PPI Scanex Plus 8-16 Channel Universal Process Scanner Instruction Manual
- June 11, 2024
- PPI
Table of Contents
PPI Scanex Plus 8-16 Channel Universal Process Scanner
101, Diamond Industrial Estate, Navghar,
Vasai Road (E), Dist. Palghar – 401 210.
Sales : 8208199048 / 8208141446
Support : 07498799226 / 08767395333
E: sales@ppiindia.net,
support@ppiindia.net
This brief manual is primarily meant for quick reference to wiring connections and parameter searching. For more details on operation and application; please log on to www.ppiindia.net
TABLE- 1
Unit Readout| Units
| ° C
| ° F
| Kelvin
| Engineering Units
| Percentage
| Pascals
| Mpascals
| Kpascals
| Bar
| Milli bar
| PSI
| kg/sq cm
| mm water gauge
| Inches water gauge
| mm mercury
| Torr
| Liters per hour Liters per minute
% Relative Humidity
% O 2
% CO 2
% Carbon Potential volts
Amps
| Milli amps
| Milli Volts
| Ohms
| Parts per million
| | | Revolutions per pinute
| Milli seconds
| Seconds
| Minutes
| Hours
| PH
| %PH
| Miles per hour
| Milli grams
| Grams
| Kilo grams
TABLE- 2
Option| Range (Min. to Max.)| Resolution
J Type T/C| 0.0 to +960.0°C / +32.0 to +1760.0°F| 1 °C/°F
or
0.1 °C/°F
K Type T/C| -200.0 to +1376.0°C / -328.0 to +2508.0°F
T Type T/C| -200.0 to +387.0°C / -328.0 to +728.0°F
R Type T/C| 0.0 to +1771.0°C / +32.0 to +3219.0°F
S Type T/C| 0.0 to +1768.0°C / +32.0 to +3214.0°F
B Type T/C| 0.0 to +1826.0°C / +32.0 to +3218.0°F
N Type T/C| 0.0 to +1314.0°C / +32.0 to +2397.0°F
**| Reserved for customer specific Thermocouple type not listed above. The
type shall be specified in accordance with the ordered (optional on request)
Thermocouple type.
3-wire, RTD Pt100| -199 to +600°C / -328 to +1112°F
or
-199.9 to +600.0°C / -328.0 to +1112.0°F| 1 °C/°F
or
0.1 °C/°F
0 to 20mA DC current| -19999 to 30000 units| 1
0.1
0.01
0.001
units
4 to 20mA DC current
0 to 80mV DC voltage
Reserved
0 to 1.25V
DC voltage
0 to 5.0V
DC voltage
0 to 10.0V
DC voltage
1 to 5.0V
DC voltage**
FRONT PANEL LAYOUT
ELECTRICAL CONNECTIONS
Keys Operation
Symbol | Key | Function |
---|---|---|
PAGE | Press to enter / exit Set-up Mode | |
DOWN | Press to decrease the parameter value. Pressing once decreases the |
value by one count; holding the key pressed speeds up the change.
| UP| Press to increase the parameter value. Pressing once increases the value
by one count; holding the key pressed speeds up the change.
| ENTER| Press to store the set parameter value and to scroll to the next
parameter.
| ALARM ACK/VIEW| Press to Acknowledge any pending Alarm(s) and to View
details of the channels under Alarm.
| AUTO / MANUAL| Press to toggle between Auto and Manual Scan Mode. In Manual
Scan Mode, Use UP / DOWN keys to the desired channel.
PV Error Indications
Message | PV Error Type |
---|---|
Over-range (PV above Max. Range) | |
Under-range (PV above Min. Range) | |
Open (Sensor open / broken) |
ELECTRICAL CONNECTIONS
Old Connections Version
8 Channel
16 Channel
New Connections Version
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>