CP electronics EBMPIR-MB-PRM Mini PIR Detector for Luminaire Integration Installation Guide

June 9, 2024
CP electronics

WD939 Issue 5 Installation Guide
EBMPIR-MB-PRM
Mini PIR Detector for Luminaire Integration (Batten Mount)

EBMPIR-MB-PRM Mini PIR Detector for Luminaire Integration

EBMPIR-MB-PRM
PRM switching, miniature, luminaire mounted, PIR, presence detector

Warning
This device should be installed by a qualified electrician in accordance with the latest edition of the IEE wiring regulations.

Dimensions (mm)

Detection pattern

Walk across

Height Range Diameter
9m 14m
7m 13m
5m 11m
3m 8m

Walk towards

Height Range Diameter
9m 7m
7m 7m
5m 7m
3m 5m

Wiring

**** Dimming ouputs

Basic insulation only. Although low voltage, this is not an SELV output and should be treated as if mains potential. Use mains rated wiring.

Key

  1. Neutral
  2. Live
  3. 10A circuit protection if required
  4. Load

Standard luminaire fitting

Mounting without key

Mounting with key. Note: Key to be at the top of the sensor.

Wire in plugs & connect to detector

Key

  1. M20 nut
  2. IP spacer

IP luminaire fitting

Key

  1. M20 nut
  2. 5° washer (optional)
  3. Silicone washer
  4. IP spacer
    • Note: Use the 5° spacers where the luminaire has a draft angle.
    • Ensure that the silicone washer and/or IP spacer are used to maintain IP rating.

Default Settings

Time out: 20 minutes.
LUX on level: 9
LUX off level: 9
Sensitivity: 9
Detection: Presence
Adjustments can be made using the optional UHS5 or UNLCDHS handsets.

Technical Data

Part code EBMPIR-MB-PRM
Weight 0.100kg
Supply voltage AC 230 VAC +/- 10%
Supply frequency 50Hz
Power consumption parasitic 807mW

Max load:
Incandescent lighting| 2A
Fluorescent lighting| 2A
Compact fluorescent
lighting| 2A
LED lighting| 2A
Cable specification| 1m 1/1.13 solid corecable 105ºC
SON lighting| Switch loads via a contactor
Working temperature range| -10 to 35ºC
Humidity| 5 to 95% noncondensing
Material (casing)| Flame retardant
ABS/PC
Insulation class| 2
IP rating| 65
**** Compliance| EMC-2014/30/EU
LVD-2014/35/EU

Testing

Presence Detection

  1. Power up the sensor. The load should come on immediately.

  2. Vacate the room or remain very still and wait for the load to switch off (this should take less than 20 minutes).

  3. Enter the room or make some movement and check that the load switches on.

 Accessories & associated products

Part Number Description
UHS5 Compact, programming
UHS7 Compact, user handset
UNLCDHS Universal LCD IR handset
CP Electronics

A Business unit of Legrand Electric Limited, Brent Crescent, London NW10 7XR, UK
t. +44 (0)333 900 0671
[email protected]|
---|---|---
www.cpelectronics.co.uk| connect with us

Due to our policy of continual product improvement CP Electronics reserves the right to alter the specification of this product without prior notice.
WD939 Issue 5 Installation Guide, EBMPIR-MB-PRM

20923
Walk towards & walk across explained
cpelectronics.co.uk/cp/wta

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

CP electronics User Manuals

Related Manuals