aerauliqa WHS400 WHS Range Ceiling High Volume Low Speed Fan Instruction Manual

September 19, 2024
aerauliqa

aerauliqa WHS400 WHS Range Ceiling High Volume Low Speed Fan

Product Information

Specifications:

  • Model: WHS Ventilatori da soffitto ad alte prestazioni (HVLS)
  • Power Supply: 400Vac, 50Hz

General Warnings
Read the instructions in the manual carefully. This Specific Manual must be read together with the General Installation, Use, and Maintenance Manual. Keep the manual for future reference. Installation, electrical connections, and maintenance should be carried out by a qualified and authorized installer in accordance with local regulations.

Specific Warnings
Use the specified torque values for tightening all hardware with the indicated thread sizes.

Typology
No specific information provided in the manual excerpt.

Key Features
The WHS series offers high-performance ceiling fans with various power and airflow capabilities.

Data @400Vac, 50Hz

Model Max Speed (r/min) Power Consumption (max kW) Max Thrust (N)
WHS400 120 0.8 272
WHS500 105 1.1 366
WHS600 84 1.4 302

Dimensions and Distances
Detailed dimensions, distances, and installation requirements are provided for each model in the WHS series.

Product Usage Instructions

Installation
Follow the detailed installation instructions provided in the manual for proper setup of the WHS series ceiling fans.

Electrical Connection Schemes
Refer to the specific electrical connection schemes for accessories such as CTRL-A, CTRL-XHS, CTRL-XWS, CTRL-XTHI, and external potentiometer control.

Cleaning
Regularly clean the fan blades and housing to maintain optimal performance.

Troubleshooting
Refer to the troubleshooting section for guidance on resolving common issues related to connection parameters, Modbus registers, alarm codes, LED status, and issue resolution.

Frequently Asked Questions (FAQ):

  1. Can I install the WHS series fans myself?
    It is recommended to have a qualified and authorized installer perform the installation to ensure safety and proper setup.

  2. How often should I clean the WHS ceiling fan?
    Regular cleaning is advised to prevent dust buildup and maintain efficient operation. The frequency may vary based on usage environment.

GENERAL INFORMATION

Carefully read the instructions contained in this manual.
This Specific Manual MUST be read in conjunction with the “Installation, Operation and Maintance General Manual”. Note: store the manual for future reference. We reserve the right to improve and make changes to the manual, products and accessories without any obligation to update previous productions and manuals.
The installation and service of the unit and complete ventilation system must be performed by an authorized installer and in accordance with local rules and regulationid.

PRECAUTIONS

In addition to the precautions indicated in the “Installation, Operation and Maintenance General Manual” special attention should be paid to the following warning notes:

  • The fan must be installed at a height of not less than 2.7m from the floor below. Installation at a lower height is considered “improper use”. In case of “improper use” the manufacturer declines all responsibility for any damage that may be caused to persons or property, and any warranty will be considered invalid.
    RECOMMENDED BOLT TORQUE FOR COARSE THREADED METRIC STEEL BOLTS TE-TCEI GRADE 8.Dimensions| M6| M8| M10| M12| M14| M16
    ---|---|---|---|---|---|---
    Nm| 9,5| 23| 46| 79| 127| 198

Table 1 Use the values shown in the table to tighten all the screws.

  • fixing: check/inspect and eventually retighten all the fixing annually.
  • windy conditions: fans should not operate in case of strong wind (6m/s) and should not be installed in places where it is frequently windy.
  • weight: it is recommended that the building structure is capable to bear approx. twice the weight of the fan as well as a torque of at least 350Nm. A professional structural engineer should perform an evaluation before installing the fan.
  • key safety features: make sure that all the supplied key safety features are used to install the fan to provide a comprehensive protection of people, animals, equipments and property.

The installer and the building owner are responsible to ensure the safety of the fan mounting system and that the fan installation is correct, in compliance with any national and local regulations.

TYPE

Ceiling fans with EC brushless motor designed for industrial, civil and zootechnical applications, where high performance with low rotation speed are required.

