EAE SW104 KNX Switch Actuator Instruction Manual Product Information

May 15, 2024
EAE

SW104 KNX Switch Actuator

“`html

Product Information

Specifications

Product Name: EAE KNX Switch Actuator

Model: SW108/104 R3.0

Order Number: 48002

Channels: 8 independent channels

Relay Type: Bistable switching relay with
16A/20AX (C-Load) relays

Operating Feature: Manual operation with slide
switches

Device Technology

Connection Diagram

Technical Data

  • Type of Protection: IP 20

  • Safety Class: II

  • Power Supply: 21V to 30V DC, SELV, < 10
    mA

  • Connections: Screw terminals

  • Switching Voltage: 277/440V AC; 50/60 Hz

  • Switching Capacity: 16A / AC 1

  • Output Life: > 3 x 10^6 cycles

  • Type of Contact: Potential-free, bistable

  • Temperature Range: – Ambient: SW108 – 65.5 x
    143 x 89mm, SW104 – 0.15 kg

  • Humidity: In accordance with the EMC guideline
    and low voltage communications

Product Usage Instructions

Configuration and Setup

To configure the switch actuator, you will need the ETS
application file .knxprod available on the EAE website. ETS
(Engineering Tool Software) is required for programming the device.
Parameter settings and related group addresses can be changed using
ETS. Follow the instructions in the ETS help file for more
details.

Operating the Device

  1. Each channel can be configured with ETS3/ETS4 or higher
    versions.

  2. The relay position is selected based on parameterization after
    bus voltage failure or return.

  3. The device has a manual operating feature allowing you to
    switch the relay on or off with slide switches.

  4. The C-Load feature enables convenient control of fluorescent
    lamps.

Maintenance and Care

Ensure proper power supply within the specified voltage range.
Regularly check connections and tighten screw terminals as needed.
Keep the device clean and free from dust or debris to maintain
optimal performance.

Frequently Asked Questions (FAQ)

Q: What is the default physical address of the device?

A: The default physical address is 15.15.255 for each
channel.

Q: How can I change the parameter settings of the device?

A: You can change the parameter settings and group addresses
using the ETS application file .knxprod available on the EAE
website. Follow the instructions in the ETS help file for detailed
guidance.

“`

EAE KNX Switch Actuator
Product Manual SW104 and SW108
Order Number: 48002

Product Manual SW108 and SW104 EAE KNX Switch Actuator

SW108/104 R3.0

Content
1 General ………………………………………………………………………………………………………………………….. 2 2 Device Technology ………………………………………………………………………………………………………….. 3
2.1 Connection Diagram…………………………………………………………………………………………………. 3 2.2 Technical Data …………………………………………………………………………………………………………. 5 3 Communication Object Table……………………………………………………………………………………………. 6 4 Parameters …………………………………………………………………………………………………………………….. 7 4.1 Main General…………………………………………………………………………………………………………… 7 4.2 Scene ……………………………………………………………………………………………………………………. 10 4.3 Channel General …………………………………………………………………………………………………….. 11 4.4 Function………………………………………………………………………………………………………………… 13
4.4.1 Staircase Function …………………………………………………………………………………………… 14 4.4.2 External Logic Function ……………………………………………………………………………………. 16 4.4.3 Internal Logic Function …………………………………………………………………………………….. 17 4.4.4 Priority Function ……………………………………………………………………………………………… 17 4.4.5 Threshold Function………………………………………………………………………………………….. 18 4.4.6 Operating Hour Function………………………………………………………………………………….. 20 4.4.7 Sweep Function ………………………………………………………………………………………………. 21 5 Process Priority Table …………………………………………………………………………………………………….. 22

©EAE Technology

www.eaetechnology.com

Page 1 / 22

Product Manual SW108 and SW104 EAE KNX Switch Actuator

SW108/104 R3.0

1 General
EAE KNX Switch Actuator has eight channels which can be configured with ETS3/ETS4 or higher version. Each channel is independent of another. It has a separate bistable switching relay. SW108 / SW104 has been designed especially for loads with high surge currents. It has 16A/20AX (C-Load) relays inside channels. C-Load feature enables a convenient control of fluorescent lambs. Also device has a manual operating feature. The relay can be switched on or off with slide switches.

The following function list provides;
· Staircase · External logic · Internal logic · Priority · Threshold · Operating hour · Sweep
Each channel of devices can choose any of these functions. The outputs are parameterized individually via ETS3/4. After bus voltage failure or voltage return the relay position is selected on dependence on the parameterization. In “ETS reset”, device parameters are return download configuration.
NOTE: Each channel is uniform. Device factory default physical address is 15.15.255.

