CP electronics EBR-CPIR-DALI Network Ceiling PIR with Photocell Installation Guide
- June 12, 2024
- CP electronics
Table of Contents
CP Electronics EBR-CPIR-DALI Network Ceiling PIR with Photocell
Product Information
Product Name | EBR-CPIR-DALI |
---|---|
Product Type | DALI network ceiling PIR with photocell |
Features |
-
PIR Sensor: Detects movement within the unit’s detection range,
allowing load control in response to changes in occupancy. -
IR Receiver: Receives control and programming commands from an
IR (infrared) handset. -
Light Level Sensor: Measures the overall light level in the
detection area. -
Status LEDs: The LED flashes Red or Green to indicate the
following:- Walk Test LED active when movement is detected
- Valid setting received
Mounting Options| Flush fixing or Surface fixing using the optional Surface
Mounting Box (part no. DBB). (Note: EBR-CPIR-DALI-IP – use the
supplied gasket to ensure IP rating, not compatible with Surface
Mounting Box part no. DBB)
Supply Voltage| 9.5VDC – 22.5VDC via DALI
Current Consumption| 8mA
Type| IP40 (EBR-CPIR-DALI), IP55 (EBR-CPIR-DALI-IP)
Compliance| EMC-2014/30/EU, LVD-2014/35/EU
Overview
The EBR-CPIR-DALI presence detector provides automatic control of lighting. It is connected to the RAPID DALI Gateway via a DALI network. Functioning as a presence detector, the unit can turn lights on when a room is occupied and off when the room is empty. An adjustable internal light sensor provides light level information to the RAPID system to allow lights to be kept off if sufficient daylight is present, and to enable maintained illuminance for dimming systems. An integral IR sensor in the unit allows the unit to be commissioned, and used in conjunction with a remote control handset (part no: UHS) to:
- Act as a conventional dimmer
- Override the unit on or off
Product Usage Instructions
- Front features
- Back features
DALI connection
Connection to the DALI bus via pluggable screw terminals. The DALI bus is
polarity insensitive.
Installation
Choosing a Suitable Location
The EBR-CPIR-DALI is designed to be ceiling mounted and must satisfy the following criteria:
- Avoid positioning the unit where direct sunlight may enter the sensor element.
- Do not site the sensor within 1m of any lighting, forced air heating or ventilation.
- Do not fix the sensor to an unstable or vibrating surface.
- Do not exceed maximum length of cable (200m) on data bus.
- Do not exceed maximum bus loading (200mA).
System wiring example
The EBR-CPIR-DALI is designed to be mounted using either:
- Flush fixing, or
- Surface fixing, using the optional Surface Mounting Box (part no. DBB). Both methods are illustrated below.
Note: EBR-CPIR-DALI-IP – use the supplied gasket to ensure IP rating (not compatible with Surface Mounting Box part no. DBB).
Flush Fixing
- Follow the wire stripping details provided in the manual.
- Mount the unit using the flush fixing method. Be careful when bending springs during mounting.
Surface Fixing
- Follow the wire stripping details provided in the manual.
- Mount the unit using the surface fixing method with 50mm or 60mm fixing centers.
Ensure that the cables are formed as shown before affixing the cable clamp. The clamp MUST clamp the outer sheath(s) only. Bend cores as shown.
System Wiring Example
Refer to the provided diagram for a system wiring example.
DALI bus loading
Devices (detectors / input units) and ballast combinations for 200mA
supply. This assumes that the sensor LEDs are all on, and the sensor is
receiving IR communication.
-
4 devices and up to 64 ballasts
-
5 devices and up to 55 ballasts
-
6 devices and up to 44 ballasts
-
7 devices and up to 33 ballasts
-
8 devices and up to 22 ballasts
-
8 devices and up to 22 ballasts
-
10 devices and up to 2 ballasts
In most realistic scenarios, only one LED is on at a time and only one detector is receiving IR; guidance changes to. -
10 devices up to 64 ballasts
-
11 devices up to 60 ballasts
-
12 devices up to 55 ballasts
-
13 devices up to 50 ballasts
-
14 devices up to 48 ballasts 15 devices up to 44 ballasts
Addressing limits of DG64 -
5 input units of 7 channels each
-
10 detectors
Technical Data
- Dimensions: See diagrams opposite
- Weight :0.07kg
- Supply Voltage :9.5VDC—22.5VDC via DALI Current consumption 8mA
- DALI bus: Cannot be considered as SELV since DALI, ballasts only offer basic insulation, therefore all devices on the DALI bus must be wired as if carrying mains potential.
- Terminal Capacity :2.5mm2 Temperature -10ºC to 35ºC
- Humidity: 5 to 95% non-condensing
- Material (casing): Flame retardant ABS and PC/ABS Compliance
- Type: Class 2
- IP rating :
- EBR-CPIR-DALI IP40
- EBR-CPIR-DALI-IP IP55
- Compliance :EMC-2014/30/EU LVD-2014/35/EU
EMC-2014/30/EU, LVD-2014/35/EU. For further compliance information, visit www.cpelectronics.co.uk/compliance
Detection diagram
Sensor Accessories
Part Number | Description |
---|---|
EBR-CPIR-DALI | DALI network ceiling PIR with photocell |
EBR-CPIR-DALI-IP | DALI network ceiling PIR with photocell sealed to IP55 |
DBB | Surface mounting box |
UHS | User handset override on/off; lux up/lux down |
UHS3 | User override remote handset on/off |
UHS3 (2) | User override remote handset, off only |
UNLCDHS | Universal LCD programming handset |
IMPORTANT NOTICE
This device should be installed by a qualified electrician in accordance with
the latest edition of the IEE Wiring Regulations and any applicable Building
Regulations.
Due to our policy of continual product improvement CP Electronics reserves the right to alter the specification of this product without prior notice.
CP Electronics – a business unit of Legrand Electric Limited Brent Crescent, London NW10 7XR UK Tel : +44 (0)333 900 0671 Fax : +44 (0)333 900 0674 VISIT AT www.cpelectronics.co.uk enquiry@cpelectronics.co.uk
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>