PPI Inde + Advanced Temperature Indicator with Alarm Instruction Manual

June 11, 2024
PPI

PPI Inde + Advanced Temperature Indicator with Alarm

PPI-Inde+Advanced-Temperature-Indicator-with-Alarm-
product

The Inde+ Advanced Temperature Indicator with Alarms is a device used for measuring temperature and providing alarms. It has various input/output configuration parameters, alarm parameters, and operator parameters that can be set by the user. The device has a front panel layout with keys for operation and a display for readout. The device also has electrical connections for output-1 SSR, output-2 relay, and input T/C Pt100.

Product Usage Instructions

To use the Inde+ Advanced Temperature Indicator with Alarms, follow the below steps:

  1. Connect the device to the power supply of LN 85~265V AC.
  2. Connect the input T/C Pt100 to the device.
  3. Set the input type by referring to Table 1 and selecting the appropriate type (default: Type K).
  4. Set the offset for measured temperature within the range of -1999 to 9999 or -199.9 to 999.9 (default: 0).
  5. Set the digital filter for PV within the range of 0.5 to 25.0 seconds (in steps of 0.5 seconds) (default: 1.0).
  6. Set the alarm parameters by selecting the alarm type (none, process low, process high), alarm hysteresis (1 to 999), and alarm logic (normal/reverse) for alarm-1 and alarm-2.
  7. Set the PV min/max parameters by selecting whether to reset the min/max process value and whether to view the maximum and minimum process value.
  8. Set the operator parameters by setting the alarm-1 setpoint and alarm-2 setpoint within the minimum to maximum range specified for the selected input type.
  9. Use the PAGE, ENTER, DOWN, and UP keys to navigate and set the parameters.
  10. View the readout on the display.

The device also provides PV error indications in case of over-range (PV above max. range), under-range (PV below min. range), or open (thermocouple/RTD broken).

For more details on operation and application, please log on to www.ppiindia.net.

This brief manual is primarily meant for quick reference to wiring connections and parameter searching. For more details on operation and application; please log on to www.ppiindia.net.

FRONT PANEL LAYOUT

INDEX48+/INDEX72+/INDEX96+

PPI-Inde+Advanced-Temperature-Indicator-with-Alarm-fig-1
\(1\)

INDEX48H+

PPI-Inde+Advanced-Temperature-Indicator-with-Alarm-fig-1
\(2\)

INPUT/OUTPUT CONFIGURATION PARAMETERS:

PV MIN/MAX PARAMETERS:

ALARM PARAMETERS:

PPI-Inde+Advanced-Temperature-Indicator-with-Alarm-fig-1
\(5\)

OPERATOR PARAMETERS:

ELECTRICAL CONNECTIONS

PPI-Inde+Advanced-Temperature-Indicator-with-Alarm-fig-1
\(8\)

Keys Operation

Symbol Key Function
**** PAGE Press to enter or exit set-up mode.
DOWN Press to decrease the parameter value. Pressing once decreases the

value by one count; holding pressed speeds up the change.
| UP| Press to increase the parameter value. Pressing once increases the value by one count; holding pressed speeds up the change.
| ENTER| Press to store the set parameter value and to scroll to the next parameter on the PAGE.

PV Error Indications

Message PV Error Type
**** Over-range

(PV above Max. Range)
****| Under-range
(PV below Min. Range)
| Open
(Thermocouple / RTD broken)

Contact Information

101, Diamond Industrial Estate, Navghar, Vasai Road (E), Dist. Palghar – 401 210.
Sales:  8208199048 / 8208141446
Support:  07498799226 / 08767395333
E:  sales@ppiindia.net, support@ppiindia.net.

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals