MW LCM-40 Switching Power Supply Installation Guide
- June 5, 2024
- MW
Table of Contents
MW LCM-40 Switching Power Supply
Features
- 180~295VAC input only
- Built-in active PFC
- Output current level selectable by DIP switch
- Built-in DALI interface and push dimming function (DA version)
- Built-in 0~10Vdc and PWM signal dimming function (Non-DA version)
- Power supply synchronization function up to 10 units
- Temperature compensation function by external NTC
- Class po wer unit, ungrounded
- Built-in 12V/50mA auxiliary output
- Full plastic case enclosed
- No-load power consumption <1W (1.2W for DA version)
- Protection s: Short circuit / Over voltage / Over temperature
- 3-year warranty
- Suitable for intelligent LED lighting
Wiring
- Housing with cable clamp for remote installation
- Use wires with an adequate cross-section (see 5)
- Use suitable mounting tools to do the wiring and mounting (see 5)
- MCB circuit breaker) with an adequate current rating to protect Use a (miniature the lighting system (see 6)
Environmental limitations
- Maximum ambient temperature must not exceed 60
- Always allow adequate ventilation clearances, 50mm, around the unit in use to prevent it from overheating
- Only install the unit in interior environments
Cautions
- This unit must be installed by a qualified electrician
- This unit is not suitable for applications where DC/DC converters are connected before LED lamps
Settings and connections
- Output Current Level Settings
The LCM can provide various output currents by setting the DIP switch. The settings of the DIP switch are shown in the tables below.
LCM-40(DA)
Voltage ran ge| Selectable Current| 1| 2| 3| 4|
5| 6
---|---|---|---|---|---|---|---
2-1 00V| 35 0mA| – —| —| – —| —| – —| —
2-8 0V| 50 0mA| ON| —| – —| —| – —| —
2-6 7V| 60 0mA| ON| ON| – —| —| – —| —
2-5 7V| **70 0mA*| ON| ON| ON| —| – —| ON
2-4 5V| 90 0mA| ON| ON| ON| ON| – —| ON
2-4 0V| 1050mA**| ON| ON| ON| ON| ON| ON
LCM-60(DA)
Voltage range| Selectable Current| 1| 2| 3| 4|
5| 6
---|---|---|---|---|---|---|---
2-90V| 50 0mA| —| —| – —| —| – —| —
2-90V| 60 0mA| ON| —| – —| —| – —| —
2-86V| **700mA*| ON| ON| – —| —| – —| —
2-67V| 90 0mA| ON| ON| ON| —| – —| ON
2-57V| 10 50mA| ON| ON| ON| ON| – —| ON
2-42V| 14 00mA**| ON| ON| ON| ON| ON| ON
Note: The factory default setting is 700mA.
Output voltage and output wattage must not exceed the rated values.
Terminal blocks assignment for LCM
-
Connection of LED Lamps
Press down the “push button” by a slotted screwdriver to insert or remove the cable. -
Connection of Dimming Functions
Note: ONLY use the open push button with ut indicator light.
Warning: Risk of short circuit. The push-button can only be linked between the PUSH and the AC/L (brown or black).
DO NOT connect the push button to the AC/N (blue or white).
Dimming control mechanism
Function | Pushing time |
---|---|
Turn-ON/OFF | 0.1 ~ 1 sec |
Dim UP/DOWN | 1.5 ~ 10 sec |
Reset | > 11 sec |
None | < 0.05 sec |
* It will always dim up when light intensity is lower than 10%, whereas it will
* Factory dimming setting: 100% always dim down when light intensity
Synchronization operation
The lights LCM units (slaves) can be dimmed synchronously through an LCM unit
(the master) driven by directly controlled via 0-10Vdc, 10V PWM, DALI or push
dim dimming function. The wiring is shown as below.
* Mating housing for SYN. connectors : JST B2B-XH or equivalent
* Maximum number of the LCM units: 10 (1 master + 9 slaves)
* Maximum cable length between each unit: 20m (based on a cable with a cross-section of 0.15mm2~0.3mm2 or AWG No. of 22 ~ 26)
* Note 1: DO NOT connect dimming circuitry to slaves.
* Note 2: Please make sure all units are set to 100% dimming setting (factory default) before synchronizing.
- NTC Connection
- Recommended Screwdriver, Wire and Torque Setting
Type| The cover (the blue one)| Scr ew ter minal
(FAN ± , NT C ± , DIM ± )
| Push ter minal
(ACL/N, PUSH, DA ± , Vo ± )
---|---|---|---
Solid wire| —–| ψ0.404 -ψ0.643 mm| ψ1. 024 -ψ1.628mm
Stranded wire| —–| 0.12 9 – 0.3 26mm 2| 0.823 – 2.08 mm2
Ameri can wire gauge| —–| 22 – 26AWG| 14 – 1 8AWG
Wire stripping length| —–| 7mm (0.27 “)| 10mm (0.39 “)
Screwdriver| 6mm Phillips| 3mm Philli ps| 3mm Phillips
Recommended tightening torque| 4.6 kgf-cm ( 4 lb-in)| 2.88 kgf-cm (2.5
lb-in)| —–
Suggested push-down strength| —–| —–| 3 – 4 KP (6.61-8.81 lb)
6. Suggested Maximum Number of the LCM Units that can be Connected to an MCB (miniature circuit breaker) at 230Vac**
Model| B10| B16| C10| C16**
---|---|---|---|---
LCM-40(DA)| 10| 16| 17| 28
LCM-60(DA)| 9| 15| 16| 26
Note: These calculated values are based on the MCB S201 series manufactured by A BB.