EAE Rosa Metal Touch Switches User Manual
- October 30, 2023
- EAE
Table of Contents
EAE Rosa Metal Touch Switches
General
Rosa KNX switches offer a wide range of functional flexibility with up to 6 programmable buttons. Rosa switches can be programmed to control lighting, shutter/blind drivers, speakers, make scene calls, and mimic panic buttons. Each button can be programmed independently for a different function.
Device Technology
Button Definitions
- Programmable Buttons (up to 6 touch buttons)
Connection Diagram
- KNX Port Terminal
- Programming Button
- Programming LED
Technical Data
Operating Voltage | Voltage | 21V… 30V DC, via the KNX bus |
---|---|---|
Current drawn from the bus | <10mA | |
Safety Rating Class | IP 20, DIN EN 60529 |
II EN 61140
Connections| KNX| Bus Connection
Operating Temperature| Ambient| -5° C + 45° C
| Storage| -25° C + 55° C
| Measurement Accuracy| ±0,3 °C
Humidity| Max. Air humidity condensation| 95% no moisture
Dimensions| Front Side| 85 x 85 mm
| Side- Surface mounted part| 11 mm
| Side- Flush mounted part| 19.4 mm
Weight| 73 g|
Box Material| Metal or Glass, polycarbonate|
CE| In accordance with the EMC guideline and low voltage|
Dimensions
Communication Object Table
No. | Object Name | Function | Number of Bits | Flags |
---|---|---|---|---|
0 | General, operation | Active | 1 | CT |
1 | Rocker 1, switch | On/Off | 1 | CWT |
Rocker 1, shutter | Up/Down | 1 | CWT | |
Rocker 1, value [0,1] | Send | 1 | CWT | |
Rocker 1, value [0…255] | Send | 8 | CWT | |
Rocker 1, value [0…65535] | Send | 16 | CWT | |
Rocker 1, value [-32768…32768] | Send | 32 | CWT | |
Rocker 1, value [0…4294967295] | Send | 64 | CWT | |
Rocker 1, value.temperature | Send | 64 | CWT | |
TouchButton 1, switch | On/Off | 1 | CWT | |
TouchButton 1, shutter | Up/Down | 1 | CWT | |
TouchButton 1, value [0,1] | On/Off | 1 | CWT | |
TouchButton 1, value [0…255] | Send | 8 | CWT | |
TouchButton 1, value [0..65535] | Send | 16 | CWT | |
TouchButton 1, value [- 32768…32768] | Send | 32 | CWT | |
TouchButton 1, value [0…4294967295] | Send | 64 | CWT | |
TouchButton 1, value.temperature | Send | 64 | CWT | |
2 | Rocker 1, dimming | Send | 4 | CWT |
Rocker 1, shutter | Stop/Lamella Adj | 1 | CWT | |
TouchButton 1, dimming | Send | 4 | CWT | |
TouchButton 1, shutter | Stop/Lamella Adj | 1 | CWT | |
TouchButton 1, value [0,1] | On/Off | 1 | CWT | |
TouchButton 1, value [0…255] | Send | 8 | CWT | |
TouchButton 1, value [0…65535] | Send | 16 | CWT | |
TouchButton 1, value [- 32768…32768] | Send | 32 | CWT | |
TouchButton 1, value [0…4294967295] | Send | 64 | CWT | |
TouchButton 1, value.temperature | Send | 64 | CWT | |
3 | Rocker 1, shutter | Top Position | 1 | CWT |
Rocker 1, status | Top Position | 1 | CWT | |
TouchButton 1, shutter | Top Position | 1 | CWT | |
TouchButton 1, status | Top Position | 1 | CWT | |
4 | Rocker 1, shutter | Bottom Position | 1 | CWT |
TouchButton 1, shutter | Bottom Position | 1 | CWT |
Parameters and Communication Objects
General
General parameters include;
- In Operation (Device Alive) Function
- Telegram Limit Function
- Rocker Count
- Light Duration Of Status Indication Function
- LED Duration of Touch Feedback Function
- Navigation LED Brightness Function
Parameters
Parameter | Settings | Description |
---|---|---|
Enable In Operation | Enable/ Disable | In operation can be used to ensure |
that the device is alive and
connected to the KNX line.
In Operation Bit| Off/ On| Visible when “Enable In Operation” is enabled. Bit value to send as device alive
operation
In Operation Send Interval[sec]| 0… 300 …65535| Visible when “Enable In Operation” is enabled. The cyclic time period for sending in the operation
bit
Enable Telegram Limit| Enable /Disable| Limits the number of telegrams to
send in the certain time period
Telegram Limit Period Duration| 50ms , 100ms, …, 30s, 1min| Visible when
“Enable Telegram Limit” is enabled. Time period to check
telegram numbers
Maximum Telegram Count in Period| 1.. 100 …255| Visible when “Enable
Telegram Limit” is enabled. The maximum number of telegrams to send in
telegram limits the period duration
Light Duration of Status Indication| 0,75s , 2.25s, 3.25s| LEDs on
duration when status LEDs are used as operation indication with rocker or
touch
buttons.
