Acuity Brands Public Restroom 0-10 nLight User Guide
- June 4, 2024
- Acuity Brands
Table of Contents
Acuity Brands Public Restroom 0-10 nLight
SEQUENCE OF OPERATION
LIGHTS
- ALL LIGHTS ARE DIMMABLE
- FIXTURES ARE CONTROLLED BASED ON POWER PACK LINE VOLTAGE AND 0-10V WIRING
- MAXIMUM LEVEL CAN BE TASK TUNED TO ANY PERCENTAGE VIA PROGRAMMING
OCCUPANCY
- PARTIAL-ON OCCUPANCY SENSORS AUTOMATICALLY ACTIVATE BETWEEN 50-70% OF CONTROLLED LIGHTING POWER OR FIXTURES MUST BE TURNED ON MANUALLY
DAYLIGHT
- NOT REQUIRED IF ROOM HAS <24 FT2. OF GLAZING OR LIGHTING LOAD< 120W IN THE SKYLIT AND THE SIDELIT DAYLIT ZONE
- SMOOTH CONTINUOUS DIMMING
- DAYLIGHT ZONES DEFINED BY RELAY PACKS
MANUAL
- ON/OFF & RAISE/LOWER CONTROL OF FIXTURES
ADDITIONAL OPTIONS
- ROOM CAN BE CONNECTED TO NLIGHT BACKBONE TO ENABLE NETWORK CONTROL, TIME SCHEDULES AND AUTOMATED DEMAND RESPONSE (OPENADR 2.0A)
- HVAC CONTROL AVAILABLE THROUGH SYSTEM-WIDE BACNET® INTERFACE OPTION ON THE ECL YPSE® CONTROLLER
- WIRELESS FIXTURE EMBEDDED CONTROL AND OCCUPANCY/DAYLIGHTING SENSOR OPTIONS AVAILABLE, PLEASE SEE THE FIXTURE SPECIFICATION SHEET
SUPPORTS THE FOLLOWING REQUIREMENTS
- FULL AUTO-OFF VIA OCCUPANCY SENSOR (SECTION 130.1c)
- .I LOCAL SWITCH .,., (SECTION 130.1a)
- MUL TI-LEVEU DIMMING CONTROL (SECTION130.1b)
- AUTOMATIC DEMAND RESPONSE(ADR)READY (SECTION 130.1e)