Zennio ZNIO-QUADP QUAD Plus Analogue/Digital Input Module User Manual
- June 6, 2024
- Zennio
Table of Contents
Zennio ZNIO-QUADP QUAD Plus Analogue/Digital Input Module
DOCUMENT UPDATES
Version | Changes | Page(s) |
---|
[1.6]_a| Changes in the application program :
· Optimisation of the thermostat and motion detector modules.
| ****
–
[1.5]_a| Changes in the application program :
· Minor corrections.
| ****
–
** [1.3]_a| Changes in the application program** :
· Optimisation of the temperature probe module.
| ****
–
[1.2]_a| Changes in the application program :
· Optimisation of the binary inputs, thermostat and motion detector modules.
| ****
–
INTRODUCTION
QUAD PLUS
**QUAD Plus** is an updated, small-size version of the popular QUAD from Zennio. This module incorporates four digital / analogue separate inputs, each configurable as:
Binary Input.
Temperature probe , either models provided by Zennio or other NTC temperature probes from other suppliers, being in that case possible to configure their parameters in ETS.
Motion detector.
Moreover, QUAD Plus implements four independent thermostats , which can be enabled and configured separately, as well as the Heartbeat function or periodical “still-alive” notification.
INSTALLATION
QUAD is connected to the KNX bus through the incorporated terminal connector, while the input lines need to be connected to QUAD Plus through the screw terminal block bundled in the device packaging. Once powered through the KNX bus, the device may be downloaded both an individual address or the application program.
The main elements are described next:
Prog./Test Button (2): a short press on this button sets the device into the programming mode, making the associated LED (2) light in red. If this button is held at the same time of applying bus power to the device, the device will enter the Safe Mode. In such case, the LED will intermit in red.
Slots for the Input Lines (3): slots for the insertion of the optional inputs terminal block (4). Alternatively, the stripped cables of the input lines can be directly screwed into the slots. Each accessory should be connected to one of the slots labelled 1 to 4 and, on the other hand, to any of the common slots, labelled as “C”.
To obtain further information about the technical features of QUAD Plus and on security and installation procedures, please refer to the Datasheet of the device, bundled with the original packaging and also available at the Zennio website, http://www.zennio.com.
CONFIGURATION
**GENERAL**
**** After importing the corresponding database in ETS and adding the device into the topology of the desired project, the configuration process begins by entering the Parameters tab of the device.
ETS PARAMETERISATION
**** The only parameterisable screen available by default is General. From this screen it is possible to activate/deactivate all the required functionality.
Heartbeat (Periodical Alive Notification) : this parameter lets the integrator incorporate a 1-Bit object to the project (“ [Heartbeat] Object to Send ‘1’ ”) that will be sent periodically with value “1” to notify that the device is still working ( still alive ).
Note : The first sending after download or bus failure takes place with a delay of up to 255 seconds, to prevent bus overload. The following sendings match the period set
__Input x : sets the type of input number “x”: “ Binary Input ”, “ Temperature Probe ” or “ Motion Detector ”. If such input is not required, it can be left as “ Disabled ”.
Thermostat x : enables or disables thermostat number “x”.
One entry per input or thermostat will be included into the tab tree on the left.
INPUTS
** QUAD Plus incorporates four analogue/digital inputs** , each configurable as a:
Binary input , for the connection of a pushbutton or a switch/sensor.
Temperature probe , to connect a temperature sensor from Zennio or NTC probes from third parties (the latter requires configuring their parameters in ETS).
Motion detector , to connect a motion detector from Zennio.
BINARY INPUT
Please refer to the specific user manual “ Binary Inputs ”, available in the QUAD Plus product section at the Zennio website, http://www.zennio.com.
TEMPERATURE PROBE
Please refer to the specific user manual “ Temperature Probe ”, available in the QUAD Plus product section at the Zennio website, http://www.zennio.com.