©EAE Technology

www.eaetechnology.com

Page 2 / 22

Product Manual SW108 and SW104 EAE KNX Switch Actuator
2 Device Technology
2.1 Connection Diagram

SW108/104 R3.0 Connection Diagram

©EAE Technology

www.eaetechnology.com

Page 3 / 22

Product Manual SW108 and SW104 EAE KNX Switch Actuator

SW108/104 R3.0

1. Physical Address Label 2. Programming Button 3. Red Programming LED 4. KNX Connection Terminal 5. Switch Position Display and ON/OFF Manual Actuation

©EAE Technology

www.eaetechnology.com

Page 4 / 22

Product Manual SW108 and SW104 EAE KNX Switch Actuator
2.2 Technical Data

SW108/104 R3.0

Type of protection Safety class Power supply : External supply Connections
Output
Output life Type of contact Installation Operating elements Temperature range
Humidity Dimensions Weight Box CE Application program

IP 20

EN 60 529

II

EN 61 140

– Voltage – Current consumption

21V… 30V DC, SELV < 10 mA

– Screw terminals – Max tightening torque

0,5…4 mm² solid and stranded wire 0,5…2,5mm² stranded wire with ferrule 0.8 Nm

– KNX

Bus connect terminal

– Number

4 output ­ SW104 8 output ­ SW108

– Switching voltage

277/440V AC; 50/60 Hz

– Switching capacity 277 V AC

16A / AC 1

– Fluorescent lighting load to EN 60 16 AX/250 VAC

669-1 – Mechanical life

3 x 106

– potential-free, bistable

– 35mm mounting rail

EN 60 715

– LED (red) and button – Ambient – Storage – Transport – max. air humidity

For physical address -5° C + 45° C -25° C + 55° C -25° C + 70° C 95 % no moisture condensation

SW108 – 65,5 x 143 x 89mm

SW104 ­ 65,5 x 72 x 89 mm SW108 0.45 kg

SW104 0.15 kg Plastic, polycarbonate, colour grey

In accordance with the EMC

guideline and low voltage

Communications

Number of addresses(max) Number of

objects

122

253

assignments(max) 253

NOTE: Device default physical address is 15.15.255. In order to configure switch actuator, ETS application file “.knxprod” is needed. It’s possible to download the file on EAE website. ETS is required for programming the device. Parameter settings and related group addresses can be changed by ETS. Learn more by reading ETS help file.

©EAE Technology

www.eaetechnology.com

Page 5 / 22

Product Manual SW108 and SW104 EAE KNX Switch Actuator

SW108/104 R3.0

3 Communication Object Table

The following 122 communication objects are available in the SW108 and SW104.

No

Object name

Function

DTP Type

0 1 2, 17, 32, 47, 62, 77, 92, 107 3, 18, 33, 48 63, 78, 93, 108 4, 19, 34, 49, 64, 79, 94, 109 5, 20, 35, 50, 65, 80, 95, 110 6, 21, 36, 51, 66, 81, 96, 111 7, 22, 37, 52, 67, 82, 97, 112 8, 23, 38, 53, 68, 83, 98, 113 9, 24, 39, 54, 69, 84, 99, 114
10, 25, 40, 55, 70, 85, 100, 115
11, 26, 41, 56, 71, 86, 101, 116
12, 27, 42, 57, 72, 87, 102, 117
13, 28, 43, 58, 73, 88, 103, 118

General, In operation General Scene 8-bit Output 1, Switch
Output 1,Status Switch
Output 1,Enable staircase function Output 1,Staircase lighting duration Output 1,Permanent ON
Output 1,External logic input Output 1,Forced positioning
Output 1,Start value of operating hour Output 1,Limit value of operating hour Output 1,Counter reset of opr. hour
Output 1,Current value of opr. hour
Output 1,Operating hour runout
Output 1,Threshold input
Output 1,Threshold input

true / false recall / save on / off on / off enable / disable 0h … 65535h on / off on / off on / off 0h … 65535 hour 0h … 65535 hour No action/reset trig 0h … 65535h
true / false
Value 0…65535 Value 0…255