Rocker Count| 1, 2 , 3, 4, 5, 6| The number of rockers should be selected compatible with the device to be able to use rockers and
touch buttons correctly.
Duration of Touch Feedback LED (after release) [0…65535 ms]| 0 …65535|
Touch Feedback LEDs lighting duration after release.
Navigation Light Brightness [0…100%]| 0… 100%| Navigation LED brightness
value
Communication Objects
No | Object Name | Function | Data Type | Flags |
---|---|---|---|---|
0 | General – In operation | Active | 1 Bit |
DPT 1.002
| CT
In operation value (0,1) selected through the “In operation bit,” parameter will be sent via the group address which is linked to this communication object.
Rockers and Touch Buttons
A total number of rockers can be selected through the “Rocker Count” parameter
in the “General” tab. Buttons on the thermostat can be used as rockers or
touch buttons. Select the desired operation from the “Rocker N” (N: Rocker
number) tab (Figure 2). If rockers are configured as touch buttons, 2 touch
button tabs will be visible under the “Rocker N” tab (Figure 3). Both rockers
and touch buttons have 5 functions;
- no function
- switch
- switch and dim
- shutter
- value operation
Rockers
A number of rockers should be selected in the “General” tabs in parameters and
should be chosen as compatible with the device that will be configured.
Rockers are numbered from top to bottom. Each Rocker contains 2 touch buttons
separately. Rockers can be configured as 4 different operations and 1 function
to disable rocker (No Function). Operation selection can be configured with
the “Rocker Function” parameter. Every function enables different parameters
and communication objects that will be explained in the following chapters.
Parameter | Setting | Description |
---|---|---|
Rocker Operation | Rocker /2 Touch Button | Selects the function of the |
rocker
Rocker Function| No Function| Disables the rocker
Switch| Rocker can be used to send on/off telegrams. (For more information
Chapter 4.2.1.1)
Switch and Dim| Rocker can send on/off and dimming telegrams. (For more
information Chapter
4.2.1.2)
Shutter| Rocker can control shutter, Venetian blind, blind, roller and
awning. (For more information Chapter 4.2.1.3)
Value Operation| Rocker buttons can send predefined values from different data types. (For more
information Chapter 4.2.1.4)
Rockers also have status LEDs which can be configured to indicate the state of the operation that is configured.
Switch
Selecting “Switch” as “Rocker Function“ enables sending 1-bit On(1)/Off(0)
telegrams to the group address that is linked to the respective communication
object. Status LEDs can be configured to notify the current status of
operation directly with buttons or using communication objects for
confirmation to show the current status.
Parameters
Parameter | Setting | Description |
---|---|---|
Mode of Buttons | Left Button On Right Button Off |
Left Button Off Right Button On
| Select which button is the ON button and which button is the OFF button
Function of LED| LED permanently Off| LED always Off
LED permanently On| LED always On
Status Indication| The Status LED of the last touched rocker button is on, the
other rocker button is off. If the “Separate Comm Object” parameter is
selected as “Enable” status LEDs will wait for confirmation from the
communication object
before changing state.
Inverted Status Indication| The status LED of the last touched rocker button is off, the other rocker button is on. If the “Separate Comm Object” parameter is selected as “Enable” status LEDs will wait for confirmation from the communication
the object before changing state.
Operation Indication| The status LED of the touched rocker button will be on for the time period selected at the “Light Duration of LED” parameter at
“General” tab.
Separate Comm Object| Enable/ Disable| Only visible when “Function of LED” is selected as “Status Indication” or “Inverted Status Indication”. This communication object is the input of confirmation for status LEDs. If selected “Enable” the respective communication object should be linked to an appropriate
group address
Communication Objects
No | Object Name | Function | Data Type | Flags | |
---|---|---|---|---|---|
1 | Rocker1 – Telegr. switch | On/Off | 1 bit |
DPT 1.001
| CWT
| On/Off telegrams will be sent to the group address that is linked to this
communication object.
3| Rocker1 – Status Comm. Obj.| On/Off| | 1 bit
DPT 1.002
| CWT
| Confirmation for On/Off switch telegrams will be received from this
communication object. If these communications objects are visible, they must
link to an appropriate group address. Otherwise, status LEDs will not function
correctly. If status confirmation is not to be used the communication object
should be disabled by “Separate Comm Object”
parameter.
