AIRZONE CB-ANT Main Control Board User Manual

June 8, 2024
AIRZONE

AIRZONE CB-ANT Main Control Board

AIRZONE MAIN CONTROL BOARD

Configurable electronic board that controls the system through wired and wireless devices. Externally powered at 110 / 230 Vac. Wall mounted.

Functionalities:

  • Control and management of the thermostats (up to 6 zones).
  • Power outlets for motorized elements.
  • Remote zone on/off module (up to 6 zones).
  • Control of optional auxiliary heat (up to two stages).
  • Control gateway management.
  • Communication with units of integral control of the installation.
  • Communications with other external control systems through integration bus.

For further information about our products, go to myzone.airzone.es

N L

  • V máx. 110/230 Vac
  • I máx. 250 mA
  • Frequency 60/50 Hz
  • Stand-by consumption 400 mW
  • Module over-current protection 250 mA

AZ1 – AZ2 – AZ3 – IU

  • Shielded twisted pair2 x 0,22 + 2 x 0,5 mm2
  • V máx 12 V

DM1

  • Shielded twisted pair 2 x 0,22 + 2 x 0,5 mm2
  • Communications protocol  MODBUS RS-485 Par – 19200 bps

Communications via radio

  • Communications protocol Airzone
  • Frequency  868.12 MHz (CEE) 915.2 MHz (EEUU, Canada, Austrialia, Nueva Zelanda)
  • Radiation power 5 dBm
  • Maximum distance in open space  40 m

M1 … M6

  • Nº of outputs
  • Maximum number of outputs per damper  2
  • V max 12 V
  • I max 150 mA

O1 – O2

  • Nº of relays 2
  • V max 24 Vdc / 48 Vdc
  • I max 1 A

Operating temperatures

  • Storage -20 … 70 ºC
  • Operation0 … 50ºC

Mechanical aspects

  • Protection class IP 21
  • Weight  616 g

DEVICE ELEMENTS

Description
  • AZ1/2/3
    Airzone connection bus

  • P3 Wireless module

  • SW1 SW1

  • DM1  Automation bus

  • IU  AC unit bu

  • M1…M6 Actuator outputs

  • DI1
    Alarm input (normally close)

  • AI1 Temperature probe

  • O1
    Auxiliary heat stage 1 output

  • O2
    Auxiliary heat stage 2 output

  • N L Power

  • ON/OFF
    Contact on/off (optional)

ASSEMBLY

This device complies with FCC / ISED regulatory notices.

SELFDIAGNOSIS

AIRZONE CB-ANT Main Control Board-10 AIRZONE
CB-ANT Main Control Board-11

CONNECTION

Do not connect the “-“ pole to the “+” terminal. It may damage the device.

  • Neutral

  • Phase

  • Ground

  • + Blanco

  • B lack/Brown I

  • Type Airzone Central V1.3

  • Licence 215562

  • Application
    Variable air volume system (without h/c coil)
    Heating    Cooling

  • Control accuracy (K)     0.3          0.3

AIRZONE CB-ANT Main Control Board-09

  • A Blue
  • – Black
  • B Green
  • + Red