EAE TECHNOLOGY LC200 EAE KNX Line Coupler Installation Guide
- June 1, 2024
- EAE Technology
Table of Contents
LC200 R1.0
Installation Manual LC200
EAE KNX Line Coupler
General Description
- The EAE LC200 Line Coupler connects two Technical Data KNX segments (for example, a KNX line with a KNX area). It has a very compact design.
- The device has a filter table (8K bytes) for main group 0..31 and ensures a galvanic isolation between the lines.
- The coupler supports KNX longframes and is compatible with the ETS® software (ETS4.2 or higher).
- The buttons on the front panel allow disabling the telegram filter for testing purposes.
- The LEDs indicate the operating status and communication errors on the bus.
- The power is supplied via the KNX bus (main line).
Technical Data
Protection Type | IP 20 | IEC 60 529 |
---|---|---|
Safety Slass | III | IEC 61140 |
Power Supply | Voltage | 21…30V DC, SELV |
Current Consumption (main) | < 5 mA | |
Current Consumption (sub) | < 3 mA | |
Connections | KNX Line (main) | Bus connection terminal |
KNX Line (sub) | Bus connection terminal | |
Operating Elements | Function button, programming button, LEDs | |
Installation | 35mm DIN rail mount | EN 60 715 TH 35-75 |
Temperature Range | Operation Storage | -5° C + 45° C -25° C + 70° C |
Humidity | %5 to 93 % non-condensing | |
Dimensions | -H x W x D | |
Width W in mm | 90 mm x W x 70 mm |
18 mm (1 module)
Mounting depth 64 mm
Weight| 40 g
Box| Plastic PA66 housing grey
CE| in accordance with EMC and low voltage directives.
Device Peripherals
- KNX bus connector (main line)
- Programming LED
- Button func. programming mode
- KNX LED (main line, multicolor)
- Mode LED (multicolor)
- KNX LED (sub line, multicolor)
- Button “Pass GAs”
- Button “Pass IAs”
- KNX bus connector (sub line)
Functions
LC200 as Area and Line Coupler
LC200 as Repeater LC200 as Line Coupler
Commissioning
Determination of the physical address and setting of parameters are actualized with Engineering Tool Software (ETS4 or higher). “.knxprod” file must be imported to the ETS.
A detailed information about parameter configuration can be found in Product Manual of device.
Installation and commissioning of device may only be implemented by trained
electricians. The relevant standards, directives, regulations and instructions
must be observed when planning and implementing the electrical installation.
-When connecting the device make sure that the device can be isolated!
-Protect the device against moisture, dirt and damage during transport, storage and operation!
-Do not operate the device out of the specified technical data which is stated.
-The device may only be operated in closed enclosures (Distribution boards)
Cleaning
If device becomes dirty, only a dry cloth can be used for cleaning. It is not suitable to use wet cloths, caustics and solvents.
© EAE Technology www.eaetechnology.com
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>