Switch and Dim
Rockers can be configured with switching and dimming capabilities. When
configured as “Switch and Dim” rocker buttons will have two modes switch mode
and dim mode. When the rocker button touched shorter than the time period
specified in the “Long Touch Duration” parameter, the rocker button will act
as a switch. In switch mode, rocker buttons will behave as normal switches as
explained in Chapter 4.1.1. When the rocker buttons touched longer than “Long
Touch Duration” rocker will enter “Dim mode”. Dimming capability can be used
in two different types “Start Stop” and “Step Wise”. Which type to use can be
configured in the “Dimming Type” parameter.
Dimming – Start Stop Type
When the rocker button is touched (and not released) and the touched duration
exceeds “Long Touch Duration” time “Increase, %100”(When the on button is
touched) or “Decrease,%100”(When the off button is touched) dimming level will
be sent using respective communication object. When the button is released
“Increase, Break” or “Decrease, Break” value will be sent to stop the dimming
operation.
Dimming – Step Wise Type
When the rocker button is touched (and not released) and the touched duration
exceeds the “Long Touch Duration” time, a step value level configured in the
“Step Value” parameter will be sent using the respective communication object.
Until the button is released same step value will be sent periodically with a
time interval defined in “Step Send Interval”.
Parameter | Setting | Description |
---|---|---|
Mode of Buttons | Left Button Brighter(On) Right Button Darker(Off) |
/ Left Button Brighter(Off) Right Button Darker(On)
| Select which rocker button is on the button and which rocker button is off
button
Long Touch Duration| 300ms/ 400ms/ 500ms/ 600ms/ 800ms /
1s / 1.2s / 1.5s/ 2s / 3s / 4s / 5s / 6s / 7s
/ 8s / 9s / 10s
| Time interval to switch from “switch mode” to “dimming mode”.
Dimming Type| Start to Stop / Step Wise| Select dimming type. (Chapter
4.2.1.2)
Step Value| %100 / %50 / %25 / %12.5 / %6.25 /
%3.13 / % 1.56
| Visible when dimming type is Step Wise. Selects the dimming resolution that will be sent at every “Step
Send Interval”.
Step Send Interval| 300ms/ 400ms/ 500ms/ 600ms/ 800ms / 1s / 1.2s / 1.5s/ 2s / 3s / 4s / 5s / 6s / 7s / 8s / 9s / 10s| Visible when dimming type is Step Wise. Selects the time interval to
send dimming increase/decrease values
Function of LED| LED Permanently Off| LED always off
LED Permanently On| LED always on
Status Indication| The status LED of the last touched rocker button is on,
another rocker button is off. If the “Separate Comm Object” parameter is
selected as “Enable” status LEDs will wait for confirmation
from communication object before changing state.
Inverted Status Indication| The status LED of the last touched rocker button is off, another rocker button is on. If the “Separate Comm Object” parameter is selected as “Enable” status LEDs will wait for confirmation
from communication object before changing state.
Operation Indication| The status LED of the touched rocker button will be on for the time period
selected at the “Light Duration of LED” parameter at the “General” tab.
Separate Comm Object| Enable / Disable| Only visible when “Function of LED” is selected as “Status Indication” or “Inverted Status Indication”. This communication object is the input of confirmation for status LEDs. If selected as “Enable” the respective communication object should be linked to an
appropriate group address
Communication Objects
No | Object Name | Function | Data type | Flags |
---|---|---|---|---|
1 | Rocker1 – switch | On/Off | 1 bit |
DPT 1.001
| CWT
On/Off telegrams will be sent to the group address that is linked to this
communication object.
2| Rocker1 – dimming| Dim| 4 bit
DPT 3.007
| CWT
Dimming values will be sent to the group address that is linked to this
communication object.
3| Rocker1-Status
Comm. Obj.
| On/Off| 1 bit
DPT 1.002
| CWT
Confirmation for On/Off switch telegrams will be received from this
communication object. If these communication objects are visible, they must
link to an appropriate group address. Otherwise, status LEDs will not function
correctly. If status confirmation is not to be used the communication object
should be
disabled by the “Separate Comm Object” parameter.
Shutter
Selecting “Shutter” for “Rocker Operation” enables shutter operation for rocker buttons. Shutter functions can be configured to control two different shutter operations “Shutter/Venetian Blind” function or the “Blind/Roller/Awning” function.
Shutter/Venetian Blind
Firstly, select which rocker button is used for the “up” operation, and which
rocker button is used for “down” operation by the “Mode of Buttons” parameter.
