CP electronics EBMPIR-MB-PRM Mini PIR Detector for Luminaire Integration Installation Guide
- June 9, 2024
- CP electronics
Table of Contents
- EBMPIR-MB-PRM Mini PIR Detector for Luminaire Integration
- Dimensions (mm)
- Detection pattern
- Wiring
- Standard luminaire fitting
- IP luminaire fitting
- Default Settings
- Technical Data
- Testing
- Accessories & associated products
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
WD939 Issue 5 Installation Guide
EBMPIR-MB-PRM
Mini PIR Detector for Luminaire Integration (Batten Mount)
EBMPIR-MB-PRM Mini PIR Detector for Luminaire Integration
EBMPIR-MB-PRM
PRM switching, miniature, luminaire mounted, PIR, presence detector
Warning
This device should be installed by a qualified electrician in accordance
with the latest edition of the IEE wiring regulations.
Dimensions (mm)
Detection pattern
Walk across
Height | Range Diameter |
---|---|
9m | 14m |
7m | 13m |
5m | 11m |
3m | 8m |
Walk towards
Height | Range Diameter |
---|---|
9m | 7m |
7m | 7m |
5m | 7m |
3m | 5m |
Wiring
**** Dimming ouputs
Basic insulation only. Although low voltage, this is not an SELV output and should be treated as if mains potential. Use mains rated wiring.
Key
- Neutral
- Live
- 10A circuit protection if required
- Load
Standard luminaire fitting
Mounting without key
Mounting with key. Note: Key to be at the top of the sensor.
Wire in plugs & connect to detector
Key
- M20 nut
- IP spacer
IP luminaire fitting
Key
- M20 nut
- 5° washer (optional)
- Silicone washer
- IP spacer
• Note: Use the 5° spacers where the luminaire has a draft angle.
• Ensure that the silicone washer and/or IP spacer are used to maintain IP rating.
Default Settings
Time out: 20 minutes.
LUX on level: 9
LUX off level: 9
Sensitivity: 9
Detection: Presence
Adjustments can be made using the optional UHS5 or UNLCDHS handsets.
Technical Data
Part code | EBMPIR-MB-PRM |
---|---|
Weight | 0.100kg |
Supply voltage AC | 230 VAC +/- 10% |
Supply frequency | 50Hz |
Power consumption parasitic | 807mW |
Max load:
Incandescent lighting| 2A
Fluorescent lighting| 2A
Compact fluorescent
lighting| 2A
LED lighting| 2A
Cable specification| 1m 1/1.13 solid corecable 105ºC
SON lighting| Switch loads via a contactor
Working temperature range| -10 to 35ºC
Humidity| 5 to 95% noncondensing
Material (casing)| Flame retardant
ABS/PC
Insulation class| 2
IP rating| 65
**** Compliance| EMC-2014/30/EU
LVD-2014/35/EU
Testing
Presence Detection
-
Power up the sensor. The load should come on immediately.
-
Vacate the room or remain very still and wait for the load to switch off (this should take less than 20 minutes).
-
Enter the room or make some movement and check that the load switches on.
Accessories & associated products
Part Number | Description |
---|---|
UHS5 | Compact, programming |
UHS7 | Compact, user handset |
UNLCDHS | Universal LCD IR handset |
CP Electronics |
A Business unit of Legrand Electric Limited, Brent Crescent, London NW10 7XR,
UK
t. +44 (0)333 900 0671
enquiry@cpelectronics.co.uk|
---|---|---
www.cpelectronics.co.uk| connect with us
Due to our policy of continual product improvement CP Electronics reserves the
right to alter the specification of this product without prior notice.
WD939 Issue 5 Installation Guide, EBMPIR-MB-PRM
20923
Walk towards & walk across explained
cpelectronics.co.uk/cp/wta