MOTION DETECTOR
It is possible to connect motion detectors from Zennio to the input ports of QUAD Plus. This brings the device with the possibility of monitoring motion and presence in the room, as well as the light level. Depending on the detection, different response actions can be parameterised.
Please refer to the “ Motion Detector ” user manual, available under the QUAD Plus product section at the Zennio website (www.zennio.com), for detailed information about the functionality and the configuration of the related parameters.
Notes :
The ZN1IO-DETEC-P motion detector is compatible with a variety of Zennio devices. However, depending on the device it is actually being connected to, the functionality may differ slightly. Therefore, please refer specifically to the aforementioned user manual.
__When connected to QUAD Plus, the rear micro-switch of model ZN1IO- DETEC-P should be set to position “ Type B ”.
THERMOSTATS
** QUAD Plus allows independently enabling and configuring up to four thermostat** functions, with independence of the number of the inputs that have been configured.
Please refer to the specific “ Zennio Thermostat ” user manual available under the QUAD Plus product section at the Zennio homepage (www.zennio.com) for detailed information about the functionality and the configuration of the related parameters.
ANNEX I. COMMUNICATION OBJECTS
** “ Functional range** ” shows the values that, with independence of any other values permitted by the bus according to the object size, may be of any use or have a particular meaning because of the specifications or restrictions from both the KNX standard or the application program itself.
Number| Size| I/O| Flags| Data type (DPT)| Functional Range|
Name| Function
---|---|---|---|---|---|---|---
1| 1 Bit| | C T – – –| DPT_Trigger| 0/1| [Heartbeat] Object to Send
‘1’| Sending of ‘1’ Periodically
2| 1 Byte| I| C – – W –| DPT_SceneControl| 0-63; 128-191| [Thermostat]
Scene Input| Scene Value
3, 33, 63, 93| 2 Bytes| I| C – – W –| DPT_Value_Temp| -273.00º –
670760.00º| [Tx] Temperature Source 1| External Sensor Temperature
4, 34, 64, 94| 2 Bytes| I| C – – W –| DPT_Value_Temp| -273.00º –
670760.00º| [Tx] Temperature Source 2| External Sensor Temperature
5, 35, 65, 95| 2 Bytes| O| C T R – –| DPT_Value_Temp| -273.00º –
670760.00º| [Tx] Effective Temperature| Effective Control Temperature
6, 36, 66, 96
|
1 Byte
|
I
|
C – – W –
|
DPT_HVACMode
| 1=Comfort 2=Standby 3=Economy 4=Building Protection|
[Tx] Special Mode|
1-byte HVAC Mode
7, 37, 67, 97
| 1 Bit| I| C – – W –| DPT_Ack| 0/1| [Tx] Special Mode: Comfort| 0 =
Nothing; 1 = Trigger
1 Bit| I| C – – W –| DPT_Switch| 0/1| [Tx] Special Mode: Comfort| 0 =
Off; 1 = On
8, 38, 68, 98