Both buttons have two functions as “short touch” function and the “long touch”
function, “Long Touch Duration” parameter configures the limit time period for
the “long touch” operation. “Long Touch” will be used to move the blind
upwards or downwards. “Short touch” has two different functions whether the
blind is moving or not. When the blind is moving “short touch” acts as a stop
button that stops the blind’s movement, when the blind is not moving “short
touch” function is used to adjust the lamella position.
| Short Touch| Long touch
---|---|---
Up Button – Blind Moving| Stop| Up
Down Button – Blind Moving| Stop| Down
Up Button – Blind Stopped| Lamella Down| Up
Down Button – Blind Stopped| Lamella Up| Down
EAE KNX Rosa Switch
When the “Up Button” long touched “Up” telegram will be transmitted using the “Rocker1 – Shutter UP/DOWN” communication object and the shutter will start moving upwards until it reaches the “Top Position” or “STOP” telegram transmitted using “Rocker1 – STOP/Lamella Adj.” communication object by short touching “Up Button” or “Down Button”. When the “Down Button” long touched “Down” telegram will be transmitted using the “Rocker1 – Shutter UP/DOWN” communication object and the shutter will start moving downwards until it reaches the “Bottom Position” or “STOP” telegram transmitted using the “Rocker1 – STOP/Lamella Adj.” communication object by short touching “Up Button” or “Down Button”. When the blind is not moving “Up Button” and “Down Button” operate as lamella adjustment and respective telegrams will be sent using the “Rocker1-STOP/Lamella Adj.” communication object.
Blind/Roller/Awning Function
Selecting the “Control Type” parameter as “Blind/Roller/Awning” disables
lamella adjustment functions of rocker buttons. In this control type, when “Up
Button” is touched “Up” telegram will be sent using the “Rocker1 – shutter.
UP/DOWN” communication object and touched again while the blind is moving
“STOP” telegram will be sent using the “Rocker1 – STOP/Lamella adj.”
communication object. When the “Down Button” touched “DOWN” the telegram will
be sent using the “Rocker1 – shutter. UP/DOWN” communication object and
touched again while the blind is moving “STOP” telegram will be sent using the
“Rocker1 – STOP/Lamella adj.” communication object.
Parameters
Parameter | Setting | Description |
---|---|---|
Mode of Buttons | Left Up Right Down |
Left Down Right Up
| Select which rocker button is the “Up Button” and which rocker
the button is the “Down Button”.
Control Type| Shutter/Venetian Blind
Blind/Roller/Awning
| Selects the control type of blinds. The shutter/Venetian Blind function
includes “Lamella Control” and the Blind/Roller/Awning function does not
include “Lamella Control”.
Function of LED| LED Permanently Off| LED always off
LED Permanently On| LED always on
Status Indication| Visualize the blind’s state using status LEDs of up and
down buttons. * [5]
Operation Indication| The status LED of the touched rocker button will be on
for the time period selected at “Light Duration of LED”
parameter at the “General” tab.
Long Touch Duration| 300ms/ 400ms/ 500ms/ 600ms/
800ms / 1s / 1.2s / 1.5s/ 2s /
3s / 4s / 5s / 6s / 7s / 8s / 9s / 10s
| Time interval to switch from short touch to long touch
*[5] LED Function – Status Indication
Status indication operates the same way for “Shutter/Venetian Blind” and
“Blind/Roller/Awning”. LED’s status is respective to the blind’s state is
given below.
| Up Button – Status LED| Down Button – Status LED
---|---|---
Moving upward| Blink| Off
Moving downward| Off| Blink
At top position| On| Off
At bottom position| Off| On
Stop between the top – bottom| Off| Off
When “Function of Led” is selected as “Status Indication”, “Top Position” and “Bottom Position” communication objects given below must be linked to the appropriate group addresses for the status LEDs to function correctly.
Communication Objects
No | Object Name | Function | Data Type | Flags |
---|---|---|---|---|
1 | Rocker1-shutter |
UP/DOWN
| Up/Down| 1 bit
DPT 1.008
| CWT
This communication object will be used to start a blind movement.
2| Rocker1 –
STOP/Lamella adj.
| Stop/Lamella adj.| 1 bit
DPT 1.002
| CWT
When the “Control Type” parameter is “Shutter/Venetian Blind” this
communication object is used to stop
movement of the blind and adjust lamella position, otherwise when the “Control Type” parameter is “Blind/Roller/Awning” only used for stopping blind movement.
3| Rocker1-Top Position| True/False| 1 bit
DPT 1.002
| CWT
This communication object should be linked to an appropriate group address
that will be used to detect whether the blind is at the “Top Position” (True)
or not (False).
4| Rocker1-Bottom Position| True/False| 1 bit
DPT 1.002
| CWT
This communication object should be linked to an appropriate group address
that will be used to detect whether the blind is at the “Bottom Position”
(True) or not (False).
Value Operation
Rocker buttons can be configured to send predefined values from different data types. Values selected for both rocker buttons will be transmitted over the same communication object.
