resideo D04FM Standard Pattern Pressure Reducing Valve Instruction Manual
- June 8, 2024
- resideo
Table of Contents
Braukmann D04FM
Installation instructions
Pressure Reducing Valve
Safety Guidelines
-
Follow the installation instructions.
-
Use the appliance
• according to its intended use
• in good condition
• with due regard to safety and risk of danger. -
Note that the appliance is exclusively for use in the applications detailed in these installation instructions (see 2 Technical Data). Any other use will not be considered to comply with requirements and would invalidate the warranty.
-
Please take note that any assembly, commissioning, servicing and adjustment work may only be carried out by authorized persons.
-
Immediately rectify any malfunctions which may influence safety.
Technical Data
Media|
---|---
Medium: Connections/Sizes| Drinking water
Connection sizes:| 3/8″, 1/2″, 3/4″
Nominal sizes:| 10, 15, 20
Pressure values|
Max. inlet pressure:| 16 bar
Outlet pressure:| 1.5 – 6 bar
Min. pressure drop:| 1 bar
Operating temperatures
Max. operating temperature medium (10 bar):| 70 °C
Max. operating temperature medium accord. to EN 1567:| 30 °C
Assembly
3.1 Installation Guidelines
-
Horizontal and vertical installation position possible
– In vertical installation position spring bonnet with adjustment knob facing upwards -
Install shut-off valves
-
The installation location should be protected against frost and be easily accessible
– Pressure gauge can be read off easily
– Simplified maintenance and cleaning -
To guarantee perfect functioning, a filter must be inserted ahead of the pressure reducing valve
-
Provide a straight section of pipework of at least five times the nominal valve size after the pressure reducing valve (in accordance with EN 806-2)
-
Requires regular maintenance in accordance with EN 806-5
3.2 Assembly instructions
CAUTION!
When using soldering connections, do not solder the connections together with
the pressure reducing valve! High temperature will irreparably damage
important internal working components!
-
Thoroughly flush pipework
-
Install pressure reducing valve
• Note flow direction
• Install without tension or bending stresses -
Set outlet pressure
The green adjustment knob must stay plugged on to prevent dirt from entering.
Start-up
4.1 Setting outlet pressure
Set outlet pressure min. 1 bar under inlet pressure.
-
Close shut-off valve on inlet
-
Release pressure on outlet side (e.g. through water tap)
-
Fit manometer (standard version)
-
Close shut-off valve on outlet
-
Fit adjustment knob
-
Slacken tension in compression spring
• Turn adjustment handle counter clockwise (-) until it does not move any more -
Slowly open shut-off valve on inlet
-
Turn adjuster knob until the manometer shows the desired value
-
Slowly open shut-off valve on outlet
Maintenance
In order to comply with EN 806-5, water fixtures must be inspected and serviced on an annual basis. As all maintenance work must be carried out by an installation company, it is recommended that a servicing contract should be taken out.
In accordance with EN 806-5, the following measures must be taken:
5.1 Inspection
-
Close shut-off valve on outlet
-
Check outlet pressure using a pressure meter when there is zero through-flow
• If the pressure is increasing slowly, the valve may be dirty or defective. In this instance, carry out servicing and cleaning (See 5.2 Maintenance) -
Slowly open shut-off valve on outlet
5.2 Maintenance
Do not use any cleansers that contain solvents and/or alcohol for cleaning the
plastic parts, because this can cause damage to the plastic components – water
damage could result.
Detergents must not be allowed to enter the environment or the sewerage
system!
-
Close shut-off valve on inlet
-
Release pressure on outlet side (e.g. through water tap)
-
Close shut-off valve on outlet
-
Fit adjustment knob
CAUTION!
There is a spring in the spring bonnet. It may cause injuries if the spring is derailing.
Make sure tension in compression spring is slackened! -
Slacken tension in compression spring
• Turn adjustment handle counter clockwise (-) until it does not move any more -
Unscrew spring bonnet
-
Remove valve insert with a pair of pliers
-
Remove filter and clean
-
Check that sealing ring, edge of nozzle and ’o’-ring are in good condition, and if necessary replace the entire valve insert
-
Reassemble in reverse order
Press in diaphragm with finger before inserting slip ring -
Set outlet pressure
Disposal
Observe the local requirements regarding correct waste recycling/disposal!
Troubleshooting
Problem | Cause | Remedy |
---|---|---|
Beating sounds | Pressure reducing valve is too large | Call our Technical |
Customer Services
Water is escaping from the spring bonnet| Diaphragm in valve insert is faulty|
Replace valve insert
Too little or no water pressure| Shut-off valves up- or downstream of the
pressure reducing valve are not fully open| Open the shut-off valves fully
Pressure reducing valve is not set to the desired outlet pressure| Set outlet
pressure
Filter in pressure reducing valve is contaminated| Clean or replace filter
Pressure reducing valve is not fitted in flow direction| Fit pressure reducing
valve in flow direction (note direction of arrow on housing)
The outlet pressure set does not remain constant| Filter in pressure reducing
valve is contaminated or worn| Clean or replace filter
Valve insert, sealing ring or edge of nozzle is contaminated or worn| Replace
valve insert
Rising pressure on outlet (e.g. in boiler)| Check check valve, safety group
etc.
Spare Parts
For Spare Parts visit homecomfort.resideo.com/europe
Accessories
For Accessories visit homecomfort.resideo.com/europe
Strandvejen 42 • Saksild
• 8300 Odder 86 62 63 64
• www.automatikcentret.dk
info@automatikcentret.dk
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>