EAE ORIA Switch Installation Guide

August 15, 2024
EAE

EAE ORIA Switch

Product Specifications

  • Type of protection: IP 20
  • Safety class: EN 60 529 II
  • KNX Supply Voltage: 21 V to 30 V DC SELV
  • Current Consumption: 10 mA
  • Bus Connection Terminal: KNX
  • Dimensions:
    • Front face (1-4 fold): 90×90 mm
    • Front face (5 fold): 90×112 mm
    • Front face (6 fold): 90×133 mm
    • Side – Surface of plaster: 8.5 mm
    • Side – Under plaster: 29.5 mm
  • Material: Plastic, polycarbonate
  • Communication Object: 50
  • Number of Addresses (max): 254
  • Number of Assignments (max): 255

Product Usage Instructions

Installation

  1. Fix the flange to the junction box using screws with the arrows on the flange pointing up.
  2. Position the switch into the junction box with the EAE logo upwards and recline it to the flange.
  3.  Slowly turn the switch clockwise until it clicks into the right position on the flange.
  4. Turn the switch counterclockwise to lock it onto the flange.

FAQ
How can I configure the parameters of the device?
You can find detailed information about parameter configuration in the Product Manual of the device.
Can anyone install and commission the device?
No, installation and commissioning should only be done by trained electricians following relevant standards and regulations.

Installation Manual ORIA
EAE KNX ORIA Switch Series

Operation and Display

  1. Button groups (1 – 6 fold)
  2. KNX Port Terminal
  3. Programming Button
  4. Programming LED

Description of the Device

  • Serial switches with plastic push-button
  • Can be configured with ETS5 or higher
  • Independent button configuration for each fold
  • Integrated Temperature Sensor (°C/°F) (Optional)
  • Integrated Humidity Sensor (Optional)
  • Different color options
  • Cleaning mode function
  • Logical function
  • Dependent or independent programmable buttons
  • 60×60 mm easy mounting to standard junction boxes
  • 6 rockers can be programmed to perform different functions
    • Switching
    • Dimming
    • Shutter/Blind
    • Value
    • Scene control
    • Status notification

Technical Data

EAE-ORIA-Switch- \(4\)

Installation

Installation of the product is done with the help of the flange which is inside the box. The flange is fixed to the junction box by using screws while the arrows on flange are headed to up. The switch is placed into the junction box by positioning the EAE logo upwards and then reclining it to the flange. The switch is slowly turned clockwise to give the  right position to it on the flange. After the clicks are on the right position, switch is turned counter- clockwise to lock it on the flange.

EAE-ORIA-Switch- \(1\) EAE-ORIA-Switch- \(1\)

Commissioning

  • Device default physical address is 15.15.255. Determination of the physical address and setting of parameters are actualized with Engineering Tool Software (ETS5 or higher). “.knxprod” file must be imported to the ETS. ( http://www.eaetechnology.com/ )
  • A detailed information about parameter configuration can be found in Product Manual of device.
  • Installation and commissioning of device may only be implemented by trained electricians. The relevant standards, directives, regulations and instructions must be observed when planning and implementing the electrical installation.
    • Protect the device against moisture, dirt and damage during transport, storage and operation!
    • Do not operate the device out of the specified technical data which is stated.
    • The device may only be operated in closed enclosures (Distribution boards)

Cleaning
If device becomes dirty, only a dry cloth can be used for cleaning. İt is not suitable to use wet cloths, caustics and solvents.