MAIN FEATURES

  • Brushless motor 380-440Vac, 3ph, 50/60Hz, IP55
  • Max temperature +50°C
  • Speed controllable
  • Suitable for S1 continuous service
  • Embedded electronic system
  • Extruded aluminium blades
  • Gearless for silent operation
  • Maintenance-free
  • Key Safety features
  • Simplified electrical wiring connection
  • Strong and robust design and manufacturing

DATA @400Vac, 50Hz

Model

| No blades| Max speed rotation| Max absorbed power| Max Thrust| Max airflow AMCA 230-15| Max airflow AMCA 230-99
---|---|---|---|---|---|---
 |  | r/min| kW| N| cfm| m3/h| SPI(1)

W/(m3/s)

| cfm| m3/h| SPI(1)

W/(m3/s)

WHS400| 5| 120| 0.8| 272| 113086| 192133| 15.0| 159927| 271717| 10.6
WHS500| 5| 105| 1.1| 366| 152319| 258791| 16.0| 215412| 365986| 11.3
WHS600| 5| 84| 1.4| 302| 178738| 303677| 16.6| 252774| 429464| 11.7

DIMENSIONS AND CLEARANCES

Model

|

ØA

|

B

max ceiling slop

| C

min safety distance from side obstacle

| D

fan height with standard downrod

| E

standard downrod length

| h min fan

installation height

|

Weight

---|---|---|---|---|---|---|---
 | mm| >°| mm| mm| mm| mm| kg
WHS400| 4000|

20

| 450|

1300

|

800

|

2700

| 105
WHS500| 5000| 550| 127
WHS600| 6000| 650| 143

COMPONENTS

  • The fan is delivered split into two kits, each one in its own box.
  • MOTOR KIT includes:
    • main body (Fig.VIII – 15).
    • standard 800mm length downrod (Fig.II – 6).
    • 2x ceiling fixing brackets (Fig.III – 7 e Fig. IV).
    • 2x fixings sets:
    • 4x M12 bolts (Fig.III and VIII – 8), 4x flat washer (Fig.III and VIII – 9), 4x spring washers (Fig.III and VIII – 10) and 4x locknuts (Fig.III and VIII – 11) for downrod fixing.
    • 10x M8 flange bolts (Fig.XIV – 20), 10x spring washers (Fig.XIV – 21),10x locknuts (Fig.XIV – 22) and 10x plastic caps (Fig.XIV – 23), to fix the blades to the main body.
    • plastic components set: hub cover (Fig.XV – 24), 5x M4 bolts (Fig.XV – 25), canopy (Fig. VI – 13) and 4x self-tapping screw (Fig.VI – 14).
    • security wires set: 1x Ø5mm 2,5m security wire with one ring (Fig.I and II – 1), 1x Ø5mm 0,35m wire with two rings (Fig.I – 3), 2x 5mm clamp (Fig.V – 12), 2x 7mm snap-hook (Fig.I – 4), 1x shackle (Fig.I – 2) for the security wire; 4x Ø3mm stabilizing wires with turnbuckle (Fig.XI – 16), 4x 5mm snap-hooks (Fig.XI – 17) and 8x 3mm clamp (Fig.XIII – 18), for the stabilizing wires.
  • BLADES KIT incudes five blades (Fig.XIV – 19).
  • The electrical wire type (Fig.II e XVI – 5, not supplied) must comply with the local regulations of the electric system and must have the following features:
    • 4 core supply power cable (one cable section ≥ 1mm2)
    • Multicore control cable (one cable section ≥ 0.5mm2)
      Note: the voltage drop cannot be higher than 4%.

INSTALLATION

  • Decide on the position the fan is to be sited keeping in consideration as follows:

    • the minimum distance from the floor to the lowest point of the fan is 2.7m.
    • the minimum distance from the fan blade to the side wall of similar obstruction depends on the fan model (§ 6 – C).
    • avoid mounting the fan directly below lights to prevent any strobe effect caused by the moving blades.
    • in any installation where fire sprinklers are placed, fan should not interfere with their operation.
    • fan should not be placed near to supply air outlet or exhausting inlets of other HVAC equipment which could decrease the fan capacity and compromise the indoor air quality as well as the occupants’ comfort:
    • supply air outlet should deliver air away from the unit.
    • exhaust fan inlets or other return air point which could create negative pressure should not be located within 1,5 times the fan diameter.
    • when mounting the fan, mark the floor with a large cross-hatched circle to alert people of the overhead fan location.
  • Compose the security cable set consisting of: Ø5mm wire of 2.5m length (1), 0.33t shackle (2), Ø5mm wire of 0.35m length with two rings (3)and 7mm snap-hook (4).

