Acuity Brands Private Restroom Enabled nLight User Guide

June 4, 2024
Acuity Brands

Acuity Brands Private Restroom Enabled nLight logo

Acuity Brands Private Restroom Enabled nLight

Acuity Brands Private
Restroom Enabled nLight product

SEQUENCE OF OPERATION

LIGHTS

  • ALL LIGHTS ARE DIMMABLE
  • FIXTURES ARE CONTROLLED BASED ON POWER PACK LINE VOLTAGE AND 0-10V WIRING
  • THE MAXIMUM LEVEL CAN BE TASK TUNED TO ANY PERCENTAGE VIA PROGRAMMING

OCCUPANCY

  • PARTIAL-ON OCCUPANCY SENSORS AUTOMATICALLY ACTIVATE BETWEEN 50-70%OF CONTROLLED LIGHTING POWER OR FIXTURES MUST BE TURNED ON MANUALLY

DAYLIGHT

  • NOT REQUIRED IF ROOM HAS <24 FT2. OF GLAZING OR LIGHTING LOAD< 120W IN THE SKYLIT AND THE SIDELIT DAYLIT ZONE
  • SMOOTH CONTINUOUS DIMMING
  • DAYLIGHT ZONES DEFINED BY RELAY PACKS

MANUAL

  • ON/OFF & RAISE/LOWER CONTROL OF FIXTURES

ADDITIONAL OPTIONS

  • THE ROOM CAN BE CONNECTED TO THE NIGHT BACKBONE TO ENABLE NETWORK CONTROL, TIME SCHEDULES, AND AUTOMATED DEMAND RESPONSE (OPENADR 2.0A)
  • HVAC CONTROL AVAILABLE THROUGH THE SYSTEM-WIDE BACNET® INTERFACE OPTION ON THE EGL YPSE® CONTROLLER
  • WIRELESS FIXTURE EMBEDDED CONTROL AND OCCUPANCY/DAYLIGHTING SENSOR OPTIONS AVAILABLE, PLEASE SEE THE FIXTURE SPECIFICATION SHEET

Acuity Brands Private Restroom Enabled nLight fig 2

SUPPORTS THE FOLLOWING REQUIREMENTSAcuity Brands Private Restroom Enabled
nLight fig 3 Note: Contact your local lighting agent for more information on nlight enabled fixtures