14, 29, 44, 59, 74, 89, 104, 119

Output 1,Threshold value Output 1,Threshold value

Value 0…65535 Value 0…255

15, 30, 45, 60, 75, 90, 105, 120
16, 31, 46, 61, 76, 91, 106, 121

Output 1,Threshold status Output 1,Sweep

true / false trigger

DTP_Bool 1.002 DPT_Scene 18.001 DPT_Switch 1.001
DPT_Switch 1.001
DPT_Enable 1.003
DPT_TimePeriodHrs 7.007 DPT_Switch 1.001
DPT_Switch 1.001
DPT_Switch_Control 2.001 DPT_TimePeriodHrs 7.007 DPT_TimePeriodHrs 7.007 DPT_Reset 1.015
DPT_TimePeriodHrs 7.007
DPT_Bool 1.002
DPT_Value_2Ucount 7.001 DPT_Value_1Ucount 5.010 DPT_Value_2Ucount 7.001 DPT_Value_1Ucount 5.010 DTP_Bool 1.002
DPT_Trigger 1.017

Number of bits
1 bit 1 byte 1 bit

Flags
CWT CW CW

1 bit

CRT

1 bit

CRW

2 byte CRW

1 bit

CW

1 bit

CW

2 bit

CW

2 byte

CW

2 byte

CW

1 bit

CW

2 byte CR(T)

1 bit

CT

2 byte

CW

1 byte

CW

2 byte

CW

1 byte

CW

1 bit

CRT

1 bit

CW

©EAE Technology

www.eaetechnology.com

Page 6 / 22

Product Manual SW108 and SW104 EAE KNX Switch Actuator
4 Parameters
4.1 Main General

SW108/104 R3.0

General Parameters

Enable manual Operation

*yes

no The switch actuator can be switched on or off with slide switches. This parameter determines the

position of relays can be modified manually or not.

Set the parameter to “yes”. Each relay can be operated manually.
Set the parameter to “no”. It is still possible to change relays position but relay return its old position in a maximum of 16 seconds.

Device alive operation active

yes

*no

This object is used to report that device is still alive and connected the KNX line. Telegram value can

be selected ON/OFF. If a telegram is not received, device may be defective or KNX cable can be

disconnected. If the parameter selected yes;

©EAE Technology

www.eaetechnology.com

Page 7 / 22

Product Manual SW108 and SW104 EAE KNX Switch Actuator

SW108/104 R3.0

In operation value Telegram data can be selected.

*send value 0′ send value1′

Operation send interval [min]

1…*15…255

Here the time interval which in operation communication object cyclically sends to KNX line.

Activate scene

yes

*no

If the parameter select `yes’, scene screen open on the main window. You can find scene information

under the scene function title.

Overwrite threshold value with download *yes no
During storage of a threshold, the threshold values are stored permanently in the device. As an alternative, the original values can be reloaded into the device during each programming run of the ETS.
Set the parameter to “yes”

User threshold values store in the device. This means threshold communication object will be overwrite threshold values but ETS download can’t write on it.
Set the parameter to “no”

Threshold values stored in the device with a storage function will be maintained. If no threshold values have been stored, the threshold values last programmed in the ETS remain valid.

Overwrite scene values with download

*yes

no During storage of a scene, the scene values are stored permanently in the device. As an alternative,

the original values can be reloaded into the device during each programming run of the ETS.

Set the parameter to “yes”

Scenes values stored in the device. This means scene communication object will be overwrite scene values but ETS download can’t write on it.
Set the parameter to “no”

Scene values stored in the device with a storage function will be maintained. If no scene values have been stored, the scene values last programmed in the ETS remain valid.

Overwrite operating hour values with

*yes

download

no

During storage of an operating hour, the operating hour values are stored permanently in the device.

As an alternative, the original values can be reloaded into the device during each programming run of

the ETS.

©EAE Technology

www.eaetechnology.com

Page 8 / 22

Product Manual SW108 and SW104 EAE KNX Switch Actuator

SW108/104 R3.0

Set the parameter to “yes”

Operating hour values stored in the device. This means operating hour communication object will be overwrite operating hour values but ETS download can’t write on it.
Set the parameter to “no”

Operating hour values stored in the device with a storage function will be maintained. If no operating hour values have been stored, the operating hour values last programmed in the ETS remain valid.

Transmission delay [2…255s] after bus voltage recovery

*2…255

The parameter defines the behaviour of the switch actuator at a bus power return. The transmission

delay time determines the period between bus voltage recovery and the point after which telegrams

can be sent.

Telegram limit active

yes

*no

Parameter selects “yes”;

Telegram limit period

50ms…*10s…1min

The limit period can be adjusted via this parameter.

