Basic switching, compact, IP40, ceiling, flush mounted, PIR, presence detector.

Warning

This device should be installed by a qualified electrician in accordance with the latest edition of the IEE wiring regulations

Downloads and Videos

cpelectronics.co.uk/cp/101

Dimensions (mm)

CP-electronics-EBDSPIR-Ceiling-Mounted-PIR-Presence-
Detectors-FIG-2

Detection pattern

CP-electronics-EBDSPIR-Ceiling-Mounted-PIR-Presence-
Detectors-FIG-3

WiringCP-electronics-EBDSPIR-Ceiling-Mounted-PIR-Presence-Detectors-
FIG-4

Key

  1. Neutral
  2. Live
  3. 10A circuit protection if required
  4. Load

Installation

  • This device is designed to be flush ceiling-mounted. See page 12 for additional mounting options.
  • Do not site the unit where direct sunlight might enter the sensor.
  • Do not site the sensor within 1m of any lighting, forced air heating, or ventilation.
  • Do not fix the sensor to an unstable or vibrating surface.

Create cut out

Cut a 64mm diameter hole in the ceiling.

Wire stripping

  • Strip the wires as shown opposite.
  • The presence detector does not require an earth conductor
Wire in plugs & connect to the detector

Wire in plug/s, using the wiring diagram on page 3 as a guide. Connect the plug/s to the detector.

Clamp cable

Continue tightening the screws until the clamp bar snaps out and is tightly engaged against the cable/s. The cable clamp must clamp the outer sheath only.

Install detector

CP-electronics-EBDSPIR-Ceiling-Mounted-PIR-Presence-
Detectors-FIG-9

  • Bend the springs up and push the detector through a hole in the ceiling.
  • When fully inserted the springs snap back to hold the device in place.
  • To avoid injury, take care when bending springs.
Adjust settings using pots

Set up Lux & time out settings using pot adjustments, before fully installing into the ceiling cut out.

Testing

Presence DetectionCP-electronics-EBDSPIR-Ceiling-Mounted-PIR-Presence-
Detectors-FIG-11

  1. Power up the sensor. The load should come on immediately.
  2. Vacate the room or remain very still and wait for the load to switch off (this should take less than 20 minutes).
  3. Enter the room or make some movement and check that the load switches on.

Technical Data

Part code EBDSPIR
Weight 0.150kg
Supply voltage AC 230 VAC +/- 10%
Supply frequency 50Hz
Power consumption parasitic 260mW
Terminal capacity 2.5mm²
Max load:
Incandescent lighting 8A
Fluorescent lighting 6A
Compact fluorescent lighting 3A
LED lighting 3A
Resistive heaters 8A

CP-electronics-EBDSPIR-Ceiling-Mounted-PIR-Presence-Detectors-
FIG-13

Accessories

Part Number
  • DBB: Surface mounting box

  • DBB-EXT:  Surface mount back box extender

  • EBD-ENCIP1: Pre-drilled 64mm hole IP65 detector enclosure

  • EXD-HSC: Extended wiring housing

  • EBDSPIR-MS: Masking shields for EBDSPIR range

  • CP Electronics

  • Brent Crescent, London NW10 7XR

  • t. +44 (0)333 900 0671

  • enquiry@cpelectronics.co.uk

  • www.cpelectronics.co.uk connect with us

  • Due to our policy of continual product improvement CP Electronics reserves the right to alter the specification of this product without prior notice.

Documents / Resources

| CP electronics EBDSPIR Ceiling Mounted PIR Presence Detectors [pdf] Installation Guide
WD101, EBDSPIR Ceiling Mounted PIR Presence Detectors, EBDSPIR, Ceiling Mounted PIR Presence Detectors, PIR Presence Detectors, Presence Detectors, Detectors
---|---

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

CP electronics User Manuals

Related Manuals