MW LCM-40 Switching Power Supply Installation Guide

June 5, 2024
MW

MW LCM-40 Switching Power Supply

MW LCM-40 Switching Power Supply

Features

  • 180~295VAC input only
  • Built-in active PFC
  • Output current level selectable by DIP switch
  • Built-in DALI interface and push dimming function (DA version)
  • Built-in 0~10Vdc and PWM signal dimming function (Non-DA version)
  • Power supply synchronization function up to 10 units
  • Temperature compensation function by external NTC
  • Class po wer unit, ungrounded
  • Built-in 12V/50mA auxiliary output
  • Full plastic case enclosed
  • No-load power consumption <1W (1.2W for DA version)
  • Protection s: Short circuit / Over voltage / Over temperature
  • 3-year warranty
  • Suitable for intelligent LED lighting

Wiring

  • Housing with cable clamp for remote installation
  • Use wires with an adequate cross-section (see 5)
  • Use suitable mounting tools to do the wiring and mounting (see 5)
  • MCB circuit breaker) with an adequate current rating to protect Use a (miniature the lighting system (see 6)

Environmental limitations

  • Maximum ambient temperature must not exceed 60
  • Always allow adequate ventilation clearances, 50mm, around the unit in use to prevent it from overheating
  • Only install the unit in interior environments

Cautions

  • This unit must be installed by a qualified electrician
  • This unit is not suitable for applications where DC/DC converters are connected before LED lamps

Settings and connections

  1. Output Current Level Settings
    The LCM can provide various output currents by setting the DIP switch. The settings of the DIP switch are shown in the tables below.
    LCM-40(DA)

Voltage ran ge| Selectable Current| 1| 2| 3| 4| 5| 6
---|---|---|---|---|---|---|---
2-1 00V| 35 0mA| – —| —| – —| —| – —| —
2-8 0V| 50 0mA| ON| —| – —| —| – —| —
2-6 7V| 60 0mA| ON| ON| – —| —| – —| —
2-5 7V| **70 0mA*| ON| ON| ON| —| – —| ON
2-4 5V| 90 0mA| ON| ON| ON| ON| – —| ON
2-4 0V| 1050mA**| ON| ON| ON| ON| ON| ON

LCM-60(DA)

Voltage range| Selectable Current| 1| 2| 3| 4| 5| 6
---|---|---|---|---|---|---|---
2-90V| 50 0mA| —| —| – —| —| – —| —
2-90V| 60 0mA| ON| —| – —| —| – —| —
2-86V| **700mA*| ON| ON| – —| —| – —| —
2-67V| 90 0mA| ON| ON| ON| —| – —| ON
2-57V| 10 50mA| ON| ON| ON| ON| – —| ON
2-42V| 14 00mA**| ON| ON| ON| ON| ON| ON

Note: The factory default setting is 700mA.
Output voltage and output wattage must not exceed the rated values.
Terminal blocks assignment for LCMMW LCM-40 Switching Power Supply FIG
1

  1. Connection of LED Lamps
    Press down the “push button” by a slotted screwdriver to insert or remove the cable.MW LCM-40 Switching Power Supply FIG 2

  2. Connection of Dimming FunctionsMW LCM-40 Switching Power Supply FIG 3
    Note: ONLY use the open push button with ut indicator light.
    Warning: Risk of short circuit. The push-button can only be linked between the PUSH and the AC/L (brown or black).
    DO NOT connect the push button to the AC/N (blue or white).
    Dimming control mechanism


Function Pushing time
Turn-ON/OFF 0.1 ~ 1 sec
Dim UP/DOWN 1.5 ~ 10 sec
Reset > 11 sec
None < 0.05 sec
  * It will always dim up when light intensity is lower than 10%, whereas it will
  * Factory dimming setting: 100% always dim down when light intensity  

Synchronization operation
The lights LCM units (slaves) can be dimmed synchronously through an LCM unit (the master) driven by directly controlled via 0-10Vdc, 10V PWM, DALI or push dim dimming function. The wiring is shown as below.MW LCM-40 Switching Power
Supply FIG 4

  * Mating housing for SYN. connectors : JST B2B-XH or equivalent
  * Maximum number of the LCM units: 10 (1 master + 9 slaves)
  * Maximum cable length between each unit: 20m (based on a cable with a cross-section of 0.15mm2~0.3mm2 or AWG No. of 22 ~ 26)
  * Note 1: DO NOT connect dimming circuitry to slaves.
  * Note 2: Please make sure all units are set to 100% dimming setting (factory default) before synchronizing.
  1. NTC Connection
  2. Recommended Screwdriver, Wire and Torque Setting

Type| The cover (the blue one)| Scr ew ter minal

(FAN ± , NT C ± , DIM ± )

| Push ter minal

(ACL/N, PUSH, DA ± , Vo ± )

---|---|---|---
Solid wire| —–| ψ0.404 -ψ0.643 mm| ψ1. 024 -ψ1.628mm
Stranded wire| —–| 0.12 9 – 0.3 26mm 2| 0.823 – 2.08 mm2
Ameri can wire gauge| —–| 22 – 26AWG| 14 – 1 8AWG
Wire stripping length| —–| 7mm (0.27 “)| 10mm (0.39 “)
Screwdriver| 6mm Phillips| 3mm Philli ps| 3mm Phillips
Recommended tightening torque| 4.6 kgf-cm ( 4 lb-in)| 2.88 kgf-cm (2.5 lb-in)| —–
Suggested push-down strength| —–| —–| 3 – 4 KP (6.61-8.81 lb)
6. Suggested Maximum Number of the LCM Units that can be Connected to an MCB (miniature circuit breaker) at 230Vac**
Model| B10| B16| C10| C16**
---|---|---|---|---
LCM-40(DA)| 10| 16| 17| 28
LCM-60(DA)| 9| 15| 16| 26

Note: These calculated values are based on the MCB S201 series manufactured by A BB.

Read User Manual Online (PDF format)