Parameters
Parameter | Setting | Description |
---|---|---|
Function of Led | LED Permanently Off | LED always off |
LED Permanently On | LED always on | |
Operation Indication | The status LED of the touched rocker button will be on |
for the time period selected at “Light Duration of LED”
parameter at the “General” tab.
Data Type| No Reaction
1-bit value
1byte value [0…255] Percent value [%0…%100] 2 byte value [- 32768…32767] 2 byte
value [0…65535]
4-byte value [floating point]
4-byte value [0…4294967295]
| Select data type.
Left Button of the Rocker
Sent value| 0 /1| Visible when “Data Type” is selected as “1-bit value”.
Transmitted value [0…255]| 0 …255| Visible when “Data Type” is selected
as “1-byte value”.
Send percent value [%0…%100]| 0… 80 …100| Visible when “Data Type” is
selected as “percent value”.
Transmitted value [- 32768…32767]| -32768… 0 …32767| Visible when “Data
Type”
selected as “2-byte value [- 32768…32767]”.
Transmitted value [0…65535]| 0 …65535| Visible when “Data Type” is
selected as “2-byte value [0…65535]”.
Float decimal| -128… 0 …127| Visible when “Data Type” selected
as “4 byte value [floating point]”.
Float rational| 0 …99| Visible when “Data Type”
selected as a “4-byte value [floating point]”.
---|---|---
Transmitted value [0…4294967295]| 0 …4294967295| Visible when “Data Type”
is selected as “4-byte value [0…4294967295]”.
Right Button of Rocker – Operate the same way as the Left Button of the Rocker
Communication Objects
No | Object Name | Function | Data type | Flags |
---|---|---|---|---|
1 | TouchButton1 – value [0,1] | True/False | 1 bit DPT 1.002 | CWT |
Enabled when “Data Type” is selected as “1-bit value”
TouchButton1– value [0…255]| Send| 1 byte DPT 5.010| CWT
Enabled when “Data Type” is selected as “1byte value [0…255]”
TouchButton1– value [0…255]| Send| 1 byte DPT 5.001| CWT
Enabled when “Data Type” is selected as “Percent value [%0…%100]
TouchButton1- value [-32768…32767]| Send| 2 byte DPT 8.001| CWT
Enabled when “Data Type” is selected as “2-byte value [-32768…32767]”
TouchButton1- value [0…65535]| Send| 2 byte DPT 7.001| CWT
| Enabled when “Data Type” is selected as “2-byte value [0…65535]”
TouchButton1- value[temperature]| Send| 4 byte DPT 14.068| CWT
Enabled when “Data Type” is selected as “4-byte value [floating point]
TouchButton1-value [0…4294967295]| Send| 4 byte DPT 12.001| CWT
Enabled when “Data Type” is selected as “4-byte value [0…4294967295]”
2| TouchButton1-long – value [0,1]| True/False| 1 bit DPT 1.002| CWT
Enabled when “Long Touch Data Type” is selected as “1-bit value”
TouchButton1-long – value [0…255]| Send| 1 byte DPT 5.010| CWT
Enabled when “Long Touch Data Type” is selected as “1byte value [0…255]”
TouchButton1– value [0…255]| Send| 1 byte DPT 5.001| CWT
Enabled when “Long Touch Data Type” is selected as “Percent value [%0…%100]
TouchButton1 – long- value [-32768…32767]| Send| 2 byte DPT 8.001| CWT
Enabled when “Long Touch Data Type” is selected as “2-byte value
[-32768…32767]”
TouchButton1- long -value [0…65535]| Send| 2 byte DPT 7.001| CWT
Enabled when “Long Touch Data Type” is selected as “2-byte value [0…65535]”
TouchButton1- long – value[temperature]| Send| 4 byte DPT 14.068| CWT
Enabled when “Long Touch Data Type” is selected as “4-byte value [floating
point]
TouchButton1- long – value [0…4294967295]| Send| 4 byte DPT 12.001| CWT
Enabled when “Long Touch Data Type” is selected as “4-byte value
[0…4294967295]”
Touch Buttons
A number of rockers should be selected in the “General” tabs in parameters and should be chosen as compatible with the device that will be configured. Touch buttons are numbered from top to bottom – right to left, topmost right touch button as touch button 1, near it is touch button 2, and so on. Touch buttons can be configured as 4 different operations and 1 function to disable the touch button (No Function). Operation selection can be configured from the “Touch Button N” (N: Touch button number) tab, visible when “Rocker Operation” is selected as “2 Touch Buttons”. Every function enables different parameters and communication objects that will be explained in the following chapters.
