aerauliqa CTRL-XTHI Instruction Manual

June 4, 2024
aerauliqa

aerauliqa-CTRL-XTHI-logo

aerauliqa CTRL-XTHI

Read this manual carefully before using the product and keep it in a safe place for reference. This product was constructed up to standard and in compliance with regulations relating to electrical equipment and must be installed by technically qualified personnel. The manufacturer assumes no responsibility for damage to persons or property resulting from failure to observe the regulations contained in this booklet.

PRECAUTIONS

  • Make sure that the mains supply to the unit is disconnected before performing any installation, service, maintenance or electrical work!
  • The installation and service of the unit and complete ventilation system must be performed by an authorized installer and in accordance with local rules and regulations.
  • If any abnormality in operation is detected, disconnect the device from the mains supply and contact a qualified technician immediately.
  • This appliance can be used by children aged from 8 years and above and persons with reduced physical, sensory or mental capabilities or lack of experience and knowledge if they have been given supervision or instruction concerning use of the appliance in a safe way and understand the hazards involved. Children shall not play with the appliance. Cleaning and user maintenance shall not be made by children without supervision.
  • For installation an omni polar switch should be incorporated in the fixed wiring, in accordance with the wiring regulations, to provide a full disconnection under overvoltage category III conditions (contact opening distance equal to or greater than 3mm).
  • A wrong electrical wiring can cause damage to the fan and interfere with other electronic devices.
  • Incorrect connection of the humidity probe can lead to its breakage. The humidity probe is sensitive to direct bright light and should therefore be installed in sheltered and protected areas.

TYPE

Controller for ventilation unit based on temperature or THI levels, and showers control.

WIRING DIAGRAM

  • 1= POWER SUPPLY 220Vac
  • 2= POWER SUPPLY 220Vac
  • 3= Pr2…. TEMPERATURE PROBE
  • 4= GND-… TEMPERATURE PROBE
  • 4= GND-… HUMIDITY PROBE (GREEN)
  • 5= Pr1 … HUMIDITY PROBE SIGNAL (BROWN)
  • 6= +12… 12Vdc POWER SUPPLY OF HE HUMIDITY PROBE (WHITE)
  • 7= NO… NO CONTACT AUX VENTILATION ON/OFF
  • 8= C… COMMON AUX VENTILATION ON/OFF
  • 9= NC… NC CONTACT AUX VENTILATION ON/OFF
  • 12= NO… NO CONTACT SHOWERS (H2O)
  • 13= C… COMMON SHOWERS (H2O)
  • 14= NC… NC CONTACT SHOWERS (H2O)
  • 18= GND-… – 0 FAN SIGNAL OUTPUT
  • 19= +10V… +10Vcc FAN SIGNAL OUTPUT

aerauliqa-CTRL-XTHI-01

HUMIDITY PROBE
Incorrect connection of the humidity probe can lead to its breakage. The humidity probe is sensitive to direct bright light and should therefore be installed in sheltered and protected areas.

FUNCTIONALITIES

INDICATORS OF THE SYSTEM STATUS

aerauliqa-CTRL-XTHI-02

SETTING OF TEMPERATURE / THI FOR VENTILATION (0-10V)
  • Press  (the led on the button flashes): the message SET_ = 22°/67 is displayed – Setting of temperature (°C/°F) to start 0-10V ventilation.
  • Press -or to change the value.
  • Press (the led on the button flashes): the message SET  = 30°/80 is displayed – Setting of the temperature (°C/°F) / THI of max 0-10V ventilation.
  • Press or  to change the value.
  • Press (the led on the button flashes): the message OUT = 0% is displayed – Reading of 0-10V output (%).
  • Press (to exit (the led on the button is off).
SETTING OF TEMPERATURE / THI FOR AUX VENTILATION (ON/OFF)
  • Press (the led on the button flashes): the message AUS = 10°/71 is displayed – Setting of temperature (°C/°F) / THI to start auxiliary ventilation (ON/OFF).
  • Press or to change the value.
  • Press to exit (the led on the button switches is off).

