Eltako EAW12DX-UC Analogue Settable Time Relay Instruction Manual
- June 3, 2024
- Eltako
Table of Contents
Eltako EAW12DX-UC Analogue Settable Time Relay
Only skilled electricians may install this electrical equipment otherwise there is the risk of fire or electric shock!
- Temperature at mounting location: -20°C up to +50°C.
- Storage temperature: -25°C up to +70°C.
- Relative humidity: annual average value <75%.
Fleeting NO contact and fleeting NC contact, 1 CO contact potential free 10
A/250 V AC. Incandescent lamps 2000 W*. Standby loss 0.02-0.4 watt only.
Modular devices for DIN-EN 60715 TH35 rail mounting. 1 module = 18 mm wide, 58
mm deep. Different functions can be selected by a rotary switch: fleeting NO
contact (EW), fleeting NC contact (AW) or fleeting NO contact and fleeting NC
contact (EAW).
With the Eltako Duplex technology (DX) the normally potential-free contacts
can still switch in zero passage when switching 230 V AC 50 Hz and therefore
drastically reduce wear. Simply connect the neutral conductor to the terminal
(N) and L to 15 (L) for this. This gives an additional standby consumption of
only 0.1 Watt.
Universal control voltage 8 to 230 V UC. Supply voltage same as the control
voltage. Time setting between 0.1 seconds and 40 hours. By using a bistable
relay coil power loss and heating is avoided even in the on mode. The switched
consumer may not be connected to the mains before the short automatic
synchronisation after installation has terminated.
Function rotary switches
- The LED below the big rotary switch indicates the contact position while time-out is in progress. It is OFF while the relay contact 15-18 is open (15-16 closed), and is continuously ON as long as the relay contact 15-18 is closed (15-16 open).
- The time base T is selected by means of the middle, latching rotary switch T. Time-base figures available are 0.1 seconds, 0.5 seconds, 2 seconds, 5 seconds, 1 minute, 2 minutes, 5 minutes, 1 hour, 2 hours and 4 hours. The total time is obtained by multiplying the time-base by the multiplier.
- The multiplier xT is set on the upper, latching rotary switch xT and is in the range from 1 to 10. Thus, time settings can be selected in the range from 0.1 seconds (time base 0.1 seconds and multiplier 1) and 40 hours (time base 4 hours and multiplier 10).
The maximum load can be used starting at a delay time or clock cycle of 5 minutes. The maximum load will be reduced for shorter times as follows: up to 2 seconds 15%, up to 2 minutes 30%, up to 5 minutes 60%.
EW = Fleeting NO contact
When the control voltage is applied the NO contact changes to 15-18 and reverts on wiping time-out. If the control voltage is removed during the wiping time the NO contact immediately reverts to 15-16 and the residual time is cancelled.
AW = Fleeting NC contact
When the control voltage is interrupted the NO contact changes to 15-18, and reverts on wiping time-out. If the control voltage is applied during the wiping time the NO contact immediately reverts to 15-16 and the residual time is cancelled.
EAW = Fleeting NO contact and fleeting NC contact
When the control voltage is applied or interrupted the relay contact changes to 15-18 and reverts after the set wiping time.
**Typical connection
**
If N is connected, the zero passage switching is active.
Technical data
The strain relief clamps of the terminals must be closed, that means the screws must be tightened for testing the function of the device. The terminals are open ex works.
Must be kept for later use! We recommend the housing for operating instructions GBA14.
Eltako GmbH D-70736 Fellbach
Technical Support English:
+49 711 94350025
technical-support@eltako.de
eltako.com
23/2021 Subject to change without notice