EAE TECHNOLOGY KNX ORIA Thermostat Installation Guide

June 1, 2024
EAE Technology

Installation Manual ORIA
EAE KNX ORIA Thermostat Series
Oria Thermostat IM R3.0

Operation and Display

EAE TECHNOLOGY KNX ORIA Thermostat - Display

1. Programmable Button Group 1
2. Fan Speed (1, 2, 3, Auto)
3. Operation Mode (Comfort, Night, Away, OFF)
4. Setpoint Temperature Up
5. Setpoint Temperature Down
6. Programmable Button Group 2| 1. KNX Port Terminal
2. Programming Button
3. Programming LED
---|---

Description of the Device

  • Temperature Adjustment on Digital LCD
  • Integrated Temperature Sensor (°C/ °F )
  • Integrated Humidity Sensor
  • Fan Speed Adjustment (1, 2, 3, Auto)
  • Different Operation Modes (Comfort, Night, Away, OFF)
  • Fully Automatic Function Mode (hot-cold transition)
  • Control Flexibility for all HVAC units including VRF-VRV and AC
  • PI rational, PI on-off (PWM), On/Off, Fan coil, Split unit controls
  • Easy mount into 60×60 mm standard switch junction boxes
  • Up to 4 fold (8 buttons) buttons can be programmed individually

▪ Switching
▪ Dimming
▪ Shutter/Blind| ▪ Value
▪ Scene control
▪ Status
---|---

Technical Data

Type of protection IP 20 EN 60 529
 Safety class II EN 61 140
 KNX Supply(1) Voltage
Current Consumptio 21 V… 30 V DC SELV

≤ 10 mA
Connections| KNX| Bus connection terminal
 Installation| 60×60 mm standard box
Temperature range| Ambient
Storage
Measurement accuracy| -5° C + 45° C
-25° C + 55° C
±0,3 °C
Humidity| Max. air humidity condensation| 95 % no moisture
Dimensions| Front face (2 fold)
Front face (3 fold)
Front face (4 fold)
Side- Surface of plaster
Side- Under plaster| 90×90 mm
90×112 mm
90×133 mm
8,5 mm
29,5 mm
Box| Plastic, polycarbonate
CE| In accordance with the EMC guideline and low voltage
 Application Program C| Communication Object
Number of Addresses(max)
Number of assignments(max)| 50
254
255

Installation

Installation of the product is done with the help of the flange which is inside the box. The flange is fixed to the junction box by using screws while the arrows on flange are headed to up. The switch is placed into the junction box by positioning the EAE logo upwards and then reclining it to the flange. The switch is slowly turned clockwise to give the right position to it on the flange. After the clicks are on the right position, switch is turned counter- clockwise to lock it on the flange.

Commissioning

Device default physical address is 15.15.255. Determination of the physical address and setting of parameters are actualized with Engineering Tool Software (ETS5 or higher). “.knxprod” file must be imported to the ETS. (http://www.eaetechnology.com/)

A detailed information about parameter configuration can be found in Product Manual of device.
Installation and commissioning of device may only be implemented by trained electricians. The relevant standards, directives, regulations and instructions must be observed when planning and implementing the electrical installation.

  • Protect the device against moisture, dirt and damage during transport, storage and operation!
  • Do not operate the device out of the specified technical data which is stated.
  • The device may only be operated in closed enclosures (Distribution boards)

Cleaning

If device becomes dirty, only a dry cloth can be used for cleaning. İt is not suitable to use wet cloths, caustics and solvents.

© EAE Technology
Ikitelli Org.San.Bolg. Ziya Gokalp Mah. Eski Turgut Ozal Cad.
No: 20 34490 Basaksehir/Istanbul Tel: +90 212 549 97 13
www.eaetechnology.com

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

EAE Technology User Manuals

Related Manuals