When the AUX ventilation is activated, the ON led switches on

SETTING OF TEMPERATURE / THI FOR SHOWERS (H2O)

It is possible to set up to 4 configurations:

  • Press (the led on the button flashes): the message H.St.1 = 26°/72 is displayed – Setting of temperature (°C/°F) / THI to start time-controlled shower 1 (ON 1 / OFF 1).
  • Press or to change the value.
  • Press (the led on the button flashes): the message H.St.2 = 28°/74 is displayed – Setting of temperature (°C/°F) / THI to start time-controlled shower 2 (ON 2 / OFF 2).
  • Press or to change the value.
  • Press (the led on the button flashes): the message H.St.3 = 30°/76 is displayed – Setting of temperature (°C/°F) / THI to start time-controlled shower 3 (ON 3 / OFF 3).
  • Press or to change the value.
  • Press (the led on the button flashes): the message H.St.4 = 32°/80 is displayed – Setting of temperature (°C/°F) / THI to start time-controlled shower 4 (ON 4 / OFF 4).
  • Press or to change the value.

The activation / deactivation of the showers is indicated through the indicators

SETTING OF THE CONSTANT DATA
  • Press contemporaneously and : the word CONF. is displayed.
  • Press to scroll the setting menu.
  • Parameters:
  • SP. Lo = % of minimum speed
  • SP Hi = % of the maximum speed
  • Star = % minimum starting speed
  • B Lo. V. = stop / limitation of 0-10V ventilation
  • 0 = deactivated (no 0-10V ventilation block)
  • 1 = activated (when showers start the 0-10V ventilation turns off or is reduced)
  • T. Dec. = early switch-off time of ventilation when showers start (0-120 sec)
  • L. Min. = min. ventilation (%) when showers start (0-100%)
AUX VENTILATION SETTING
  • Press contemporaneously and : the word CONF. is displayed.
  • Press to scroll the setting menu.
  • BL.AU. = Stop of the auxiliary ventilation when showers start
  • 0 = deactivated (no auxiliary ventilation block)
  • 1 = activated (when showers start, the auxiliary ventilation switches off)
SHOWERS CONFIGURATION (H2O)
  • Press contemporaneously and : the word CONF. is displayed.
  • Press to scroll the setting menu.
  • Parameters :
    • t.on.1 = Working time – Timing range 1
    • t.off.1 = Pause time – Timing range 1
    • T.on.2 = Working time – Timing range 2
    • T.off.2 = Pause time – Timing range 2
    • T.on.3 = Working time – Timing range 3
    • T.off.3 = Pause time – Timing range 3
    • T.on.4 = Working time – Timing range 4
    • T.off.4 = Pause time – Timing range 4
    • d.H2O = Shower start/stop hysteresis
SETTING OF THE SYSTEM SECONDARY PARAMETERS
  • Press contemporaneously and : the word CONF. is displayed.
  • Press to scroll the setting menu.
  • Cor.1 = temperature probe 1 correction
  • SCAL = °C/°F Celsius or Fahrenheit degree
  • Cor. H = 00.0 humidity probe correction (for probe 4/20mA insert – 4.0)
  • OFFS. = es.0.958 humidity probe target value (insert value indicated in the probe documentation)
  • Slop. = es.30.68 humidity probe target value (insert value indicated in the probe documentation)
  • T.HS = °25.0 operation temperature of the humidity probe
  • t. I nt. = 0-10V integration time
  • V. Hu M = humidity value shown on the display
  • V.THI = THI value shown on the display
  • Mod = °C/THI = operation mode (temperature or THI)
SETTING OF THE SYSTEM SECONDARY PARAMETERS

MANUAL CONTROL (RECOMMENDED FOR AUTHORISED TECHNICIANS)

SPEED

  • Keep pressed for at least 5 sec. to switch to the manual mode.

  • The lads “SPEED VENTILATION” flash and the 0-10V regulation % is displayed.

  • Press or to increase / decrease.

  • Press for at least 5 sec. to go back to auto mode.
    H2O

  • Keep pressed for at least 10 sec. to switch to the manual mode.

  • The word OFF is displayed. The H2O led switches off.

  • Press to start the shower (ON). The H2O led switches on.

  • Press to stop the shower (OFF).

  • Press for at least 10 sec. to go back to auto mode.

MEMORY OF THE REGISTERED TEMPERTURES /THI

(The values are retained even with the controller switched off).

  • Press : the diagram is displayed followed by the maximum registered temperature/THI value. Keeping pressed for more than 3 seconds, the word CLEA. is shown and the memory is cleared.
  • Press : the diagram is displayed followed by the minimum registered temperature/THI value. Keeping pressed for more than 3 seconds, the word CLEA. is shown and the memory is cleared.

SYSTEM RESET

  • Disconnect the controller from the main power supply.
  • Connect the controller to the main power supply and keep the button pressed until the word BOOT is displayed.
  • Release and wait for the reset.
  • ATTENTION: Any setting will return to the default.