CP Electronics EBDMR-AD Ceiling Mounted PIR Presence Detectors Installation Guide

June 12, 2024
CP electronics

CP Electronics logo WD996 Issue 4 Installation Guide
EBDMR-AD
1-10V dimming PIR Presence Detector

EBDMR-AD Ceiling Mounted PIR Presence Detectors

1 –10V analogue dimming, mid range, ceiling PIR presence/absence detector
Warning
This device should be installed by a qualified electrician in accordance with the latest edition of the IEE wiring regulations.

Downloads and Videos

cpelectronics.co.uk/cp/996

Dimensions (mm)

CP Electronics EBDMR-AD Ceiling Mounted PIR Presence Detectors - fig
1

Detection pattern

CP Electronics EBDMR-AD Ceiling Mounted PIR Presence Detectors - fig
2

Wiring

Dimming ouputs
Basic insulation only. Although low voltage, this is not an SELV output and should be treated as if mains potential. Use mains rated wiring.
Single channel dimming
Switches the luminaire with occupancy and maintains illuminance. Dims and switches using optional centre biased retractive switch.CP Electronics
EBDMR-AD Ceiling Mounted PIR Presence Detectors - fig 3 Key

  1. Neutral
  2. Live
  3. 10A circuit protection if required
  4. Load
  5. Centre biased retractive switch, 230V (for absence detection)
  6. Dimming ballast

Switching channel is L-Out,
Dimming channel is DIM +/-
Single channel switchingCP Electronics EBDMR-AD Ceiling Mounted PIR
Presence Detectors - fig 4 Key

  1. Neutral
  2. Live
  3. 10A circuit protection if required
  4. Load
  5. Centre biased retractive switch, 230V (for absence detection)

Switching channel is L-Out,
Dimming channel is DIM +/-

Installation

This device is designed to be flush ceiling-mounted.

  • Do not site the unit where direct sunlight might enter the sensor
  • Do not site the sensor within 1m of any lighting, forced air heating or ventilation.
  • Do not fix the sensor to an unstable or vibrating surface.
  • Occupancy is best detected when the ambient temperature is different to that of the human body, thus, use within -20 to 35ºC ambient temperature.

Create cut out Cut a 64mm diameter hole in the ceiling.
Wire stripping Strip the wires as shown opposite. Presence detector does not require earth conductor.
Wire in plugs & connect to detectorCP Electronics EBDMR-AD Ceiling
Mounted PIR Presence Detectors - fig 7Wire in plug/s, using wiring diagram on page 3 as a guide. Connect the plug/s to the detector.
Clamp cableCP Electronics EBDMR-AD Ceiling Mounted PIR Presence
Detectors - fig 8 Continue tightening the screws until the clamp bar snaps out and is tightly engaged against the cable/s. The cable clamp must clamp the outer sheath only.
Install detectorCP Electronics EBDMR-AD Ceiling Mounted PIR Presence
Detectors - fig 9 Bend the springs up and push detector through hole in ceiling. When fully inserted the springs snap back to hold the device in place.
**** To avoid injury, take care when bending springs.

Default Settings

Time out: 20 minutes.
LUX on level: 999
LUX off level: 999
Sensitivity on: 9
Sensitivity off: 9
Detection: Presence
Adjustments can be made using the optional UHS5 or UNLCDHS handsets.

Testing

CP Electronics EBDMR-AD Ceiling Mounted PIR Presence Detectors - fig
10

  1. Power up the sensor. The load should come on immediately.
  2. Vacate the room or remain very still and wait for the load to switch off (this should take less than 20 minutes).
  3. Enter the room or make some movement and check that the load switches on.

Absence Detection

  1. Power up the sensor. Switch the load on.
  2. Vacate the room and wait for the load to switch off (this should under than 20 minutes).
  3. Enter the room, the load will remain off until you switch it on again.

Technical Data

Part code EBDMR-AD
Weight 0.15kg
Supply voltage 230 VAC +/- 10%
Circuit Protection -:10A.MCB Type B
Supply frequency 50Hz
Power consumption parasitic 724mW
Terminal capacity 2.5mm?

Max Switched load (L-Out)
Resistive| Incandescent [10A1
Capacitive| Fluorescentn OA] Electronic gear [10A] LED Lighting [10A)
Inductive| Fan [10A)
Load inrush rating| 200A for 300psec
Max Dim load (1-10V)| Up to 10 drivers
Light detection range| Usable 15-950 Lux
Time out range| 10s-99m
Working temperature range| -10 to 35°C
Humidity| 5 to 95% non-condensing
Material (casing)| Flame retardantABS
and PC/ABS
Insulation class| 2
IP rating| 40
Compliance | EMC-2014/30/EU.
LVD-2014/35/EU

Accessories & associated products

Part Number Description
DBB Surface mounting box
DBB-EXT Surface mount back box extender
EBD-ENCIP1 Pre-drilled 64mm hole IP65 detector enclosure
EXD-HSC Extended wiring housing
UHS5 Compact, programming/commissioning handset
UHS7 Compact, user handset
UNLCDHS Universal LCD IR handset/commissioning handset

CP Electronics logoCP Electronics
Brent Crescent, London NW10 7XR
t. +44 (0)333 900 0671
[email protected]
www.cpelectronics.co.uk
connect with us
Due to our policy of continual product improvement CP Electronics reserves the right to alter the specification of this product without prior notice.
WD996 Issue 4 Installation Guide, EBDMR-AD

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

CP electronics User Manuals

Related Manuals