EAE SW104 KNX Switch Actuator Instruction Manual Product Information
- May 15, 2024
- EAE
Table of Contents
SW104 KNX Switch Actuator
“`html
Product Information
Specifications
Product Name: EAE KNX Switch Actuator
Model: SW108/104 R3.0
Order Number: 48002
Channels: 8 independent channels
Relay Type: Bistable switching relay with
16A/20AX (C-Load) relays
Operating Feature: Manual operation with slide
switches
Device Technology
Connection Diagram
Technical Data
-
Type of Protection: IP 20
-
Safety Class: II
-
Power Supply: 21V to 30V DC, SELV, < 10
mA -
Connections: Screw terminals
-
Switching Voltage: 277/440V AC; 50/60 Hz
-
Switching Capacity: 16A / AC 1
-
Output Life: > 3 x 10^6 cycles
-
Type of Contact: Potential-free, bistable
-
Temperature Range: – Ambient: SW108 – 65.5 x
143 x 89mm, SW104 – 0.15 kg -
Humidity: In accordance with the EMC guideline
and low voltage communications
Product Usage Instructions
Configuration and Setup
To configure the switch actuator, you will need the ETS
application file .knxprod available on the EAE website. ETS
(Engineering Tool Software) is required for programming the device.
Parameter settings and related group addresses can be changed using
ETS. Follow the instructions in the ETS help file for more
details.
Operating the Device
-
Each channel can be configured with ETS3/ETS4 or higher
versions. -
The relay position is selected based on parameterization after
bus voltage failure or return. -
The device has a manual operating feature allowing you to
switch the relay on or off with slide switches. -
The C-Load feature enables convenient control of fluorescent
lamps.
Maintenance and Care
Ensure proper power supply within the specified voltage range.
Regularly check connections and tighten screw terminals as needed.
Keep the device clean and free from dust or debris to maintain
optimal performance.
Frequently Asked Questions (FAQ)
Q: What is the default physical address of the device?
A: The default physical address is 15.15.255 for each
channel.
Q: How can I change the parameter settings of the device?
A: You can change the parameter settings and group addresses
using the ETS application file .knxprod available on the EAE
website. Follow the instructions in the ETS help file for detailed
guidance.
“`
EAE KNX Switch Actuator
Product Manual SW104 and SW108
Order Number: 48002
Product Manual SW108 and SW104 EAE KNX Switch Actuator
SW108/104 R3.0
Content
1 General ………………………………………………………………………………………………………………………….. 2 2 Device
Technology ………………………………………………………………………………………………………….. 3
2.1 Connection Diagram…………………………………………………………………………………………………. 3 2.2 Technical
Data …………………………………………………………………………………………………………. 5 3 Communication Object
Table……………………………………………………………………………………………. 6 4 Parameters
…………………………………………………………………………………………………………………….. 7 4.1 Main
General…………………………………………………………………………………………………………… 7 4.2 Scene
……………………………………………………………………………………………………………………. 10 4.3 Channel General
…………………………………………………………………………………………………….. 11 4.4
Function………………………………………………………………………………………………………………… 13
4.4.1 Staircase Function …………………………………………………………………………………………… 14 4.4.2 External
Logic Function ……………………………………………………………………………………. 16 4.4.3 Internal Logic
Function …………………………………………………………………………………….. 17 4.4.4 Priority Function
……………………………………………………………………………………………… 17 4.4.5 Threshold
Function………………………………………………………………………………………….. 18 4.4.6 Operating Hour
Function………………………………………………………………………………….. 20 4.4.7 Sweep Function
………………………………………………………………………………………………. 21 5 Process Priority Table
…………………………………………………………………………………………………….. 22
©EAE Technology
www.eaetechnology.com
Page 1 / 22
Product Manual SW108 and SW104 EAE KNX Switch Actuator
SW108/104 R3.0
1 General
EAE KNX Switch Actuator has eight channels which can be configured with
ETS3/ETS4 or higher version. Each channel is independent of another. It has a
separate bistable switching relay. SW108 / SW104 has been designed especially
for loads with high surge currents. It has 16A/20AX (C-Load) relays inside
channels. C-Load feature enables a convenient control of fluorescent lambs.
Also device has a manual operating feature. The relay can be switched on or
off with slide switches.
The following function list provides;
· Staircase · External logic · Internal logic · Priority · Threshold ·
Operating hour · Sweep
Each channel of devices can choose any of these functions. The outputs are
parameterized individually via ETS3/4. After bus voltage failure or voltage
return the relay position is selected on dependence on the parameterization.