| 1 Bit| I| C – – W –| DPT_Ack| 0/1| [Tx] Special Mode: Standby| 0 =
Nothing; 1 = Trigger
1 Bit| I| C – – W –| DPT_Switch| 0/1| [Tx] Special Mode: Standby| 0 =
Off; 1 = On
9, 39, 69, 99
| 1 Bit| I| C – – W –| DPT_Ack| 0/1| [Tx] Special Mode: Economy| 0 =
Nothing; 1 = Trigger
1 Bit| I| C – – W –| DPT_Switch| 0/1| [Tx] Special Mode: Economy| 0 =
Off; 1 = On
10, 40, 70, 100
| 1 Bit| I| C – – W –| DPT_Ack| 0/1| [Tx] Special Mode: Protection| 0 =
Nothing; 1 = Trigger
1 Bit| I| C – – W –| DPT_Switch| 0/1| [Tx] Special Mode: Protection| 0 =
Off; 1 = On
11, 41, 71, 101| 1 Bit| I| C – – W –| DPT_Window_Door| 0/1| [Tx] Window
Status (Input)| 0 = Closed; 1 = Open
12, 42, 72, 102| 1 Bit| I| C – – W –| DPT_Ack| 0/1| [Tx] Comfort
Prolongation| 0 = Nothing; 1 = Timed Comfort
13, 43, 73, 103
|
1 Byte
|
O
|
C T R – –
|
DPT_HVACMode
| 1=Comfort 2=Standby 3=Economy 4=Building Protection|
[Tx] Special Mode Status|
1-byte HVAC Mode
14, 44, 74, 104
| 2 Bytes| I| C – – W –| DPT_Value_Temp| -273.00º – 670760.00º| [Tx]
Setpoint| Thermostat Setpoint Input
2 Bytes| I| C – – W –| DPT_Value_Temp| -273.00º – 670760.00º| [Tx] Basic
Setpoint| Reference Setpoint
15, 45, 75, 105| 1 Bit| I| C – – W –| DPT_Step| 0/1| [Tx] Setpoint Step|
0 = -0.5ºC; 1 = +0.5ºC
16, 46, 76, 106| 2 Bytes| I| C – – W –| DPT_Value_Tempd| -670760.00º –
670760.00º| [Tx] Setpoint Offset| Float Offset Value
17, 47, 77, 107
|
2 Bytes
|
O
|
C T R – –
|
DPT_Value_Temp
|
-273.00º – 670760.00º
| [Tx] Setpoint Status|
Current Setpoint
---|---|---|---|---|---|---|---
18, 48, 78, 108| 2 Bytes| O| C T R – –| DPT_Value_Temp| -273.00º –
670760.00º| [Tx] Basic Setpoint Status| Current Basic Setpoint
19, 49, 79, 109| 2 Bytes| O| C T R – –| DPT_Value_Tempd| -670760.00º –
670760.00º| [Tx] Setpoint Offset Status| Current Setpoint Offset
20, 50, 80, 110
| 1 Bit| I| C – – W –| DPT_Reset| 0/1| [Tx] Setpoint Reset| Reset
Setpoint to Default
1 Bit| I| C – – W –| DPT_Reset| 0/1| [Tx] Offset Reset| Reset offset
21, 51, 81, 111| 1 Bit| I| C – – W –| DPT_Heat_Cool| 0/1| [Tx] Mode| 0 =
Cool; 1 = Heat
22, 52, 82, 112| 1 Bit| O| C T R – –| DPT_Heat_Cool| 0/1| [Tx] Mode
Status| 0 = Cool; 1 = Heat
23, 53, 83, 113| 1 Bit| I| C – – W –| DPT_Switch| 0/1| [Tx] On/Off| 0 =
Off; 1 = On
24, 54, 84, 114| 1 Bit| O| C T R – –| DPT_Switch| 0/1| [Tx] On/Off
Status| 0 = Off; 1 = On
25, 55, 85, 115| 1 Byte| O| C T R – –| DPT_Scaling| 0% – 100%| [Tx]
Control Variable (Cool)| PI Control (Continuous)
26, 56, 86, 116| 1 Byte| O| C T R – –| DPT_Scaling| 0% – 100%| [Tx]
Control Variable (Heat)| PI Control (Continuous)
27, 57, 87, 117| 1 Bit| O| C T R – –| DPT_Switch| 0/1| [Tx] Control
Variable (Cool)| 2-Point Control
| 1 Bit| O| C T R – –| DPT_Switch| 0/1| [Tx] Control Variable (Cool)|
PI Control (PWM)
