AGENT
D powder . -
PROPELLANT
Dehumidified air or N2 . -
VALVE
CPF M. 30×1.5, brass body, levers with red painting Ral 3000. -
USE
D fire rating (recommended in environments with risks arising from the presence of flammable metal).
Note: image is for illustrative purpose only, the product purchased can
has some differences
6 Kg powder fire extinguisher, temperature range from -30°C to +60°C,
manufactured in accordance to UNI EN 3-7, certified according to the directive
for pressure equipment PED 2014/68/EU.
Quality Product certification guaranteed by Bureau Veritas Italia.
Suitable for use on fire involving electrical voltages up to 1.000 V, at a
distance of 1 mt.
APPROVED/CERTIFIED FIRE EXTINGUISHER:
FIRE RATING :
TECHNICAL SPECIFICATIONS
FIRE RATING | D |
---|---|
EXTINGUISHING AGENT | EPD 0356 (PRO-M) – D powder |
PROPELLANT | Dehumidified air or N2 ,15 Bar at 20°C |
TEMPERATURE RANGE | -30°C / +60°C |
NOMINAL CHARGE | 6 Kg |
FULL WEIGHT | ~ 10 Kg |
DIMENSIONS | Height(base-valve) 505 mm Diameter 160 mm |
DISCHARGE TIME | 18,5 sec. |
VALVE TIGHTENING TORQUE | Minimum 45 Nm, Maximum 68 Nm |
CYLINDER PRESSURE TEST | PT 27 bar |
CYLINDER VOLUME | 7,3 L. |
SAFETY VALVE | Set between 20 and 24 bar |
CYLINDER MATERIAL | Alloy steel |
EXTERNAL/INTERNAL TREATMENT | Sandblast and epoxypolyestere powder painting, |
Red Ral 3000 colour
PACKAGING
STANDARD : maximum 100 pieces for pallet (44 pieces for box, max 2 boxes for pallet) (12 pieces in single packaging) Pallet dimensions 100x120x160(h) cm
SINGLE PACKAGING ON REQUEST:
- maximum 64 pieces on pallet 100×120 cm
- maximum 48 pieces on pallet 80×120 cm
Note: the packaging quantities and measurements are indicative and can be subject at changes
MAINTENANCE AND INSTALLATION
For outdoor or marine installation is recommended to protect the fire extinguisher with cover or box. Maintenance according to the rules in use in utilization country.
SPARE PARTS
NUMBER | DESCRIPTION |
---|---|
1 | Valve M. 30×1.5 |
2 | Cylinder |
3 | PVC dip tube |
4 | Hose |
5 | Extension hose |
6 | Horn |
7 | Magnet stop hose |
8 | Label |
9 | Safety pin |
Safety valve | |
Safety pin seal |
© REPRODUCTION IS PROHIBITEDhttps://www .bio-genesis.it