  • Insert the security wire (1) and electric cables (5 – not supplied) into the downrod (6).

  • Fix the downrod (6) to the ceiling brackets (7) by means of the M12 bolts (8), the flat washer (9), the spring washers (10) and the locknuts (11).

  • Fix the assembly to the ceiling/beam through the 8 holes on the brackets (7) and fix the security wire (1) to the ceiling/beam using the clamps (12). Fixing screws/plugs are not supplied.

  • Fix the canopy (13) at the top, using the supplied self-tapping screws (14).

  • Remove from the main body the three transport feet (15) (Fig.VII), by unscrewing the bolts, washers and locknuts

  • Fix the main body (15) to the downrod (6) using the M12 bolts (8), the flat washer (9), the spring washers (10) and locknuts (11).

  • Connect the electric cables (5) to the motor through the front cable grommets, by removing the upper door to access the internal terminal block.

  • Let out the safety wire (1) laterally, hooking the snap-hooks (4) to the eyebolts on the motor, verifying the correct tightening.

  • Connect the Ø3mm stabilizing wires with the turnbuckle (16) to the motor support using the 5mm snap-hooks (17) and stabilise the fan; securely fix the other end of the stabilizing wires to the ceiling using the clamps (18). Fixing screws for the ceiling/ beam are not supplied.

  • Insert the blade (19) over the blade root, lock it with the M8 flange bolts (20), spring washers (21) and locknuts (22). Tighten the screws making reference to table 1. Mount the plastic caps (23) on the locknuts.
    Mount the plastic blade terminals (24) using the appropriate screws (25).

  • Mount the plastic cover (24) under the hub using the M4 bolts (25); in case water is used for washing, drill a hole in the plastic cover for water drainage.

  • Make the connection to the power supply/control network by connecting the wired cables (5) to the motor through a junction box (not supplied) to be placed near the ventilation unit. Size the cables appropriately taking into account the distance between the ventilation unit and the power supply point. The complete electrical system must be carried out by a qualified and authorized installer, in accordance with the local requirements.

WIRING DIAGRAM

  • Make sure that the mains supply to the unit is disconnected before performing any installation, service, maintance or electrical work!
  • The installation and service of the unit and complete ventilation system must be performed by an authorized installer and in accordance with local rules and regulations.
  • Fan must be earthed.

The fans are supplied with the termination resistor disabled (no bridge between terminals 4 and 6 on the motor board). To reduce possible signal degradation it is recommended to enable the terminating resistor (bridge between terminals 4 and 6 on motor board) of the last fan connected to the communication line. In all cases where this is not necessary or appropriate, it is recommended to check that the terminating resistor is disabled.

WARNING: regardless of the control system in place (analogic or ModBus), it’s strongly recommended to wire the ModBus communication line and make it accessible from ground level, in order to ease troubleshooting via ModBus anytime after the installation.

CTRL-A (accessory on request)

CTRL-HS (accessory on request)

For functionalities, refer to the dedicated manual of the CTRL-HS touch control panel.

CTRL-XWS (accessory on request)

CTRL-XTHI (accessory on request)

CONTROL WITH EXTERNAL POTENTIOMETER (not supplied)

CLEANING

The unit (IP55) can be washed with water jets. In this case it is recommended to drill a hole under the plastic hub cover for water drainage.

TROUBLESHOOTING

Connection parameters

Protocol MODBUS/RTU over RS485
Baud Rate (bps) 9600
Data bits 8
Parity bits none
Stop bits 2
HVLS Slave Address 1

Modbus Registers – Input Register
These registers are READ-ONLY, and can be read using the function 04 READ INPUT REGISTERS.