Max. number of transmitted telegrams

1…20…255

within a period

Max number of telegrams per period, can be sent freely.

©EAE Technology

www.eaetechnology.com

Page 9 / 22

Product Manual SW108 and SW104 EAE KNX Switch Actuator
4.2 Scene

SW108/104 R3.0

Scene Parameters
The scene function of the switch actuator has an 8 bit scene object. It is possible to define for each 64 scene with parameter window. 8 independent values can be stored for each relay. The scene can be specified that the relay open contact’ (off),close contact’ (on) or `keep position’ its state.

A scene is activated when it receives its scene number at the scene object. The storing of the current channel values is carried out using the scene object.

For example;

Scene
1 2 3 4 5 6 7 8 9 10 11 … 63 64

recall

Hex.

Des.

0x00

0

0x01

1

0x02

2

0x03

3

0x04

4

0x05

5

0x06

6

0x07

7

0x08

8

0x09

9

0x0A

10

0x3E

62

0x3F

63

save

Hex.

Des.

0x80

128

0x81

129

0x82

130

0x83

131

0x84

132

0x85

133

0x86

134

0x87

135

0x88

136

0x89

137

0x8A

138

0xE2

190

0xE3

191

©EAE Technology

www.eaetechnology.com

Page 10 / 22

Product Manual SW108 and SW104 EAE KNX Switch Actuator
4.3 Channel General

SW108/104 R3.0

Channel General Parameters

Contact type

normally closed *normally open

The relays of a switching output can be parameterized as normally closed or normally open. This feature offers the possibility of inversion the switching state. Important: This state is only valid for switch communication object. Other relay function always works normally.

Normally closed contact
Switch state = off (0) relay contact closed Switch state = on (1) relay contact open

Normally open contact
Switch state = off (0) relay contact open Switch state = on (1) relay contact closed

NOTE: Switch Status object shows switch state which it is shown at information label on device.

Send switch status feedback telegram

no

after change

after request *after change or request The switch status feedback can be used as an active or passive communication object. Active

message object, the switch status telegram is transmitted to the bus automatically when a relay state

changes. Passive status object, there is no telegram transmission after relay state changes. If you

want to learn switch status, you must read communication object. Communication object flags are

automatically set by ETS.

NOTE: Switching state changes by manual operation are not detected.

©EAE Technology

www.eaetechnology.com

Page 11 / 22

Product Manual SW108 and SW104 EAE KNX Switch Actuator

SW108/104 R3.0

Create status object “Status Switch”

*yes

no

If this parameter select `yes’, ETS create another communication object for use only status switch.

The status object can be used to display the current output switching status on a display.

Send status after bus voltage return

yes

*no

You can use this parameter to send the switching state in the event of bus voltage recovery.

Behaviour after ETS program

*keep position

open contact

close contact

After ETS programming, relay position set the wanted switching position.

Set the parameter to “keep position”

In this setting, the relay remains in the current state. Any manual operation occurs in the meantime the switch actuator return its old position. The device doesn’t know the status of the relay.

Set the parameter to “open contact” or “close contact”

The relay contact open or close after bus voltage return.

Behaviour bus voltage failure

*keep position open contact close contact

When the bus voltage fails, the device set the wanted switching state of the output. The relay can be

open, close or keep position it occupied prior to the failure. At the same time, the current switching

position of the relay is stored in the devices.

Behaviour bus voltage return

keep position

open contact

close contact

*state as before bus voltage failure

When the bus voltage returns, the device set the wanted switching state of the output.

Set the parameter to “keep position”

In this setting, the relay remains in the current state. Any manual operation occurs in the meantime the switch actuator return its old position. The device doesn’t know the status of the relay.
Set the parameter to “open contact” or “close contact”

The relay contact open or close after bus voltage return.

Set the parameter to “state as before bus voltage failure”

If the parameter set to “state as before bus voltage failure”, then the relay is set to the value. The value stored at the time of the bus voltage failure.

©EAE Technology

www.eaetechnology.com

Page 12 / 22

Product Manual SW108 and SW104 EAE KNX Switch Actuator
4.4 Function

SW108/104 R3.0

Above function parameters can be set for each channel. These functions;
I. Staircase II. External logic III. Internal logic IV. Priority V. Threshold VI. Operating hour VII. Sweep
Please find description of these functions below.