28, 58, 88, 118| 1 Bit| O| C T R – –| DPT_Switch| 0/1| [Tx] Control
Variable (Heat)| 2-Point Control
| 1 Bit| O| C T R – –| DPT_Switch| 0/1| [Tx] Control Variable (Heat)|
PI Control (PWM)
29, 59, 89, 119| 1 Bit| O| C T R – –| DPT_Switch| 0/1| [Tx] Additional
Cool| Temp >= (Setpoint+Band) => “1”
30, 60, 90, 120| 1 Bit| O| C T R – –| DPT_Switch| 0/1| [Tx] Additional
Heat| Temp <= (Setpoint-Band) => “1”
31, 61, 91, 121| 1 Bit| O| C T R – –| DPT_Switch| 0/1| [Tx] PI State
(Cool)| 0 = PI signal 0%; 1 = PI signal greater than 0%
32, 62, 92, 122| 1 Bit| O| C T R – –| DPT_Switch| 0/1| [Tx] PI State
(Heat)| 0 = PI signal 0%; 1 = PI signal greater than 0%
123, 127, 131, 135| 2 Bytes| O| C T R – –| DPT_Value_Temp| -273.00º –
670760.00º| [Ix] Current Temperature| Temperature Sensor Value
124, 128, 132, 136| 1 Bit| O| C T R – –| DPT_Alarm| 0/1| [Ix]
Overcooling| 0 = No Alarm; 1 = Alarm
125, 129, 133, 137| 1 Bit| O| C T R – –| DPT_Alarm| 0/1| [Ix]
Overheating| 0 = No Alarm; 1 = Alarm
126, 130, 134, 138| 1 Bit| O| C T R – –| DPT_Alarm| 0/1| [Ix] Probe
Error| 0 = No Alarm; 1 = Alarm
139, 145, 151, 157| 1 Bit| I| C – – W –| DPT_Enable| 0/1| [Ix] Input
Lock| 0 = Unlock; 1 = Lock
140, 146, 152, 158
| 1 Bit| | C T – – –| DPT_Switch| 0/1| [Ix] [Short Press] 0| Sending of
0
1 Bit| | C T – – –| DPT_Switch| 0/1| [Ix] [Short Press] 1| Sending of 1
1 Bit| I| C T – W –| DPT_Switch| 0/1| [Ix] [Short Press] 0/1 Switching|
Switching 0/1
1 Bit| | C T – – –| DPT_UpDown| 0/1| [Ix] [Short Press] Move Up
Shutter| Sending of 0 (Up)
1 Bit| | C T – – –| DPT_UpDown| 0/1| [Ix] [Short Press] Move Down
Shutter| Sending of 1 (Down)
1 Bit| | C T – – –| DPT_UpDown| 0/1| [Ix] [Short Press] Move Up/Down
Shutter| Switching 0/1 (Up/Down)
1 Bit| | C T – – –| DPT_Step| 0/1| [Ix] [Short Press] Stop/Step Up
Shutter| Sending of 0 (Stop/Step Up)
1 Bit| | C T – – –| DPT_Step| 0/1| [Ix] [Short Press] Stop/Step Down
Shutter| Sending of 1 (Stop/Step Down)
| 1 Bit| | C T – – –| DPT_Step| 0/1| [Ix] [Short Press] Stop/Step
Shutter (Switched)| Switching of 0/1 (Stop/Step Up/Down)
---|---|---|---|---|---|---|---
4 Bit
| |
C T – – –
|
DPT_Control_Dimming
| 0x0 (Stop)
0x1 (Dec. by 100%) 0x2 (Dec. by 50%) 0x3 (Dec. by 25%) 0x4 (Dec. by 12%) 0x5 (Dec. by 6%) 0x6 (Dec. by 3%) 0x7 (Dec. by 1%) 0x8 (Stop)
0x9 (Inc. by 100%) 0xA (Inc. by 50%) 0xB (Inc. by 25%) 0xC (Inc. by 12%) 0xD (Inc. by 6%) 0xE (Inc. by 3%) 0xF (Inc. by 1%)
|
[Ix] [Short Press] Brighter|
Increase Brightness
4 Bit
| |
C T – – –
|
DPT_Control_Dimming
| 0x0 (Stop)
0x1 (Dec. by 100%)
…
0x8 (Stop)
0x9 (Inc. by 100%)
…
0xF (Inc. by 1%)
|
[Ix] [Short Press] Darker|
Decrease Brightness
4 Bit
| |
C T – – –
|
DPT_Control_Dimming
| 0x0 (Stop)
0x1 (Dec. by 100%)
…
0x8 (Stop)
0x9 (Inc. by 100%)
…
0xF (Inc. by 1%)
|
[Ix] [Short Press] Brighter/Darker|
