EAE DA110 KNX DALI Gateway 64 Ballast Individual Control Instruction Manual

June 20, 2024
EAE

EAE DA110 KNX DALI Gateway 64 Ballast Individual Control

EAE DA110 KNX DALI Gateway 64 Ballast Individual Control

Description

DALI Gateway operates as an interface between KNX bus and DALI bus system. DALI line power supply is integrated in the device. DA110 is used to control up to 64 normal DALI operating devices. (E.g. electronic ballasts, LED ballasts, transformers etc.)

Description

Connection

  1. Physical address label
  2.  KNX programming button
  3. KNX programming mode LED, Red
  4. KNX connection terminal
  5. DALI output
  6. Mains Connector
  7. Operating Led, Green
  8. DALI Status Led, Yellow
  9. Manual Mode LED, Red
  10. Manual Button
  11. Test Button

Technical Data

Protection Type e IP 20 EN 60 529
Safety Class II EN 61 140
KNX Supply KNX Supply 21 V… 30 V DC SELV
Current Consumption ≤ 10 mA
Main Supply Voltage 16 V DC typical
Current Max. 200 mA
DALI protocol EN 62 238Connections
Connections Screw Terminals;

0,3…2,5mm² solid and stranded wire
0,3…1,5mm² stranded wire with ferrule
Max tightening torque| 0.5 Nm
KNX| Bus connect terminal
Output| Number of DALI devices| Max. 64
Cable lengths;
1.5 mm2 300m 0.75 mm2 150m 0.5mm2 100m
Installation| 35mm mounting rai| EN 60 715
Temperature range| Ambient| -5° C + 45° C
Storage| -25° C + 55° C
Humidity| Max. air humidity| 95 % non-condense
Dimensions| 70 x W x 91mm| W=72 mm (4 modules)
Box| Plastic, polycarbonate, colour grey
CE| In accordance with the EMC guideline and low voltage directives.

Operation and Display

ON-LED: Lights up when device is working properly.

DALI STATUS-LED
Off: No problem.
On : There is a short circuit on DALI Bus or line voltage (220 v) is connected to DALI Bus.
Flashing Slowly: There is device which has problem on the DALI Bus.
Flashing Quickly: Initialization
MANUAL-LED: Lights up when manual control is activated.
MANUAL BUTTON: Activate/Deactivate manual control. Press the manual button for 3 seconds to activate manual control.
TEST BUTTON: Lights on/off and dims all ballasts when manual is activated.
PROGRAMMING-LED: Red led lights up after the programming button pressed.

Installation

Device is compatible for mounting to 35 mm DIN rail EN 60 715.

Installation

Connection

KNX Bus must be connected to the KNX connection terminal. KNX Bus connector polarity must be respected. DALI and Mains connections are made using screw terminals. Terminal names can be found on the device and user manual

Commissioning

With EAE DALI Commissioning Tool, assignment of DALI members to light groups can be done easily. Physical address assigning and parameter settings are actualized with Engineering Tool Software (ETS5 or higher). “.knxprod” file must be imported to the ETS.

IconA detailed information about parameter configuration can be found in Product Manual of device.

IconInstallation and commissioning of device should only be implemented by trained electricians. The relevant standards, directives, regulations and instructions must be observed when planning and implementing the electrical installation.

  • When connecting the device make sure that the device can be isolated!
  • Protect the device against moisture, dirt and damage during transport, storage and operation!
  • Do not operate the device out of the specified technical data stated in this document.
  • The device may only be operated in closed enclosures (Distribution boards)

Cleaning

If device becomes dirty, only a dry cloth must be used for cleaning. It is not appropriate to use wet cloths, caustics and solvents.

www.eaetechnology.com

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

EAE User Manuals

Related Manuals