CATTLE 24 2022 DESIGN GUIDE
WIRELESS LoBBY WITH NLIGHT AIR ENABLED FIXTURES
SEQUENCE OF OPERATION:
LIGHTS
- ALL LIGHTS ARE DIMMABLE
- ALL FIXTURES CAN BE CONTROLLED
- TOGETHER OR INDEPENDENTLY
- MAXIMUM LEVEL CAN BE TASK TUNED TO ANY
- PERCENTAGE VIA PROGRAMMING
OCCUPANCY
- PARTIAL-ON OCCUPANCY SENsORS
- AUTOMATICALLY ACTIVATE BETWEEN 50-70%
- OF CONTROLLED LIGHTING POVWER OR FIXTURES
- MUST BE TURNED ON MANUALLY
- PLUG LOAD TURNS OFF AUTOMATICALLY
- FIXTURES AND PLUG LOAD AUTOMATICALLY
- TURN OFF WHEN ROOM BECOMES VACANT
DAYLIGHT
- NOT REQUIRED IF ROOM HAS <24 FT2. OF
- GLAZING OR LIGHTING LOAD 120W IN THE
- SKYLIT AND THE SIDELIT DAYLIT ZONE
- SMOOTH cONTINUOUS DIMMING
- DAYLIGHT ZONES DEINED BY RELAY PACKS
MANUAL
- ON/OFF& RAISELOWER CONTROL OF FIXTURES
ADDITIONAL OPTIONS
- ROOM CAN BE CONNECTED TO NLIGHT
- BACKBONE TO ENABLE NETWwORK CONTROL,
- TIME SCHEDULES AND AUTOMATED DEMAND
- RESPONSE (OPENADR 2.0A)
- HVAC CONTROL AVAILABLE THROUGH
- SYSTEM-WIDE BACNET® INTERFACE OPTION ON
- THE ECLYPSE® CONTROLLER
- WIRELESS FIXTURE EMBEDDED CONTROL AND
- OCCUPANCY/DAYLIGHTING SENSOR OPTIONS
- AVAILABLE, PLEASE SEE THE FIXTURE
- SPECIFICATION SHEET
SUPPORTS THE FOLLOWING REQUIREMENTS
- FULL AUTO-OFF VIMA OCCUPANCY SENSOR (SECTION 130.1c)
- AREA CONTROL (SECTION 130.1a)
- MULTI-LEVEL/ DIMMING CONTROL (SECTION 130.1b)
- AUTOMATIC DEMAND RESPONSE (ADR) READY (SECTION 130.1e)”
- MULTI-LEVEL DAYLIGHT CONTROL SECTION 130.1d)
Note: Contact your local lighting agent for more information on nLight-enabled fixtures