Eltako DL-PD-300W-RLC-HS Phase Dimmer Instruction Manual
- June 4, 2024
- Eltako
Table of Contents
DL-PD-300W-RLC-HS Phase Dimmer
Instruction Manual
DL-PD-300W-RLC-HS Phase Dimmer
Phase dimmer with DALI control input (DT4)
DL-PD-300W-RLC-HS
Only skilled electricians may install this electrical equipment
otherwise there is the risk of fire or electric shock!
The temperature at the mounting location: -20°C up to +50°C.
Storage temperature: -25°C up to +70°C.
Relative humidity: annual average value <75%.
Phase dimmer with DALI control input forDIN top-hat rails DIN-EN 60715
TH35. 98×17,5×56 mm. Protection class IP20.
Suitable for dimming 230 V LED retrofit luminaries using DALI Converts DALI
dimming level to a voltage with leading or trailing edge. The minimum dimming
level (MIN LEVEL) is adjustable via DALI. Additional operating mode as a
switch (conforms to DT7) as from Firmware 3.5. The module represents a bus
user and is therefore addressable. Double terminals for easy looping of the
DALI bus.
Dimming range 0.1%-100%·
Supply voltage 230 V AC.
Output load range 10-300 W.
High efficiency. Configuration via DALI Cockpit PC software.
Function:
The DALI PD is an interface between classic dimming technology (phase dimming) and DALI which is based on the standard for DALI Control Gear (IEC 62386-102) and Device Type 4 equipment (IEC 62386-205). The DALI PD interface converts the required dimming level into a corresponding voltage signal with a leading or trailing edge. Depending on the load the universal dimmer operates as a leading or trailing edge dimmer. The operating mode can be requested over DALI (DT4). The dimming characteristic is based on a logarithmic scale as stipulated in the DALI standard. The leading or trailing edge control supplies a sinusoidal voltage with a phase-cut on the leading or trailing edge. The PHYSICAL MIN LEVEL is 3%.
As of Firmware version 3.5, the DALI PD is equipped with an additional
operating mode. It is switchable from DT4 operating mode (phase dimming) to
DT7 (switch). In this operating mode, the DALI PD acts as a switch. Its
behavior in this mode corresponds to the DALI standard for DT7 devices
(IEC62386-208). In this operating mode, the switch characteristic is
determined by comparing the virtual dim level (VDAP) with 4 switching
thresholds. The virtual dim level (VDAP) corresponds to the dim level of a
DALI electronic ballast with its corresponding characteristics (limited by MIN
LEVEL and MAX LEVEL, dimming speed limited by fade time and fade rate). There
are 2 switching thresholds in each dimming direction and they are used for
comparison with the virtual dim level:
A threshold with the value ‘MASK’ is inactive and is not used in the
comparison.
Switch-on/off delays can be implemented with fading.
The device is powered from the DALI bus so that there is only partial support
for the SYSTEM FAILURE LEVEL. On current devices (identified by Firmware >
4.0), you can choose between 0%,100%, and MASK. On older models the SYSTEM
FAILURE LEVEL is fixed – the 25 W variant outputs 100%; the 300 W variant
outputs 0%.
Technical data
Output load range | 10-300 W |
---|---|
Screw terminals: | 2,5 mm² |
The crossed-out waste container indicates that the battery may not be
disposed of with other household or commercial waste.
Must be kept for later use!
Eltako GmbH
D-70736 Fellbach
Technical Support English:
+49 711 94350025
technical-support@eltako.de
eltako.com
05/2022
Subject to change without notice.