Function Parameters

©EAE Technology

www.eaetechnology.com

Page 13 / 22

Product Manual SW108 and SW104 EAE KNX Switch Actuator
4.4.1 Staircase Function

SW108/104 R3.0

Staircase Function Parameters
In order to use staircase function, `Staircase’ should be enabled on the function window. Than required parameters and communication objects will be visible. The staircase function can be parameterized for each channel.

Staircase function has got a three communication object. These are “Enable staircase function”, “Staircase lighting duration” and “Permanent ON”.

Duration of staircase lighting [min]/ [sec]

0…5…240[min] 0…59 [sec]

Staircase function on time is calculated by “duration of staircase lighting”. Staircase lighting time is defined by this parameter. At the end of the on time, the relay off or active the staircase warning

functions.

Staircase retrigger

*not retriggerable

yes retriggerable

up to staircase lighting time 2x

up to staircase lighting time 3x

up to staircase lighting time 4x

up to staircase lighting time 5x This parameter defines whether the staircase on time can be retrigger able or not so the on time can

be extended by `Enable staircase function’. You can repeat retrigger function until the repeater count

reached the maximum value (2x, 3x, 4x, 5x). If the parameter selects `not retriggerable’, staircase on

time doesn’t extend.

Reaction to OFF telegram

*switch off

Ignore

After this parameter selected switching off’, ignoredEnable staircase function’ communication

object `disable’ command.

©EAE Technology

www.eaetechnology.com

Page 14 / 22

Product Manual SW108 and SW104 EAE KNX Switch Actuator

SW108/104 R3.0

Staircase time can be changed by object

yes

*no

Staircase lighting duration’ communication object is visible if aStaircase time can be changed by

object’ parameter selects `yes’. This communication object is 2 byte. The value defines the staircase

on time in second.

NOTE: After a bus voltage fails, staircase on time returns default value (Duration of staircase lighting).

Restart staircase after “Permanent ON”

yes

*no

If this parameter is selected yes’, receivePermanent ON’ communication object after restart

staircase function.

Activate pre-warning time?

yes

*no

The warning function can be activated by this parameter select `yes’. Then, you can adjust pre-

warning time, number of pre-warning and time for pre-warning interval. The warning function is for

warning that the staircase lighting time run out and the lights are switched off soon. In the warning,

lights short turn off. Switch status is ON until finish warning time.

Pre-warning time Minutes (0…59)

*0…59

Second (0…59)

0…*30…59

How long the lights shall be switched on in the period.

Number of pre-warning (1…10)

1…*2…10

Enter the number of how many blink doing in the warning.

Time for pre-warning intervals

0…*3…59

Seconds (0…59)

How long the lights shall be switched off in the period.

Activate on delay

yes

*no

This parameter is used to delay switch off position before staircase start.

©EAE Technology

www.eaetechnology.com

Page 15 / 22

Product Manual SW108 and SW104 EAE KNX Switch Actuator
4.4.2 External Logic Function

SW108/104 R3.0

External Logic Parameters
Logic function can be used independently for each output. With this function, the Switch’ object can be logically linked with theExternal logic input’. Channel relay switch a result of the logic operation. For example Switch’ object value 1 andExternal logic input’ object value 0 relay switch as a result of 1 & 0 operation.

External logic function type

*AND

OR

XOR This parameter selects the type of logic function between Switch’ and External logic input’ objects.

Invert result

yes

*no

If you want to inverted logic function result, you should select `yes’.

Logic object value after bus voltage return “1” *”0″
This parameter defines the value of the `External logic input’ object after bus voltage return.

NOTE: The values of the `External logic’ communication objects doesn’t store at the bus voltage failure.

©EAE Technology

www.eaetechnology.com

Page 16 / 22

Product Manual SW108 and SW104 EAE KNX Switch Actuator
4.4.3 Internal Logic Function

SW108/104 R3.0

Internal Logic Parameters
You can enter the opening or closing scenario of the channel. In this function, each relay can be switched only one time because this reaction protects the devices from infinite loop. An internal logic function can be parameterized separately for each output. The relay of the channel doesn’t participate to the scenario.

Relay 1…8 state

*don’t care

off

on

To create scenario to open or close channel relay, positions of other channels of the switch actuator

are set with these parameters. The channels that doesn’t need to participate this scenario should be

left don’t care.

4.4.4 Priority Function
If the priority function is enabled, `Forced positioning’ communication object is visible. It hasn’t got any parameter. This is the standard forced position working.

