BIOGENESIS 6 L Foam Portable Fire Extinguisher User Manual
- October 30, 2023
- BIOGENESIS
Table of Contents
BIOGENESIS 6 L Foam Portable Fire Extinguisher User Manual
- CYLINDER
In high-strength alloy steel, deep drawing, external powder painting Red Ral
-
EXTINGUISHING AGENT
Water-based foam. -
PROPELLANT
Dehumidified air or nitrogen (N2). -
VALVE
CPF M. 30×1.5, brass body, with anti-corrosion treatment. -
USE
A B F fire rating (solid materials, flammable liquids, cooking oils).
Note: image is for illustrative purpose only, the product purchased can has some difference
6 L foam fire extinguisher, temperature range from +5°C to +60°C, manufactured
in accordance to UNI EN 3-7, (D.M. 7.1.2005), approved Marine Equipment
Directive MED 2014/90/EU, certified according to the directive for pressure
equipment PED 2014/68/EU.
Quality Product certification guaranteed by Bureau Veritas Italia.
Suitable for use on fire involving electrical voltages up to 1. 000 V, at a
distance of 1 meter.
MODALITY OF USE
-
REMOVE SAFETY PIN
-
HOLD THE HOSE
-
SQUEEZE GRIP LEVER
-
AIM THE JET AT BASE OF FIRE
Follow the instructions present on the marking label.
ATTENTION: Do not direct the jet at people. If you’re dispensing in close spaces, then ventilate the room. The fire extinguisher can be used on fire involving electrical voltages up to 1. 000 V, at a distance of 1 meter.
INSTALLATION AND COMMISSIONING
The installation of the fire extinguisher must be performed according to the
rules in force.
The fire extinguisher have to be installed in a safe and stable support, with
a gripping at a maximum recommended height of 110 cm.
The fire extinguisher must be free of obstructions and marked by an
appropriate identifying label.
It is recommended to install it in a dry place, protected from the atmospheric
agents.
It is recommended the installation of water-based fire extinguishers for close
spaces.
The commissioning of the fire extinguisher for the protection of the area must
be carried out by qualified personnel according to the rule in force within 6
months from the date of production and/or placing on themarket, reported in
the declaration of conformity released by the producer.
MAINTENANCE PERIODS FOR EFFICIENCY GUARANTEES
The maintaning of the product efficiency have to be carried out from the
responsible person.
It is recommended a visual check of the efficiency state every three months
since the commissioning time apart if there are different dispositions.
It is advisable to : verify that the fire extinguisher would be in a correct
position, safe and stable, free from impediment for the use; identify the fire
extinguisher with an appropriate identification sign; make sure of its
structural integrity and that is free from any damage; check that the original
documentations is available.
Any restoration operations and instrumental checking have to be realized
exclusively by qualified personnel who possess the necessary documentations to
mantain the constancy of the product performance.
Any tampering or intromission by unauthorized personnel voids the product
warranty.
TECHNICAL SPECIFICATIONS
FIRE RATING | 43 A 233 B 75 F |
---|---|
EXTINGUISHING AGENT | Foam EWAB1 |
PROPELLANT | Dehumidified air or Nitrogen (N2), 15 bar at 20°C |
TEMPERATURE RANGE | +5°C / +60 |
NOMINAL CHARGE | 6 Liters |
FULL WEIGHT | ~ 9,65 Kg |
DIMENSIONS | Height (base – valve) 540 +/- 5 mm |
Diameter (cylinder) 160 +/- 2 mm
DISCHARGE TIME| ~ 20,9 seconds
Read User Manual Online (PDF format)