In “ETS reset”, device parameters are return download configuration.
NOTE: Each channel is uniform. Device factory default physical address is
15.15.255.
©EAE Technology
www.eaetechnology.com
Page 2 / 22
Product Manual SW108 and SW104 EAE KNX Switch Actuator
2 Device Technology
2.1 Connection Diagram
SW108/104 R3.0 Connection Diagram
©EAE Technology
www.eaetechnology.com
Page 3 / 22
Product Manual SW108 and SW104 EAE KNX Switch Actuator
SW108/104 R3.0
1. Physical Address Label 2. Programming Button 3. Red Programming LED 4. KNX Connection Terminal 5. Switch Position Display and ON/OFF Manual Actuation
©EAE Technology
www.eaetechnology.com
Page 4 / 22
Product Manual SW108 and SW104 EAE KNX Switch Actuator
2.2 Technical Data
SW108/104 R3.0
Type of protection Safety class Power supply : External supply Connections
Output
Output life Type of contact Installation Operating elements Temperature range
Humidity Dimensions Weight Box CE Application program
IP 20
EN 60 529
II
EN 61 140
– Voltage – Current consumption
—
21V… 30V DC, SELV < 10 mA
– Screw terminals – Max tightening torque
0,5…4 mm² solid and stranded wire 0,5…2,5mm² stranded wire with ferrule 0.8 Nm
– KNX
Bus connect terminal
– Number
4 output SW104 8 output SW108
– Switching voltage
277/440V AC; 50/60 Hz
– Switching capacity 277 V AC
16A / AC 1
– Fluorescent lighting load to EN 60 16 AX/250 VAC
669-1 – Mechanical life
3 x 106
– potential-free, bistable
– 35mm mounting rail
EN 60 715
– LED (red) and button – Ambient – Storage – Transport – max. air humidity
For physical address -5° C + 45° C -25° C + 55° C -25° C + 70° C 95 % no moisture condensation
SW108 – 65,5 x 143 x 89mm
SW104 65,5 x 72 x 89 mm SW108 0.45 kg
SW104 0.15 kg Plastic, polycarbonate, colour grey
In accordance with the EMC
guideline and low voltage
Communications
Number of addresses(max) Number of
objects
122
253
assignments(max) 253
NOTE: Device default physical address is 15.15.255. In order to configure switch actuator, ETS application file “.knxprod” is needed. It’s possible to download the file on EAE website. ETS is required for programming the device. Parameter settings and related group addresses can be changed by ETS. Learn more by reading ETS help file.
©EAE Technology
www.eaetechnology.com
Page 5 / 22
Product Manual SW108 and SW104 EAE KNX Switch Actuator
SW108/104 R3.0
3 Communication Object Table
The following 122 communication objects are available in the SW108 and SW104.
No
Object name
Function
DTP Type
0 1 2, 17, 32, 47, 62, 77, 92, 107 3, 18, 33, 48 63, 78, 93, 108 4, 19, 34,
49, 64, 79, 94, 109 5, 20, 35, 50, 65, 80, 95, 110 6, 21, 36, 51, 66, 81, 96,
111 7, 22, 37, 52, 67, 82, 97, 112 8, 23, 38, 53, 68, 83, 98, 113 9, 24, 39,
54, 69, 84, 99, 114
10, 25, 40, 55, 70, 85, 100, 115
11, 26, 41, 56, 71, 86, 101, 116
12, 27, 42, 57, 72, 87, 102, 117
13, 28, 43, 58, 73, 88, 103, 118
General, In operation General Scene 8-bit Output 1, Switch
Output 1,Status Switch
Output 1,Enable staircase function Output 1,Staircase lighting duration Output
1,Permanent ON
Output 1,External logic input Output 1,Forced positioning
Output 1,Start value of operating hour Output 1,Limit value of operating hour
Output 1,Counter reset of opr. hour
Output 1,Current value of opr. hour
Output 1,Operating hour runout
Output 1,Threshold input
Output 1,Threshold input
true / false recall / save on / off on / off enable / disable 0h … 65535h on /
off on / off on / off 0h … 65535 hour 0h … 65535 hour No action/reset trig 0h
… 65535h
true / false
Value 0…65535 Value 0…255
14, 29, 44, 59, 74, 89, 104, 119
Output 1,Threshold value Output 1,Threshold value
Value 0…65535 Value 0…255
15, 30, 45, 60, 75, 90, 105, 120
16, 31, 46, 61, 76, 91, 106, 121
Output 1,Threshold status Output 1,Sweep
true / false trigger
DTP_Bool 1.002 DPT_Scene 18.001 DPT_Switch 1.001
DPT_Switch 1.001
DPT_Enable 1.003
DPT_TimePeriodHrs 7.007 DPT_Switch 1.001
DPT_Switch 1.001
DPT_Switch_Control 2.001 DPT_TimePeriodHrs 7.007 DPT_TimePeriodHrs 7.007
DPT_Reset 1.015
DPT_TimePeriodHrs 7.007
DPT_Bool 1.002
DPT_Value_2Ucount 7.001 DPT_Value_1Ucount 5.010 DPT_Value_2Ucount 7.001
