Overview
The EBR-DIN-DALIG64 is a Rapid lighting control module designed for
controlling 64 addressable DALI devices such as fluorescent or LED lighting
ballasts. There are two relays providing a switched live output and a third
relay for emergency test. Additionally there is a volt free contact to control
external devices. This LCM also has a total of 8 switch inputs and 2 DALI
connections. Used in conjunction with our range of DALI presence detectors a
single DALI cable can be run to digitally control all the lighting and power
the sensors. This saves time and money on additional specialist cable. It is
ideal for chilled beam, continuous run lighting, and core areas.
Please speak to our technical team for further information.
Features
Front features
Mains connections
-
Live, Earth, Neutral.
SELV switch inputs -
8 SELV switch inputs.
Volt free outputs -
3 x normally open 10A 230VAC rated Voltage free relays. Used to switch external peripherals, such as HVAC and BMS systems.
-
1 x normally closed 6A 230VAC rated Voltage free relay. Suitable for emergency testing.
Communication ports -
1 x power and Rapid network bus port
-
1 x DALI port
Removable Terminals (plug & socket) Hardware build 1.4 or later versions are upgraded with removeable terminals throughout for easy wiring or product replacement onsite.
Removable memory feature Hardware build 1.4 or later versions are upgraded with the removable memory feature that allows settings to be easily transferred to a replacement unit without re-programming.
System wiring example
DALI bus loading
Devices (detectors / input units) and ballast combinations for 200mA supply. This assumes that the sensor LEDs are all on, and the sensor is receiving IR communicant.
-
4 devices and up to 64 ballasts
-
5 devices and up to 55 ballasts
-
6 devices and up to 44 ballasts
-
7 devices and up to 33 ballasts
-
8 devices and up to 22 ballasts
-
9 devices and up to 12 ballasts
-
10 devices and up to 2 ballasts
In most realistic scenarios, only one LED is on at a time and only one detector is receiving IR; guidance changes to. -
10 devices up to 64 ballasts
-
11 devices up to 60 ballasts
-
12 devices up to 55 ballasts
-
13 devices up to 50 ballasts
-
14 devices up to 48 ballasts
-
15 devices up to 44 ballasts
Addressing limits of DG64 -
5 input units of 7 channels each
-
10 detectors
Technical data
Dimensions See diagrams opposite
Weight 0.40kg
Supply Voltage 220 – 240VAC
Frequency 50Hz
Relay rating Normally open relays 10A
Normally closed relay 6A
Volt free output 10A
Terminal Capacity 2.5mm2
Power consumption On 2930mW, Off 2120mW
DALI Voltage 16VDC via DALI
DALI Output Current 250mA (maximum)
DALI bus Cannot be considered as SELV since DALI, ballasts only offer basic
insulation, therefore all devices on the DALI bus must be
wired as if carrying mains potential.
Temperature -10ºC to 35ºC
Humidity 5 to 95% non-condensing
Material (casing) Flame retardant ABS and PC/ABS
Classifications Insulation Class II
Purpose Operating control
Construction Incorporated control
Type of action Type 1.B action
micro disconnection
Software class Class A
Pollution Degree 2
Compliance
For further compliance information visit
www.cpelectronics.co.uk/compliance
Part numbers
Part number Description
Control module EBR-DIN-DALIG64 DIN rail DALI lighting control module
Accessories UNLCDHS Universal LCD programming handset
Due to our policy of continual product improvement CP Electronics reserves the right to alter the specification of this product without prior notice.
CP Electronics – a business unit of
Legrand Electric Limited
Brent Crescent, London NW10 7XR UK
Tel: +44 (0)333 900 0671
Fax: +44 (0)333 900 0674
www.cpelectronics.co.uk
enquiry@cpelectronics.co.uk
Ref: #WD583 Issue 10
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>