Parameter | Setting | Description |
---|---|---|
Touch Button Function | No Function | Disables the touch button |
Switch | Touch buttons can be used to send |
on/off telegrams. (For more information Chapter 4.2.2.1)
Switch and Dim| Touch buttons can send on/off and
dimming telegrams. (For more information Chapter 4.2.2.2)
Shutter| The touch button can control the shutter, Venetian blind, blind, roller, and awning. (For more information
Chapter 4.2.2.3)
Value Operation| The touch button can send predefined values from different data types.
(Refer to Section 4.2.2.4)
Touch buttons also have status LEDs which can be configured to indicate the state of the operation that is configured.
Switch
Selecting “Switch” as “Touch Button Function“ enables sending 1-bit On(1)/Off(0) telegrams to the group address that is linked to the respective communication object. Touching and releasing buttons can be assigned to different commands (On, Off, Toggle, and No Command). Status LEDs can be configured to notify the current status of operation directly with buttons or using communication objects for confirmation to show the current status.
Parameters
Parameter | Setting | Description |
---|---|---|
Command on Touch | On / Off / Toggle / No command | Selects button function |
when button touched.
Command on Release| On / Off / Toggle / No command| Selects button
function when button released.
Function of LED| LED permanently Off| LED always Off
LED permanently On| LED always On
Status Indication| Last transmitted command “on” -> LED on Last transmitted
command “off” -> LED off If “Separate Comm Object” is enabled, status LEDs
will wait for
confirmation before changing status.
Inverted Status Indication| Last transmitted command “on” -> LED off Last transmitted command “off” -> LED on If “Separate Comm Object” is enabled, status LEDs will wait for
confirmation before changing status.
Operation Indication| The status LED of the touched touch button will be on for the time period selected at the “Light Duration of LED” parameter in the “General” tab.
The last transmitted command value has no effect to the status-led operation.
Separate Comm Object| Enable/ Disable| Only visible when “Function of LED” is selected as “Status Indication” or “Inverted Status Indication”. This communication object is the
input of confirmation for status LEDs. If selected “Enable” the respective communication object should be linked
to an appropriate group address.
Communication Objects
No | Object Name | Function | Data Type | Flags |
---|---|---|---|---|
1 | TouchButton1 | switch | 1 bit |
DPT 1.001
| CWT
On/Off telegrams will be sent to the group address that is linked to this
communication object.
3| TouchButton1| Status Comm.Obj.| 1 bit
DPT 1.002
| CWT
Confirmation for On/Off switch telegrams will be received from this
communication object. If these communications objects are visible, it must
link to an appropriate group address. Otherwise, status LEDs will not function
correctly. If status confirmation is not to be used the communication object
should be
disabled by the “Separate Comm Object” parameter.
Switch and Dim
When touch button function is selected as “Switch and Dim” the touch button can be configured in three different ways to control brightness value.
| Short Touch| Long touch
---|---|---
Darker(Short Touch Off)| Off (%0)| Decrease, (%XX)
Brighter(Short Touch On)| On(%100)| Increase,(%XX)
Darker/Brighter(Short Touch Toggle)| Toggle between Darker/Brighter| Decrease,
(%XX) / Increase,(%XX)
%XX values can have different values relative to the “Dimming Type” parameter. The “Dimming Type” parameter allows two different types of dimming functionality “Start Stop” and “Step Wise”.
Dimming – Start Stop Type
When the touch button is touched (and not released) and the touched duration
exceeds “Long Touch Duration” time “Increase, %100” (When the button in
Brighter mode) or “Decrease, %100” (When the button in Darker mode) dimming
level will be send using respective communication object. When the button
released “Increase, Break” or “Decrease, Break” value will be sent.
Dimming – Step Wise Type
When the touch button is touched (and not released) and the touch duration
exceeds the “Long Touch Duration” time, a step value level configured in the
“Step Value” parameter will be sent using the respective communication object.
If the button mode is “Darker”, “Decrease, % [Step Value]”, else button mode
is “Brighter”, “Increase, % [Step Value]” values will be sent. Until the
button is released same step value will be sent periodically with a time
interval defined in “Step Send Interval”.
Parameters
Parameter | Setting | Description |
---|---|---|
Dim Operation | Darker (Short Touch Off) Brighter (Short Touch On) |
Darker/Brighter (Short Touch
Toggle)
| Select the touch button dim operation. (For more information Chapter
4.2.2.2)
Long Touch Time| 300ms/ 400ms/ 500ms/ 600ms/| Time interval to switch from
| 800ms /| “switch/toggle mode” to “dimming
| 1s / 1.2s / 1.5s/ 2s / 3s / 4s / 5s / 6s /| mode”.
| 7s|
| / 8s / 9s / 10s|
Dimming Type| Start to Stop / Step Wise| Select dimming type. ( For more
information Chapter 4.2.2.2)
Step Value| %100 / %50 / %25 / %12.5 / %6.25 /| Visible when the dimming
type is Step
| %3.13 / % 1.56| Wise. Selects the dimming resolution
| | that will be sent at every “Step
| | Send Interval”.
