CP electronics EBDRC-AD Ceiling Mounted PIR Presence Detectors Installation Guide
- June 12, 2024
- CP electronics
Table of Contents
- CP electronics EBDRC-AD Ceiling Mounted PIR Presence Detectors
- Product Information
- Product Usage Instructions
- Dimensions (mm)
- Detection pattern
- Single channel wiring
- Installation
- Testing
- Technical Data
- Accessories & associated products
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
CP electronics EBDRC-AD Ceiling Mounted PIR Presence Detectors
Product Information
Product Name: Corridor Light Control
Detector
Model: EBDRC-AD
Installation Guide: WD940 Issue 5
Manufacturer: cpelectronic s.co.uk/cp/940
Languages:
- English (EN)
- German (DE)
- Spanish (ES)
- Portuguese (PT)
- Italian (IT)
- Dutch (NL)
- Russian (RU)
Important Safety Instructions:
- This device should be installed by a qualified electrician in accordance with the latest edition of the IEE wiring regulations.
- Basic insulation only. Although low voltage, this is not an SELV output and should be treated as if mains potential. Use mains rated wiring.
Technical Specifications:
-
Cut Out Size: 74mm
-
Sensitivity: High
-
Detection Range: 2.8m for walk towards, 10m for walk across,
and 24m for absence detection -
Switching Channel: L-Out
-
Dimming Channel: DIM +/-
Product Usage Instructions
Installation
- Cut a 74mm diameter hole in the ceiling.
- Connect the device according to the wiring regulations and using mains rated wiring.
Operation
Switching Channel 1 (Occupancy Detection)
- Connect the neutral wire (1) to the device.
- Connect the live wire (2) to the device.
- If required, connect a 10A circuit protection (3) to the device.
- Connect the load (4) to the device.
- Use a centre biased retractive switch (5) for absence detection. This switch should be connected to 230V.
- If applicable, connect a dimming ballast (6) to the device.
Switching Channel 2 (Override Switch)
- Connect the neutral wire (1) to the device.
- Connect the live wire (2) to the device.
- Connect an optional override switch (SW1/UP) to control channel 1.
- Connect an optional override switch (SW2 DOWN) to control channel 2.
Note: Channel 2 does not support dimming output.
1–10V analogue dimming, adjustable head, ceiling PIR presence/absence detector
Warning
This device should be installed by a qualified electrician in accordance with the latest edition of the IEE wiring regulations.
Dimensions (mm)
74mm cut out
Downloads and Videos
Detection pattern
Wiring
Dimming ouputs
Basic insulation only. Although low voltage, this is not an SELV output and
should be treated as if mains potential. Use mains rated wiring.
Single channel wiring
Key
- Neutral
- Live
- 10A circuit protection if required
- Load
- Centre biased retractive switch, 230V (for absence detection)
- Dimming ballast
Switching channel is L-Out, Dimming channel is DIM +/-
Single channel dimming
Switches the luminaire with occupancy and maintains illuminance. Dims and
switches using optional centre biased retractive switch.
Single channel switching
Switches channel 1 only with occupancy, optional override switch.
No dimming output.
Installation
This device is designed to be flush ceiling-mounted.
- Do not site the unit where direct sunlight might enter the sensor.
- Do not site the sensor within 1m of any lighting, forced air heating or ventilation.
- Do not fix the sensor to an unstable or vibrating surface.
- Occupancy is best detected when the ambient temperature is different to that of the human body, thus, use within -20 to 35ºC ambient temperature.
Create cut out
Cut a 74mm diameter hole in the ceiling.
Wire stripping
Strip the wires as shown opposite. Presence detector does not require earth
conductor.
Wire in plugs & connect to detector
Wire in plug/s, using wiring diagram on page 3 as a guide. Connect the plug/s
to the detector.
Clamp cable
Continue tightening the screws until the clamp bar snaps out and is tightly
engaged against the cable/s. The cable clamp must clamp the outer sheath only.
Install detector
Bend the springs up and push detector through hole in ceiling. When fully
inserted the springs snap back to hold the device in place.
To avoid injury, take care when bending springs.
Head position & locking
-
Remove metal locking clip from rear of unit.
-
Set sensor head position to 90º for maximum detection range. Push clip into position shown in the adjacent diagram to lock head. To remove clip, lever out with a small screwdriver.
Sensor head position < 90deg may result in varying detection range & sensitivity. -
Mount the detector centrally above the doorways for optimum detection as shown in the above image.
-
Mount the detector as close to the doorway as possible for precise movement detection and high sensitivity.
Default Settings
Time out: 20 minutes.
- LUX on level: 999
- LUX off level: 999
- Sensitivity on: 9
- Sensitivity off: 9
- Detection: Presence
Adjustments can be made using the optional UHS5 or UNLCDHS handsets.
Testing
Presence Detection
- Power up the sensor. The load should come on immediately.
- Vacate the room or remain very still and wait for the load to switch off (this should take less than 20 minutes).
- Enter the room or make some movement and check that the load switches on.
Absence Detection
- Power up the sensor. Switch the load on.
- Vacate the room and wait for the load to switch off (this should under than 20 minutes).
- Enter the room, the load will remain off until you switch it on again.
Technical Data
- Part code EBDRC-AD
- Weight 0.15kg
- Supply voltage 230 VAC +/- 10%
- Circuit Protection ≤10A, MCB Type B
- Supply frequency 50Hz
- Power consumption parasitic 807mW
- Terminal capacity 2.5mm²
Max Switched load ( L-Out )
- Resistive Incandescent [10A] Fluorescent [10A]
- Capacitive Electronic gear [10A] LED Lighting [10A]
- Inductive Fan [10A]
- Load inrush rating 200A for 300µsec
- Max Dim load (1-10V ) Up to 10 drivers
- Light detection range Usable 15-950 Lux
- Time out range 10s–99m
- Working temperature range -10 to 35ºC
- Humidity 5 to 95% non-condensing
- Material (casing) Flame retardant ABS and PC/ABS
- Insulation class 2
- IP rating 40
- Compliance EMC-2014/30/EU, LVD-2014/35/EU
Accessories & associated products
CP Electronics
Brent Crescent, London NW10 7XR
t.+44 (0)333 900 0671
enquiry@cpelectronics.co.uk
connect with us
Due to our policy of continual product improvement CP Electronics reserves the right to alter the specification of this product without prior notice.