Bit 1 Bit 0

0

0

0

1

1

0

1

1

Function
forced positioning not active ­ normal control forced positioning not active ­ normal control Forced positioning active ­ switch off Forced positioning active ­ switch on

©EAE Technology

www.eaetechnology.com

Page 17 / 22

Product Manual SW108 and SW104 EAE KNX Switch Actuator
4.4.5 Threshold Function

SW108/104 R3.0

Threshold Parameters
The function can be configured 1 byte or 2 byte. The value of Threshold input communication object falls below or exceeds a limit of threshold value. Then the relay position can be changed by this way.

Object size

*1 byte

2 byte The threshold value function data type determined here. All of the parameters associated with it

which will change.

Threshold value

0…*128…255 (for 1 byte)

0…*20000…65535 (for 2 byte)

Threshold limit value enters here. This parameter is dependent `Object size’ parameter.

Threshold reaction

*OFF (0) below threshold, ON (1) above threshold

ON (1) below threshold, OFF (0) above threshold This parameter determines the switch state. If the value of the `Threshold input’ communication

object value bellows or above the threshold limit value, the relay switched on or off position.

Threshold value can be changed

yes

by object

*no

If the parameter selects yes’,Threshold value’ communication object is visible. Threshold value can

be changed by this object.

Threshold hysteresis

yes

*no

Hysteresis is dependence of a system not only its current value but also on its past value.

If the parameter selects `yes’;

©EAE Technology

www.eaetechnology.com

Page 18 / 22

Product Manual SW108 and SW104 EAE KNX Switch Actuator
Hysteresis percentage (1…10)

%1…*%5…%11

SW108/104 R3.0

For example: Hysteresis percentage parameter selected %10. You can see this state below graphic. Threshold hysteresis value measure formula 100 * 10 / 100 = 10 and threshold high and low limit 100 +- 10.

Threshold Graphic

©EAE Technology

www.eaetechnology.com

Page 19 / 22

Product Manual SW108 and SW104 EAE KNX Switch Actuator
4.4.6 Operating Hour Function

SW108/104 R3.0

Operating Hour Parameters
The operating hours count the relay on time. The operating hours sums up to determine on time. The accumulated operating hours are stored in the 2 byte counter. The counter value sends to bus cyclically or after request. If the voltage fails or ETS programming, all operating hour counter stored in the devices. After the bus voltage returns, the device updates communication object value.

NOTE: User changed relay position by hand; device cannot detect it so operating hour doesn’t start the counting.

Counter type

*up counter

down counter Up counter: The operating hours start the count from ‘0’. The maximum counting value is 65535

hours. When the operating hour reached limit value, `Operating hour runout’ telegram sends to bus.

Then the operating hours counter stop.

Down counter: The operating hours preset value counting down. When the counter reached 0′, the counting status is reported to the bus viaOperating hour runout’.

Limit value preset

no preset

*set with parameter

set with object

The start or limit value preset here. A limit value can be preset as an option.

No preset

For up/down counter the limit value set to 65535. This is the maximum value both of operating hour.

©EAE Technology

www.eaetechnology.com

Page 20 / 22

Product Manual SW108 and SW104 EAE KNX Switch Actuator

SW108/104 R3.0

Set with parameter

This parameter selects; `Limit value/Counter start’ parameter is visible. This parameter is used for setting limit value of up counter, start value of down counter.
Set with object

This parameter defines whether the start/limit value can be individually adapted from the bus.

Send counter value

cyclic sending

*after request

cyclic sending and after request The current count of the operating hours can be learned three way cyclic sending’,after request’

and `cyclic sending and after request’.

4.4.7 Sweep Function

Sweep Parameters
Sweep function only starts to operate if the relay is switched ON. It’s an alternative way for turning off the relay with pre-warning. The sweep function is desired to warn a person that lights will go out shortly.

Send counter value

1…*3…10

The lamps connected to the relay will then be switched off as many times. Enter the number of how

many blink doing in the warning.

Blink on time

0,5sec…*1sec…5sec

How long the lights shall be switched on in the period.

©EAE Technology

www.eaetechnology.com

Page 21 / 22

Product Manual SW108 and SW104 EAE KNX Switch Actuator

Blink off time

*300ms…1sec

How long the lights shall be switched off in the period.

Wait time after blinks (sec)

0…*30…255

How long the lights shall be switched on after sweep blink finished.

5 Process Priority Table

SW108/104 R3.0

©EAE Technology

www.eaetechnology.com

Page 22 / 22