DPT_Value_1Ucount 5.010 DTP_Bool 1.002
DPT_Trigger 1.017
Number of bits
1 bit 1 byte 1 bit
Flags
CWT CW CW
1 bit
CRT
1 bit
CRW
2 byte CRW
1 bit
CW
1 bit
CW
2 bit
CW
2 byte
CW
2 byte
CW
1 bit
CW
2 byte CR(T)
1 bit
CT
2 byte
CW
1 byte
CW
2 byte
CW
1 byte
CW
1 bit
CRT
1 bit
CW
©EAE Technology
www.eaetechnology.com
Page 6 / 22
Product Manual SW108 and SW104 EAE KNX Switch Actuator
4 Parameters
4.1 Main General
SW108/104 R3.0
General Parameters
Enable manual Operation
*yes
no The switch actuator can be switched on or off with slide switches. This parameter determines the
position of relays can be modified manually or not.
Set the parameter to “yes”. Each relay can be operated manually.
Set the parameter to “no”. It is still possible to change relays position but
relay return its old position in a maximum of 16 seconds.
Device alive operation active
yes
*no
This object is used to report that device is still alive and connected the KNX line. Telegram value can
be selected ON/OFF. If a telegram is not received, device may be defective or KNX cable can be
disconnected. If the parameter selected yes;
©EAE Technology
www.eaetechnology.com
Page 7 / 22
Product Manual SW108 and SW104 EAE KNX Switch Actuator
SW108/104 R3.0
In operation value Telegram data can be selected.
*send value 0′ send value
1′
Operation send interval [min]
1…*15…255
Here the time interval which in operation communication object cyclically sends to KNX line.
Activate scene
yes
*no
If the parameter select `yes’, scene screen open on the main window. You can find scene information
under the scene function title.
Overwrite threshold value with download *yes no
During storage of a threshold, the threshold values are stored permanently in
the device. As an alternative, the original values can be reloaded into the
device during each programming run of the ETS.
Set the parameter to “yes”
User threshold values store in the device. This means threshold communication
object will be overwrite threshold values but ETS download can’t write on it.
Set the parameter to “no”
Threshold values stored in the device with a storage function will be maintained. If no threshold values have been stored, the threshold values last programmed in the ETS remain valid.
Overwrite scene values with download
*yes
no During storage of a scene, the scene values are stored permanently in the device. As an alternative,
the original values can be reloaded into the device during each programming run of the ETS.
Set the parameter to “yes”
Scenes values stored in the device. This means scene communication object will
be overwrite scene values but ETS download can’t write on it.
Set the parameter to “no”
Scene values stored in the device with a storage function will be maintained. If no scene values have been stored, the scene values last programmed in the ETS remain valid.
Overwrite operating hour values with
*yes
download
no
During storage of an operating hour, the operating hour values are stored permanently in the device.
As an alternative, the original values can be reloaded into the device during each programming run of
the ETS.
©EAE Technology
www.eaetechnology.com
Page 8 / 22
Product Manual SW108 and SW104 EAE KNX Switch Actuator
SW108/104 R3.0
Set the parameter to “yes”
Operating hour values stored in the device. This means operating hour
communication object will be overwrite operating hour values but ETS download
can’t write on it.
Set the parameter to “no”
Operating hour values stored in the device with a storage function will be maintained. If no operating hour values have been stored, the operating hour values last programmed in the ETS remain valid.
Transmission delay [2…255s] after bus voltage recovery
*2…255
The parameter defines the behaviour of the switch actuator at a bus power return. The transmission
delay time determines the period between bus voltage recovery and the point after which telegrams
can be sent.
Telegram limit active
yes
*no
Parameter selects “yes”;
Telegram limit period
50ms…*10s…1min
The limit period can be adjusted via this parameter.