Step Send Interval| 300ms/ 400ms/ 500ms/ 600ms/| Visible when the dimming type
is Step
| 800ms /| Wise. Selects the time interval to
| 1s / 1.2s / 1.5s/ 2s / 3s / 4s / 5s / 6s /| send dimming
increase/decrease
| 7s
/ 8s / 9s / 10s
| values
Function of LED| LED Permanently Off| LED always off
LED Permanently On| LED always on
Status Indication| Last transmitted command “on” -> LED on Last transmitted
command “off” -> LED off If “Separate Comm Object” is enabled, status LEDs
will wait for
confirmation before changing status.
Inverted Status Indication| Last transmitted command “on” -> LED off Last transmitted command “off” -> LED on If “Separate Comm Object” is enabled, status LEDs will wait for
confirmation before changing status.
Operation Indication| The status LED of the touched touch button will be on for the time period selected at “Light Duration of LED”
parameter at the “General” tab.
Separate Comm Object| Enable / Disable| Only visible when “Function of LED” is selected as “Status Indication” or “Inverted Status Indication”. This communication object is the input of confirmation for status LEDs. If selected “Enable” the respective communication object should be linked to an appropriate group
address.
Communication Objects
No | Object Name | Function | Data type | Flags |
---|---|---|---|---|
1 | TouchButton1 – switch | On/Off | 1 bit |
DPT 1.001
| CWT
On/Off telegrams will be sent to the group address that is linked to this
communication object.
2| TouchButton1 – dimming| Dim| 4 bit
DPT 3.007
| CWT
Dimming values will be sent to the group address that is linked to this
communication object.
3| TouchButton1- Status
Comm. Obj.
| On/Off| 1 bit
DPT 1.002
| CWT
Confirmation for On/Off switch telegrams will be received from this
communication object. If these communications objects are visible, it must
link to an appropriate group address. Otherwise, status LEDs will not function
correctly. If status confirmation is not to be used the communication object
should be
disabled by the “Separate Comm Object” parameter.
Shutter
Selecting “Shutter” for “Touch Button Function” enables shutter operation for touch buttons. Shutter functions can be configured to control two different shutter operations “Shutter/Venetian Blind” function or the “Blind/Roller/Awning” function. In both functions touch button can be configured as 3 different button functions; Up, Down, and Toggle. When the touch button is selected as up or down, that button can only move the blind and lamella to the configured direction. For example, if configured as up button, the touch button can be used to move the blind up and adjust the lamella down. If the touch button configured as a toggle button, a single button can be used to move the blind up–down and adjust the lamella up–down.
Shutter/Venetian Blind Function
When “Controller Type” is configured as “Shutter/Venetian Blind”, lamella
operations of blind control will be enabled as the “short touch” function of
the touch button. Also, the “Button Function” parameter enables the use of the
touch button 3 different ways;
Up: “Long Touch” moves the blind upwards; “Short Touch” operates two
different ways, short touched while the blind is moving, stops the blind, and
short touched while the blind is not moving adjusts the lamella position down.
Down: “Long Touch” moves the blind downwards; “Short Touch” operates two
different ways, short touched while the blind is moving, stops the blind,
short touched while the blind is not moving adjusts the lamella position up.
Toggle: “Long Touch” moves the blind upwards or downwards toggling the last “Long Touch” action. For example, if the last state was up, when the touch button is long touched, it will send a “Down” telegram. Every time the touch button is long touched it will toggle its last state. If the touch button is short-touched while the blind is moving upward or downward “Short Touch” will stop the blind, if the blind is not moving “Short Touch” will adjust the lamella. Lamella adjustment will operate respective to the last state, for example, if the last “Long Touch” action was up, then lamella will be adjusted down when touch button short touched and if the last “Long Touch” action was down, then lamella will be adjusted up when touch button short touched.
Blind/Roller/Awning Function
When “Controller Type” is configured as “Blind/Roller/Awning Function” lamella
operations of blind control will be disabled and “short touch” will only stop
the movement of the blind. “Button Function”the parameter enables the use of
the touch button 3 different ways;
Up: “Long Touch” moves the blind upwards; “Short Touch” stops the blind.
Down: “Long Touch” moves the blind downwards; “Short Touch” stops the
blind.