Register Address| __

Description

| Dimension (Word)| Data Type| U.M. (data on the register)| Example

Register valueReal value

---|---|---|---|---|---
3| Measured speed| 1| ushort| 0.1rpm| 490 → 49rpm
10| Alarm 1| 1| ushort| –| See table (§ 11.3)
17| Alarm 2| 1| ushort| –| See table (§ 11.3)

Alarm codes/LED status/Troubleshooting

ALARM 1 VALUE

|

ALARM 2 VALUE

|

ALARM DESCRIPTION POSSIBLE CAUSE

|

TROUBLESHOOTING

---|---|---|---
0| 0| No error| –
1| 0| Memory error – motor parameters lost| Contact manufacturer/technical support
2| 0| Short circuit – electronics power module damaged| Board damaged – replace board

3

|

0

|

Motor synchronization lost – wrong motor parameters or electronics damaged

| Check motor windings.

If motor windings OK (all 3 windings have same resistance), replace board.

If motor windings damaged (open/short circuit), replace motor.

4

|

32

| Over voltage: supply voltage above 565Vac (DC bus voltage over 800V) during motor running| Check power supply voltage check power supply wiring

4

|

33

| Under voltage: supply voltage below 212Vac (DC bus voltage below 300V) during motor running| Check power supply voltage check power supply wiring
4| 113| Electronics temperature over 85°C (check input register 15)| Check if operating temperature is above rated maximum operating temperature.

Check mechanical load for anomalies (e.g. difficult turning)

4| 114| Motor windings temperature over 125°C (check input register 16)| Check if operating temperature is above rated maximum operating temperature.

Check mechanical load for anomalies (e.g. difficult turning)

For additional information on HVLS Modbus control, contact the manufacturer/technical support.

DECLARATION OF CONFORMITY AND INCORPORATION

UE DECLARATION OF CONFORMITY/INCORPORATION
Manufacturer: AERAULIQA SRL Via Mario Calderara 39/41 – 25018 Montichiari (BS) – ITALY

UE DECLARATION OF CONFORMITY
We herewith declare that the following range:

WHS series ceiling fans

  • BRAND: AERAULIQA
  • MODELS: WHS400, WHS500, WHS600

on the basis of its design and construction as partly completed machines brought onto the market, is designed in compliance within relevant health and safety requirements of the following Directives:

  • 2014/35/UE – Low Voltage Directive (LVD)
  • 2014/30/UE – Electromagnetic Compatibility (EMC)
  • 2009/125/EC – Energy Related Products (ErP)

in the event that alterations are made to the machinery without prior consent with the manufacturer, this declaration becomes invalid. This declaration is issued under the sole responsibility of the manufacturer.

UE DECLARATION OF INCORPORATION
In accordance with the Machinery Directive 2006/42/EC.

We herewith declare that the following range:
WHS series ceiling fans

BRAND: AERAULIQA
MODELS: WHS400, WHS500, WHS600

on the basis of its design and construction of partly completed machines, is designed in compliance with the Essential Health and Safety Requirements (EHSRs) of ANNEX l, sections 1.1.2 (Safety integration), 1.1.5 (Handling), 1.4.1 (Protective devices), 1.5.1 (Electricity) of EC Machinery Directive 2006/42/EC.
The machinery is incomplete and must not be put into service until such time as the machinery which is partly complete is to be incorporated and has been assessed and declared in conformity with the provisions of the Machinery Directive 2006/42/EC.
We undertake to transmit, upon a reasoned request by appropriate national authorities, relevant information on the partly completed machinery identified above.

During installation, it is recommended to write the serial number of the unit in this manual and keep it safe for maintenance service.

Via Mario Calderara 39/41, 25018 Montichiari (Bs)
C.F. e P.IVA/VAT 03369930981 – REA BS-528635
Tel: +39 030 674681
Fax: +39 030 6872149
www.aerauliqa.it
www.aerauliqa.com
info@aerauliqa.it 

Aerauliqa S.r.l. reserves the right to modify/make improvements to products and/or this instruction manual at any time and without prior notice.

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

aerauliqa User Manuals

Related Manuals