Max. number of transmitted telegrams
1…20…255
within a period
Max number of telegrams per period, can be sent freely.
©EAE Technology
www.eaetechnology.com
Page 9 / 22
Product Manual SW108 and SW104 EAE KNX Switch Actuator
4.2 Scene
SW108/104 R3.0
Scene Parameters
The scene function of the switch actuator has an 8 bit scene object. It is
possible to define for each 64 scene with parameter window. 8 independent
values can be stored for each relay. The scene can be specified that the relay
open contact’ (off),
close contact’ (on) or `keep position’ its state.
A scene is activated when it receives its scene number at the scene object. The storing of the current channel values is carried out using the scene object.
For example;
Scene
1 2 3 4 5 6 7 8 9 10 11 … 63 64
recall
Hex.
Des.
0x00
0
0x01
1
0x02
2
0x03
3
0x04
4
0x05
5
0x06
6
0x07
7
0x08
8
0x09
9
0x0A
10
…
…
0x3E
62
0x3F
63
save
Hex.
Des.
0x80
128
0x81
129
0x82
130
0x83
131
0x84
132
0x85
133
0x86
134
0x87
135
0x88
136
0x89
137
0x8A
138
…
…
0xE2
190
0xE3
191
©EAE Technology
www.eaetechnology.com
Page 10 / 22
Product Manual SW108 and SW104 EAE KNX Switch Actuator
4.3 Channel General
SW108/104 R3.0
Channel General Parameters
Contact type
normally closed *normally open
The relays of a switching output can be parameterized as normally closed or normally open. This feature offers the possibility of inversion the switching state. Important: This state is only valid for switch communication object. Other relay function always works normally.
Normally closed contact
Switch state = off (0) relay contact closed Switch state = on (1) relay
contact open
Normally open contact
Switch state = off (0) relay contact open Switch state = on (1) relay contact
closed
NOTE: Switch Status object shows switch state which it is shown at information label on device.
Send switch status feedback telegram
no
after change
after request *after change or request The switch status feedback can be used as an active or passive communication object. Active
message object, the switch status telegram is transmitted to the bus automatically when a relay state
changes. Passive status object, there is no telegram transmission after relay state changes. If you
want to learn switch status, you must read communication object. Communication object flags are
automatically set by ETS.
NOTE: Switching state changes by manual operation are not detected.
©EAE Technology
www.eaetechnology.com
Page 11 / 22
Product Manual SW108 and SW104 EAE KNX Switch Actuator
SW108/104 R3.0
Create status object “Status Switch”
*yes
no
If this parameter select `yes’, ETS create another communication object for use only status switch.
The status object can be used to display the current output switching status on a display.
Send status after bus voltage return
yes
*no
You can use this parameter to send the switching state in the event of bus voltage recovery.
Behaviour after ETS program
*keep position
open contact
close contact
After ETS programming, relay position set the wanted switching position.
Set the parameter to “keep position”
In this setting, the relay remains in the current state. Any manual operation occurs in the meantime the switch actuator return its old position. The device doesn’t know the status of the relay.
Set the parameter to “open contact” or “close contact”
The relay contact open or close after bus voltage return.
Behaviour bus voltage failure
*keep position open contact close contact
When the bus voltage fails, the device set the wanted switching state of the output. The relay can be
open, close or keep position it occupied prior to the failure. At the same time, the current switching
position of the relay is stored in the devices.
Behaviour bus voltage return
keep position
open contact
close contact
*state as before bus voltage failure
When the bus voltage returns, the device set the wanted switching state of the output.
Set the parameter to “keep position”
In this setting, the relay remains in the current state. Any manual operation
occurs in the meantime the switch actuator return its old position. The device
doesn’t know the status of the relay.
Set the parameter to “open contact” or “close contact”
The relay contact open or close after bus voltage return.
Set the parameter to “state as before bus voltage failure”
If the parameter set to “state as before bus voltage failure”, then the relay is set to the value. The value stored at the time of the bus voltage failure.
©EAE Technology
www.eaetechnology.com
Page 12 / 22
Product Manual SW108 and SW104 EAE KNX Switch Actuator
4.4 Function
SW108/104 R3.0
Above function parameters can be set for each channel. These functions;
I. Staircase II. External logic III. Internal logic IV. Priority V. Threshold
VI. Operating hour VII. Sweep
Please find description of these functions below.
