CP electronics EBDSPIR-AD Ceiling Mounted PIR Presence Detectors Installation Guide
- June 12, 2024
- CP electronics
Table of Contents
CP electronics EBDSPIR-AD Ceiling Mounted PIR Presence Detectors
1–10V analogue dimming, ceiling PIR presence/absence detector
Warning
- This device should be installed by a qualified electrician in accordance with the latest edition of the IEE wiring regulations.
- cpelectronics.co.uk/cp/924
Dimensions (mm)
Detection pattern
Wiring
Dimming ouputs
- Basic insulation only. Although low voltage, this is not a SELV output and should be treated as if mains potential. Use mains-rated wiring.
Single channel dimming
- Switches the luminaire with occupancy and maintains illuminance. Dims and switches using an optional centre-biased retractive switch.
Key
- Neutral
- Live
- 10A circuit protection if required
- Load
- Centre biased retractive switch, 230V (for absence detection)
- Dimming ballast
- Switching channel is L-Out,
- Dimming channel is DIM +/-
Single channel switching
- Switches channel 1 only with occupancy, optional override switch. No dimming output.
Key
- Neutral
- Live
- 10A circuit protection if required
- Load
- Centre biased retractive switch, 230V (for absence detection)
- Switching channel is L-Out,
- Dimming channel is DIM +/-
Installation
This device is designed to be flush ceiling-mounted.
- Do not site the unit where direct sunlight might enter the sensor.
- Do not site the sensor within 1m of any lighting, forced air heating or ventilation.
- Do not fix the sensor to an unstable or vibrating surface.
- Occupancy is best detected when the ambient temperature is different to that of the human body, thus, use within -20 to 35ºC ambient temperature.
Create cut out
- Cut a 64mm diameter hole in the ceiling.
Wire stripping
- Strip the wires as shown opposite. Presence detector does not require earth conductor.
Wire in plugs & connect to detector
- Wire in plug/s, using wiring diagram on page 3 as a guide. Connect the plug/s to the detector.
Clamp cable
- Continue tightening the screws until the clamp bar snaps out and is tightly engaged against the cable/s. The cable clamp must clamp the outer sheath only.
Install detector
- Bend the springs up and push detector through hole in ceiling. When fully inserted the springs snap back to hold the device in place.To avoid injury, take care when bending springs.
Default Settings
- Time out: 20 minutes.
- LUX on level: 999
- LUX off level: 999
- Sensitivity on: 9
- Sensitivity off: 9
- Detection: Presence
- Adjustments can be made using the optional UHS5 or UNLCDHS handsets.
Testing
Presence Detection
- Power up the sensor. The load should come on immediately.
- Vacate the room or remain very still and wait for the load to switch off (this should take less than 20 minutes).
- Enter the room or make some movement and check that the load switches on.
Absence Detection
- Power up the sensor. Switch the load on.
- Vacate the room and wait for the load to switch off (this should under than 20 minutes).
- Enter the room, the load will remain off until you switch it on again.
Technical Data
- This page is intentionally left blank
- This page is intentionally left blank
Accessories & associated products
Part Number Description
- Surface mounting box
- Surface mount back box extender
- Pre-drilled 64mm hole IP65 detector enclosure
- Extended wiring housing
- Masking shields for EBDSPIR range
- Compact, programming/commissioning handset
- Compact, user handset
- Universal LCD IR handset/commissioning handset