General Description
  • The EAE LC200 Line Coupler connects two Technical Data KNX segments (for example, a KNX line with a KNX area). It has a very compact design.
  • The device has a filter table (8K bytes) for main group 0..31 and ensures a galvanic isolation between the lines.
  • The coupler supports KNX longframes and is compatible with the ETS® software (ETS4.2 or higher).
  • The buttons on the front panel allow disabling the telegram filter for testing purposes.
  • The LEDs indicate the operating status and communication errors on the bus.
  • The power is supplied via the KNX bus (main line).
Technical Data
Protection Type IP 20 IEC 60 529
Safety Slass III IEC 61140
Power Supply Voltage 21…30V DC, SELV
Current Consumption (main) < 5 mA
Current Consumption (sub) < 3 mA
Connections KNX Line (main) Bus connection terminal
KNX Line (sub) Bus connection terminal
Operating Elements Function button, programming button, LEDs
Installation 35mm DIN rail mount EN 60 715 TH 35-75
Temperature Range Operation Storage -5° C + 45° C -25° C + 70° C
Humidity %5 to 93 % non-condensing
Dimensions -H x W x D
Width W in mm 90 mm x W x 70 mm

18 mm (1 module)
Mounting depth 64 mm
Weight| 40 g
Box| Plastic PA66 housing grey
CE| in accordance with EMC and low voltage directives.

Device Peripherals
  1. KNX bus connector (main line)
  2. Programming LED
  3. Button func. programming mode
  4. KNX LED (main line, multicolor)
  5. Mode LED (multicolor)
  6. KNX LED (sub line, multicolor)
  7. Button “Pass GAs”
  8. Button “Pass IAs”
  9. KNX bus connector (sub line)
Functions

EAE TECHNOLOGY LC200 EAE KNX Line Coupler 3
LC200 as Area and Line Coupler

EAE TECHNOLOGY LC200 EAE KNX Line Coupler 4
LC200 as Repeater LC200 as Line Coupler

Commissioning

Determination of the physical address and setting of parameters are actualized with Engineering Tool Software (ETS4 or higher). “.knxprod” file must be imported to the ETS.

A detailed information about parameter configuration can be found in Product Manual of device.

Installation and commissioning of device may only be implemented by trained electricians. The relevant standards, directives, regulations and instructions must be observed when planning and implementing the electrical installation.
-When connecting the device make sure that the device can be isolated!
-Protect the device against moisture, dirt and damage during transport, storage and operation!
-Do not operate the device out of the specified technical data which is stated.
-The device may only be operated in closed enclosures (Distribution boards)

Cleaning

If device becomes dirty, only a dry cloth can be used for cleaning. It is not suitable to use wet cloths, caustics and solvents.

© EAE Technology www.eaetechnology.com

References