Switch Bright/Dark
1 Bit| | C T – – –| DPT_Switch| 0/1| [Ix] [Short Press] Light On|
Sending of 1 (On)
1 Bit| | C T – – –| DPT_Switch| 0/1| [Ix] [Short Press] Light Off|
Sending of 0 (Off)
1 Bit| I| C T – W –| DPT_Switch| 0/1| [Ix] [Short Press] Light On/Off|
Switching 0/1
1 Byte| | C T – – –| DPT_SceneControl| 0-63; 128-191| [Ix] [Short
Press] Run Scene| Sending of 0 – 63
1 Byte| | C T – – –| DPT_SceneControl| 0-63; 128-191| [Ix] [Short
Press] Save Scene| Sending of 128 – 191
1 Bit| I/O| C T R W –| DPT_Switch| 0/1| [Ix] [Switch/Sensor] Edge|
Sending of 0 or 1
1 Byte| | C T – – –| DPT_Value_1_Ucount| 0 – 255| [Ix] [Short Press]
Constant Value (Integer)| 0 – 255
1 Byte| | C T – – –| DPT_Scaling| 0% – 100%| [Ix] [Short Press]
Constant Value (Percentage)| 0% – 100%
2 Bytes| | C T – – –| DPT_Value_2_Ucount| 0 – 65535| [Ix] [Short Press]
Constant Value| 0 – 65535
| | | | | | (Integer)|
---|---|---|---|---|---|---|---
2 Bytes| | C T – – –| 9.xxx| -671088.64 – 670760.96| [Ix] [Short Press]
Constant Value (Float)| Float Value
141, 150, 156, 162
| 1 Byte| I| C – – W –| DPT_Scaling| 0% – 100%| [Ix] [Long Press]
Dimming Status (Input)| 0% – 100%
1 Byte| I| C – – W –| DPT_Scaling| 0% – 100%| [Ix] [Long Press] Shutter
Status (Input)| 0% = Top; 100% = Bottom
142, 148, 154, 160
| 1 Bit| | C T – – –| DPT_Switch| 0/1| [Ix] [Long Press] 0| Sending of
0
1 Bit| | C T – – –| DPT_Switch| 0/1| [Ix] [Long Press] 1| Sending of 1
1 Bit| I| C T – W –| DPT_Switch| 0/1| [Ix] [Long Press] 0/1 Switching|
Switching 0/1
1 Bit| | C T – – –| DPT_UpDown| 0/1| [Ix] [Long Press] Move Up Shutter|
Sending of 0 (Up)
1 Bit| | C T – – –| DPT_UpDown| 0/1| [Ix] [Long Press] Move Down
Shutter| Sending of 1 (Down)
1 Bit| | C T – – –| DPT_UpDown| 0/1| [Ix] [Long Press] Move Up/Down
Shutter| Switching 0/1 (Up/Down)
1 Bit| | C T – – –| DPT_Step| 0/1| [Ix] [Long Press] Stop/Step Up
Shutter| Sending of 0 (Stop/Step Up)
1 Bit| | C T – – –| DPT_Step| 0/1| [Ix] [Long Press] Stop/Step Down
Shutter| Sending of 1 (Stop/Step Down)
1 Bit| | C T – – –| DPT_Step| 0/1| [Ix] [Long Press] Stop/Step Shutter
(Switched)| Switching of 0/1 (Stop/Step Up/Down)
4 Bit
| |
C T – – –
|
DPT_Control_Dimming
| 0x0 (Stop)
0x1 (Dec. by 100%)
…
0x8 (Stop)
0x9 (Inc. by 100%)
…
0xF (Inc. by 1%)
|
[Ix] [Long Press] Brighter|
Long Pr. -> Brighter; Release -> Stop
4 Bit
| |
C T – – –
|
DPT_Control_Dimming
| 0x0 (Stop)
0x1 (Dec. by 100%)
…
0x8 (Stop)
0x9 (Inc. by 100%)
…
0xF (Inc. by 1%)
|
[Ix] [Long Press] Darker|
Long Pr. -> Darker; Release -> Stop
4 Bit
| |
C T – – –
|
DPT_Control_Dimming
| 0x0 (Stop)
0x1 (Dec. by 100%)
…
0x8 (Stop)
0x9 (Inc. by 100%)
…
0xF (Inc. by 1%)
|
[Ix] [Long Press] Brighter/Darker|
Long Pr. -> Brighter/Darker; Release -> Stop