Toggle: “Long Touch” action moves the blind upwards or downwards toggling
the last “Long
Touch” action. For example, if the last state was up, when the touch button is
long touched it will send a “Down” telegram. Every time touch button is long
touched it will toggle its last state. “Short Touch” stops the blind whether
it’s moving upwards or downwards
Parameters
Parameter | Setting | Description |
---|---|---|
Touch Button Function | Up / Down / Toggle | Chapter 4.2.2.3 |
Control Type | Shutter/Venetian Blind |
Blind/Roller/Awning
| Selects the control type of blinds. The shutter/Venetian Blind function includes “Lamella Control” and the Blind/Roller/Awning function does not include “Lamella
Control”.
Function of LED| LED Permanently Off| LED always off
| LED Permanently On| LED always on
| Status Indication| Visualize the blind’s state using
status LEDs of up and down buttons. * [6]
| Operation Indication| The status LED of the touched rocker button will be on for the time period selected at the “Light Duration of LED” parameter at
“General” tab.
Long Touch Duration| 300ms / 400ms/ 500ms/ 600ms/ 800ms / 1s / 1.2s / 1.5s/ 2s /
3s / 4s / 5s / 6s / 7s / 8s / 9s /
10s
| Time interval to switch from short touch to long touch
Communication Objects
*[6] LED Function – Status Indication operates the same way for “Shutter/Venetian Blind” and “Blind/Roller/Awning”. LEDs status respective to the blind’s state and “Button Function” configuration given below;
| Up Mode| Down Mode| Toggle Mode
---|---|---|---
Moving upward| Blink| Off| Blink
Moving downward| Off| Blink| Blink
At top position| Off| Off| Off
At bottom position| Off| Off| Off
Stop between top – bottom| Off| Off| Off
When “Function of Led” is selected as “Status Indication”, “Top Position” and “Bottom Position” communication objects given below must be linked to the appropriate group addresses for the LEDs to function correctly.
Value Operation
Touch button can be configured to send predefined values from different data types. Additionally, a long touch request can be enabled to be used as a secondary value operation.
Parameters
Parameter | Setting | Description |
---|---|---|
Function of Led | LED Permanently Off | LED always off |
LED Permanently On | LED always on | |
Operation Indication | The status LED of the touched rocker button will be on |
for the time period selected at “Light Duration of LED”
parameter at the “General” tab.
Data Type| No Reaction
1-bit value
1byte value [0…255] Percent value [%0…%100]
2 byte value [-32768…32767] 2 byte value [0…65535]
4-byte value [floating point]
4-byte value [0…4294967295]
| Select data type.
Sent value| 0 /1| Visible when “Data Type” is selected as “1-bit value”.
Transmitted value [0…255]| 0 …255| Visible when “Data Type” is selected
as “1-byte value”.
Send percent value [%0…%100]| 0… 80 …100| Visible when “Data Type” is
selected as “percent value”.
Transmitted value [-32768…32767]| -32768… 0 …32767| Visible when “Data
Type” is selected as “2-byte value [- 32768…32767]”.
Transmitted value [0…65535]| 0 …65535| Visible when “Data Type” is
selected as a “2-byte value [0…65535]”.
Float decimal| -128… 0 …127| Visible when “Data Type”
selected as a “4-byte value [floating point]”.
Float rational| 0 …99| Visible when “Data Type” is selected as “4-byte
value [floating point]”.
Transmitted value [0…4294967295]| 0 …4294967295| Visible when “Data Type”
is selected as “4-byte value [0…4294967295]”.
Long Touch Request| No / Yes| Enable/Disable long touch duration
Long Touch Duration| 100ms / 1s / 10s / 1min / 10min| The select time
period for long touch operation
Long Touch Data Type| No Reaction
1-bit value
1byte value [0…255] Percent value [%0…%100]
2 byte value [-32768…32767] 2 byte value [0…65535]
4-byte value [floating point]
4-byte value [0…4294967295]
| Select data type.
Sent value| 0 /1| Visible when “Long Touch Data
Type” selected as “1-bit value”.
Transmitted value [0…255]| 0 …255| Visible when “Long Touch Data
Type” selected as “1 byte value”.
Send percent value [%0…%100]| 0… 80 …100| Visible when “Long Touch Data
Type” selected as “percent value”.
EAE KNX Rosa Switch
Transmitted value [- 32768…32767]| -32768… 0 …32767| Visible when “Long Touch Data Type” selected as “2 byte
value [- 32768…32767]”.
---|---|---
Transmitted value [0…65535]| 0 …65535| Visible when “Long Touch Data
Type” selected as “2
byte value [0…65535]”.
Float decimal| -128… 0 …127| Visible when “Long Touch Data Type” selected as “4
byte value [floating point]”.
Float rational| 0 …99| Visible when “Long Touch Data Type” selected as “4
byte value [floating point]”.
Transmitted value [0…4294967295]| 0 …4294967295| Visible when “Long Touch Data Type” is selected as a “4-byte value [0…4294967295]”.
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>