Function Parameters
©EAE Technology
www.eaetechnology.com
Page 13 / 22
Product Manual SW108 and SW104 EAE KNX Switch Actuator
4.4.1 Staircase Function
SW108/104 R3.0
Staircase Function Parameters
In order to use staircase function, `Staircase’ should be enabled on the
function window. Than required parameters and communication objects will be
visible. The staircase function can be parameterized for each channel.
Staircase function has got a three communication object. These are “Enable staircase function”, “Staircase lighting duration” and “Permanent ON”.
Duration of staircase lighting [min]/ [sec]
0…5…240[min] 0…59 [sec]
Staircase function on time is calculated by “duration of staircase lighting”. Staircase lighting time is defined by this parameter. At the end of the on time, the relay off or active the staircase warning
functions.
Staircase retrigger
*not retriggerable
yes retriggerable
up to staircase lighting time 2x
up to staircase lighting time 3x
up to staircase lighting time 4x
up to staircase lighting time 5x This parameter defines whether the staircase on time can be retrigger able or not so the on time can
be extended by `Enable staircase function’. You can repeat retrigger function until the repeater count
reached the maximum value (2x, 3x, 4x, 5x). If the parameter selects `not retriggerable’, staircase on
time doesn’t extend.
Reaction to OFF telegram
*switch off
Ignore
After this parameter selected switching off’, ignored
Enable staircase
function’ communication
object `disable’ command.
©EAE Technology
www.eaetechnology.com
Page 14 / 22
Product Manual SW108 and SW104 EAE KNX Switch Actuator
SW108/104 R3.0
Staircase time can be changed by object
yes
*no
Staircase lighting duration’ communication object is visible if a
Staircase
time can be changed by
object’ parameter selects `yes’. This communication object is 2 byte. The value defines the staircase
on time in second.
NOTE: After a bus voltage fails, staircase on time returns default value (Duration of staircase lighting).
Restart staircase after “Permanent ON”
yes
*no
If this parameter is selected yes’, receive
Permanent ON’ communication
object after restart
staircase function.
Activate pre-warning time?
yes
*no
The warning function can be activated by this parameter select `yes’. Then, you can adjust pre-
warning time, number of pre-warning and time for pre-warning interval. The warning function is for
warning that the staircase lighting time run out and the lights are switched off soon. In the warning,
lights short turn off. Switch status is ON until finish warning time.
Pre-warning time Minutes (0…59)
*0…59
Second (0…59)
0…*30…59
How long the lights shall be switched on in the period.
Number of pre-warning (1…10)
1…*2…10
Enter the number of how many blink doing in the warning.
Time for pre-warning intervals
0…*3…59
Seconds (0…59)
How long the lights shall be switched off in the period.
Activate on delay
yes
*no
This parameter is used to delay switch off position before staircase start.
©EAE Technology
www.eaetechnology.com
Page 15 / 22
Product Manual SW108 and SW104 EAE KNX Switch Actuator
4.4.2 External Logic Function
SW108/104 R3.0
External Logic Parameters
Logic function can be used independently for each output. With this function,
the Switch’ object can be logically linked with the
External logic input’.
Channel relay switch a result of the logic operation. For example Switch’ object value 1 and
External logic input’ object value 0 relay switch as a
result of 1 & 0 operation.
External logic function type
*AND
OR
XOR This parameter selects the type of logic function between Switch’ and
External logic input’ objects.
Invert result
yes
*no
If you want to inverted logic function result, you should select `yes’.
Logic object value after bus voltage return “1” *”0″
This parameter defines the value of the `External logic input’ object after
bus voltage return.
NOTE: The values of the `External logic’ communication objects doesn’t store at the bus voltage failure.
©EAE Technology
www.eaetechnology.com
Page 16 / 22
Product Manual SW108 and SW104 EAE KNX Switch Actuator
4.4.3 Internal Logic Function
SW108/104 R3.0
Internal Logic Parameters
You can enter the opening or closing scenario of the channel. In this
function, each relay can be switched only one time because this reaction
protects the devices from infinite loop. An internal logic function can be
parameterized separately for each output. The relay of the channel doesn’t
participate to the scenario.
Relay 1…8 state
*don’t care
off
on
To create scenario to open or close channel relay, positions of other channels of the switch actuator
are set with these parameters. The channels that doesn’t need to participate this scenario should be
left don’t care.
4.4.4 Priority Function
If the priority function is enabled, `Forced positioning’ communication object
is visible. It hasn’t got any parameter. This is the standard forced position
working.
