Acuity Brands Gymnasium Enabled nLight AIR T24 2022 User Guide

June 4, 2024
Acuity Brands

Acuity Brands Gymnasium Enabled nLight AIR T24 2022
logo

Acuity Brands Gymnasium Enabled nLight AIR T24 2022

SEQUENCE OF OPERATION

Acuity Brands Gymnasium Enabled nLight AIR T24
2022 fig 1

LIGHTS

  • ALL LIGHTS ARE DIMMABLE
  • THE MAXIMUM LEVEL CAN BE TASK TUNED TO ANY PERCENTAGE VIA PROGRAMMING

OCCUPANCY

  • PARTIAL-ON OCCUPANCY SENSORS AUTOMATICALLY ACTIVATE BETWEEN 50-70% OF CONTROLLED LIGHTING POWER OR FIXTURES MUST BE TURNED ON MANUALLY
  • FIXTURES AUTOMATICALLY TURN OFF WHEN ROOM BECOMES VACAN

DAYLIGHT

  • NOT REQUIRED IF ROOM HAS <24 FT2. OF GLAZING OR LIGHTING LOAD < 120W IN THE SKYLIT AND THE SIDELIT DAYLIT ZONE
  • SMOOTH CONTINUOUS DIMMING
  • DAYLIGHT ZONES ARE DEFINED BY RELAY PACKS MANUAL
  • ON/OFF & RAISE/LOWER CONTROL OF LIGHTS

ADDITIONAL OPTIONS

  • ROOM CAN BE CONNECTED TO NLIGHT BACKBONE TO ENABLE NETWORK CONTROL, TIME SCHEDULES AND AUTOMATED DEMAND RESPONSE (OPENADR 2.0A)
  • HVAC CONTROL AVAILABLE THROUGH SYSTEM-WIDE BACNET® INTERFACE OPTION ON THE ECL YPSE CONTROLLER OR THROUGH OCCUPANCY SENSOR AUXILIARY RELAY (AR) CONTACT OPTION
  • WIRELESS FIXTURE EMBEDDED CONTROL AND OCCUPANCY/DAYLIGHTING SENSOR OPTIONS AVAILABLE,
    PLEASE SEE THE FIXTURE SPECIFICATION SHEET

Fixture(s) assumed to include the emergency option.
For the battery backup option, no dedicated EM circuit is necessary.Acuity
Brands Gymnasium Enabled nLight AIR T24 2022 fig 2

SUPPORTS THE FOLLOWING REQUIREMENTS:Acuity Brands Gymnasium Enabled
nLight AIR T24 2022 fig 3 Note: Contact your local lighting agent for more information on nlight-enabled fixtures