1 Bit| | C T – – –| DPT_Switch| 0/1| [Ix] [Long Press] Light On|
Sending of 1 (On)
1 Bit| | C T – – –| DPT_Switch| 0/1| [Ix] [Long Press] Light Off|
Sending of 0 (Off)
| 1 Bit| I| C T – W –| DPT_Switch| 0/1| [Ix] [Long Press] Light On/Off|
Switching 0/1
---|---|---|---|---|---|---|---
1 Byte| | C T – – –| DPT_SceneControl| 0-63; 128-191| [Ix] [Long Press]
Run Scene| Sending of 0 – 63
1 Byte| | C T – – –| DPT_SceneControl| 0-63; 128-191| [Ix] [Long Press]
Save Scene| Sending of 128 – 191
1 Bit| O| C T R – –| DPT_Alarm| 0/1| [Ix] [Switch/Sensor] Alarm:
Breakdown or Sabotage| 1 = Alarm; 0 = No Alarm
2 Bytes| | C T – – –| 9.xxx| -671088.64 – 670760.96| [Ix] [Long Press]
Constant Value (Float)| Float Value
2 Bytes| | C T – – –| DPT_Value_2_Ucount| 0 – 65535| [Ix] [Long Press]
Constant Value (Integer)| 0 – 65535
1 Byte| | C T – – –| DPT_Scaling| 0% – 100%| [Ix] [Long Press] Constant
Value (Percentage)| 0% – 100%
1 Byte| | C T – – –| DPT_Value_1_Ucount| 0 – 255| [Ix] [Long Press]
Constant Value (Integer)| 0 – 255
143, 149, 155, 161| 1 Bit| | C T – – –| DPT_Trigger| 0/1| [Ix] [Long
Press/Release] Stop Shutter| Release -> Stop Shutter
144, 147, 153, 159
| 1 Byte| I| C – – W –| DPT_Scaling| 0% – 100%| [Ix] [Short Press]
Shutter Status (Input)| 0% = Top; 100% = Bottom
1 Byte| I| C – – W –| DPT_Scaling| 0% – 100%| [Ix] [Short Press] Dimming
Status (Input)| 0% – 100%
163| 1 Byte| I| C – – W –| DPT_SceneNumber| | [Motion Detector] Scene
Input| Scene Value
164| 1 Byte| | C T – – –| DPT_SceneControl| 0-63; 128-191| [Motion
Detector] Scene Output| Scene Value
165, 194, 223, 252| 1 Byte| O| C T R – –| DPT_Scaling| 0% – 100%| [Ix]
Luminosity| 0-100%
166, 195, 224, 253| 1 Bit| O| C T R – –| DPT_Alarm| 0/1| [Ix] Open
Circuit Error| 0 = No Error; 1 = Open Circuit Error
167, 196, 225, 254| 1 Bit| O| C T R – –| DPT_Alarm| 0/1| [Ix] Short
Circuit Error| 0 = No Error; 1 = Short Circuit Error
168, 197, 226, 255| 1 Byte| O| C T R – –| DPT_Scaling| 0% – 100%| [Ix]
Presence State (Scaling)| 0-100%
169, 198, 227, 256
|
1 Byte
|
O
|
C T R – –
|
DPT_HVACMode
| 1=Comfort 2=Standby 3=Economy 4=Building Protection|
[Ix] Presence State (HVAC)|
Auto, Comfort, Standby, Economy, Building Protection
170, 199, 228, 257| 1 Bit| O| C T R – –| DPT_Occupancy| 0/1| [Ix]
Presence State (Binary)| Binary Value
| 1 Bit| O| C T R – –| DPT_Ack| 0/1| [Ix] Presence: Slave Output| 1 =
Motion Detected
171, 200, 229, 258| 1 Bit| I| C – – W –| DPT_Window_Door| 0/1| [Ix]
Presence Trigger| Binary Value to Trigger the Presence Detection
172, 201, 230, 259| 1 Bit| I| C – – W –| DPT_Ack| 0/1| [Ix] Presence:
Slave Input| 0 = Nothing; 1 = Detection from slave device
173, 202, 231, 260| 2 Bytes| I| C – – W –| DPT_TimePeriodSec| | [Ix]
Presence: Waiting Time| 0-65535 s.