Bit 1 Bit 0
0
0
0
1
1
0
1
1
Function
forced positioning not active normal control forced positioning not active
normal control Forced positioning active switch off Forced positioning
active switch on
©EAE Technology
www.eaetechnology.com
Page 17 / 22
Product Manual SW108 and SW104 EAE KNX Switch Actuator
4.4.5 Threshold Function
SW108/104 R3.0
Threshold Parameters
The function can be configured 1 byte or 2 byte. The value of Threshold input
communication object falls below or exceeds a limit of threshold value. Then
the relay position can be changed by this way.
Object size
*1 byte
2 byte The threshold value function data type determined here. All of the parameters associated with it
which will change.
Threshold value
0…*128…255 (for 1 byte)
0…*20000…65535 (for 2 byte)
Threshold limit value enters here. This parameter is dependent `Object size’ parameter.
Threshold reaction
*OFF (0) below threshold, ON (1) above threshold
ON (1) below threshold, OFF (0) above threshold This parameter determines the switch state. If the value of the `Threshold input’ communication
object value bellows or above the threshold limit value, the relay switched on or off position.
Threshold value can be changed
yes
by object
*no
If the parameter selects yes’,
Threshold value’ communication object is
visible. Threshold value can
be changed by this object.
Threshold hysteresis
yes
*no
Hysteresis is dependence of a system not only its current value but also on its past value.
If the parameter selects `yes’;
©EAE Technology
www.eaetechnology.com
Page 18 / 22
Product Manual SW108 and SW104 EAE KNX Switch Actuator
Hysteresis percentage (1…10)
%1…*%5…%11
SW108/104 R3.0
For example: Hysteresis percentage parameter selected %10. You can see this state below graphic. Threshold hysteresis value measure formula 100 * 10 / 100 = 10 and threshold high and low limit 100 +- 10.
Threshold Graphic
©EAE Technology
www.eaetechnology.com
Page 19 / 22
Product Manual SW108 and SW104 EAE KNX Switch Actuator
4.4.6 Operating Hour Function
SW108/104 R3.0
Operating Hour Parameters
The operating hours count the relay on time. The operating hours sums up to
determine on time. The accumulated operating hours are stored in the 2 byte
counter. The counter value sends to bus cyclically or after request. If the
voltage fails or ETS programming, all operating hour counter stored in the
devices. After the bus voltage returns, the device updates communication
object value.
NOTE: User changed relay position by hand; device cannot detect it so operating hour doesn’t start the counting.
Counter type
*up counter
down counter Up counter: The operating hours start the count from ‘0’. The maximum counting value is 65535
hours. When the operating hour reached limit value, `Operating hour runout’ telegram sends to bus.
Then the operating hours counter stop.
Down counter: The operating hours preset value counting down. When the counter
reached 0′, the counting status is reported to the bus via
Operating hour
runout’.
Limit value preset
no preset
*set with parameter
set with object
The start or limit value preset here. A limit value can be preset as an option.
No preset
For up/down counter the limit value set to 65535. This is the maximum value both of operating hour.
©EAE Technology
www.eaetechnology.com
Page 20 / 22
Product Manual SW108 and SW104 EAE KNX Switch Actuator
SW108/104 R3.0
Set with parameter
This parameter selects; `Limit value/Counter start’ parameter is visible. This
parameter is used for setting limit value of up counter, start value of down
counter.
Set with object
This parameter defines whether the start/limit value can be individually adapted from the bus.
Send counter value
cyclic sending
*after request
cyclic sending and after request The current count of the operating hours can
be learned three way cyclic sending’,
after request’
and `cyclic sending and after request’.
4.4.7 Sweep Function
Sweep Parameters
Sweep function only starts to operate if the relay is switched ON. It’s an
alternative way for turning off the relay with pre-warning. The sweep function
is desired to warn a person that lights will go out shortly.
Send counter value
1…*3…10
The lamps connected to the relay will then be switched off as many times. Enter the number of how
many blink doing in the warning.
Blink on time
0,5sec…*1sec…5sec
How long the lights shall be switched on in the period.
©EAE Technology
www.eaetechnology.com
Page 21 / 22
Product Manual SW108 and SW104 EAE KNX Switch Actuator
Blink off time
*300ms…1sec
How long the lights shall be switched off in the period.
Wait time after blinks (sec)
0…*30…255
How long the lights shall be switched on after sweep blink finished.
5 Process Priority Table
SW108/104 R3.0
©EAE Technology
www.eaetechnology.com
Page 22 / 22