174, 203, 232, 261| 2 Bytes| I| C – – W –| DPT_TimePeriodSec| | [Ix]
Presence: Listening Time| 1-65535 s.
175, 204, 233, 262| 1 Bit| I| C – – W –| DPT_Enable| 0/1| [Ix] Presence:
Enable| According to parameters
176, 205, 234, 263| 1 Bit| I| C – – W –| | | [Ix] Presence: Day/Night|
According to parameters
177, 206, 235, 264| 1 Bit| O| C T R – –| DPT_Occupancy| 0/1| [Ix]
Presence: Occupancy State| 0 = Not Occupied; 1 = Occupied
178, 207, 236, 265| 1 Bit| I| C – – W –| DPT_Ack| 0/1| [Ix] External
Motion Detection| 0 = Nothing; 1 = Motion detected by an
| | | | | | | external sensor
---|---|---|---|---|---|---|---
179, 184, 189, 208,
213, 218, 237, 242,
247, 266, 271, 276
|
1 Byte
|
O
|
C T R – –
|
DPT_Scaling
|
0% – 100%
| [Ix] [Cx] Detection State (Scaling)|
0-100%
180, 185, 190, 209,
214, 219, 238, 243,
248, 267, 272, 277
|
1 Byte
|
O
|
C T R – –
|
DPT_HVACMode
| 1=Comfort 2=Standby 3=Economy 4=Building Protection|
[Ix] [Cx] Detection State (HVAC)|
Auto, Comfort, Standby, Economy, Building Protection
181, 186, 191, 210,
215, 220, 239, 244,
249, 268, 273, 278
|
1 Bit
|
O
|
C T R – –
|
DPT_Switch
|
0/1
| [Ix] [Cx] Detection State (Binary)|
Binary Value
182, 187, 192, 211,
216, 221, 240, 245,
250, 269, 274, 279
|
1 Bit
|
I
|
C – – W –
|
DPT_Enable
|
0/1
| [Ix] [Cx] Enable Channel|
According to parameters
183, 188, 193, 212,
217, 222, 241, 246,
251, 270, 275, 280
|
1 Bit
|
I
|
C – – W –
|
DPT_Switch
|
0/1
| [Ix] [Cx] Force State|
0 = No Detection; 1 = Detection
Join a nd send us you r inquiries
about Zennio devices:
Zennio Avance y Tecnología S.L. C/ Río Jarama, 132. Nave P-8.11 45007 Toledo (Spain).
Tel . +34 925 232 002
www.zennio.com info@ zennio .com
Documents / Resources
|
Zennio ZNIO-QUADP QUAD Plus Analogue/Digital Input
Module
[pdf] User Manual
ZNIO-QUADP, QUAD Plus Analogue Input Module, QUAD Plus Digital Input Module
---|---
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>