MW 15W Ultra Slim Step Shape DIN Rail Instructions
- June 7, 2024
- MW
Table of Contents
15W
Ultra Slim Step Shape
DIN-Rail
HDR-15 series
Features
- Ultra slim design with 17.5mm (1SU) width
- Universal input 85~264VAC (277VAC operational)
- No load power consumption<0.3W
- Isolation class II
- Pass LPS (Limited power source)
- DC output voltage adjustable
- Protections: Short circuit/Overload/Over voltage
- Cooling by free air convection (working temperature: -30~+70°C)
- DIN rail TS-35/7.5 or 15 mountable
- Overvoltage category III
- LED indicator for power on
- 3 years warranty
Applications
- Household control system
- Building automation
- Industrial control system
- Factory automation
- Electro-mechanical apparatus
Description
HDR-15 is one economical ultra-slim 15W DIN rail power supply series, adapt to
be installed on TS-35/7.5 or TS-35/15 mounting rails. The body is designed
17.5mm(1SU) in width, which allows space-saving inside the cabinets. The
entire series adopts the full range AC input from 85VAC to 264VAC (277VAC
operational) and conforms to EN61000-3-2, the norm the European Union
regulates for harmonic current.
HDR-15 is designed with plastic housing that can effectively prevent a user
from electric hazards. With a working efficiency of up to 87%, the entire
series can operate at the ambient temperature between -30°C and air
convection. The complete protection functions and relevant certificates for
home automation and industrial 70°C under control apparatus (IEC60950-1,
UL508, UL60950-1, EN61558-2-16) make HDR-65 a very competitive power supply
solution for household and industrial applications.
Model Encoding
SPECIFICATION
MODEL | HDR-15-5 | HDR-15-12 | HDR.45-15 | HDR-15-24 | HDR-15-411 |
---|---|---|---|---|---|
OUTPUT | DC VOLTAGE | 5V | 12V | 15V | 24V |
RATED CURRENT | 2.4A | 125A | 1A | 0.63A | 0.32A |
CURRENT RANGE | 0-2.4A | 0 – 1.25A | 0-IA | 0 – 0.63A | 0 -0.32A |
RATED POWER | 12W | 15W | 15W | 15.2W | 15.4W |
RIPPLE 8 NOISE (max.) Natal | 80mVp-p | 120mVp-p | 120mVp-p | 150mVp-p | 240mVp-p |
VOLTAGE ADJ. RANGE | 4.5 – 5.5V | 10.8 – 13.8V | 135 – 18V | 21.6 – 29V | 43.2 – |
55.2V
VOLTAGE TOLERANCE Note.3| ±2.0%| ±1.0%| ±1.0%| ±1.0%| ±1.0%
LINE REGULATION| ±1.0%| ±1.0%| ±1.0%| ±1.0%| ±1.0%
LOAD REGULATION| ±1.0%| ±1.0%| ±1.0%| ±1.0%| ±1.0%
SETUP, RISE TIME| 2000ms. 80ms(230VAC, 2000ms. 80ms/115VAC at fel load
HOLD UP TIME (Typ.)| 30ms230VAC, 12ms/115VAC at ful load
INPUT| VOLTAGE RANGE| 85 – 264VAC (277VAC opesaticnal ) , 120- 370VDC (390NDC
operational )
FREQUENCY RANGE| 47 -63Hz
EFFICIENCY (Typ.)| BO% , 185% ,185.5%, 186%, 187%
AC CURRENT (Typ.)| 0.5A/115VAC, 0.25A230VAC
INRUSH CURRENT (Typ.)| COLD START 25A/115VAC , 45N230VAC
PROTECTION| OVERLOAD| 110 – 145% rated output power
Hiccup mode Wien output voltage <50%. recovers automatically after fault
condition is removed
Constant current Laing within 50% -100% rated output voltage, recovers automatically after faun ooncteon is removed
OVER VOLTAGE| 5.75 – 6.75V| 14.2- 16.2V 1 18.8 – 22.5V|
30′- 36V| 56 5 – 64.6V
Protection type : Shut off o/p voltage, Swale by zener diode
EIPPROMIERT| WORKING TEMP.| -30 – +70t (Refer Tel:/eating Curve)
WORKING HUMIDITY| 20 – 90% RH non-condensing
STORAGE TEMP., HUMIDITY| -40-485’C, 10- 95% RH non-condensitg
TEMP. COEFFICIENT| -±0.03%R.: (0 – 50.C) RH non-condensing
VIBRATION| 10- 500Hz. 2G 10min./Icycle. period fa 60min. each along X. Y. Z
axes: Mounting: Compliance to IEC60068-2-6
OPERATING ALTITUDE| 2000 meters
OVER VOLTAGE CATEGORY| ill : According to EN61558, EN50178,EN60664-1,
EN62477-1 : altitude up to 2000 meters
SAFETY &
EMC (Nets 4)
| SAFETY STANDARDS| UL60950-1, UL508, TUV EN61558-2-16.IEC60950-1, EAC TP TC
004, BSMI CNS14336-1 approved: Design refer to TUV EN60950-1
WITHSTAND VOLTAGE| 1/P-01P:4KVAC
ISOLATION RESISTANCE| UP-OIP:100M Ohms! 500VDC / 25C/ 70% RH
EMC EMISSION| Parameter| Standard| Test Level / Note
Conducted| EN55032(CISPR32), CNS13438| Class B
Radiated| EN55032(CISPR32). CN$13438| Class 8
Harmonic Current| EN61000-3-2| Class A
Voltage Facies| EN61000-3-3|
EMC IMMUNITY| EN55024, EN55035. EN61000-6-2. EN61204-3
Parameter| Standard| Test Level /Note
ESD| EN61000-4-2| Level 3. BKV air: Level 2, 4XV contact. °mem A
Radiated Susceptibility| EN61000-4-3| Leve13. aiteria A
EFT/Burest| EN61000-4-4| Leve13. crrteria A
Surge| EN61000-4-5| Leve14,2KV/L-N, aiteria A
Conducted| EN61000-4-6| Level 3. criteria A
Magnetic Field| EN61000-4-8| Level 4. aiteda A
Voltage Dips and interruptions| EN810004-11| >95% dip 0.5 periods. 30% dip 25
periods. >95% interruptions 250 periods
OTHERS| MTBF| 1166K hrs mil. MIL-HDBK-217F (25t)
DIMENSION| 17.5’90’54.5mm (WI-I’D)
PACKING| 78g:160pcs/13.5149/1.19CUFT
NOTE
- All parameters NOT specially mentioned are measured at 230VAC input, rated load, and 25°C of ambient temperature.
- Ripple & noise are measured at 20MHz of bandwidth by using a 12″ twisted pair-wire terminated with a 0.1μf & 47μf parallel capacitor.
- Tolerance: includes set up tolerance, line regulation, and load regulation.
- The power supply is considered as an independent unit, but the final equipment still needs to re-confirm that the whole system complies with the EMC directives. For guidance on how to perform these EMC tests, please refer to EMI testing of component power supplies. (as available on http://www.meanwell.com)
- The ambient temperature derating of 3.5/1000m with fanless models and of 5/1000m with fan models for operating altitude higher than 2000m(6500ft).
Block Diagram
Derating Curve
Output Derating VS Input Voltage
Mechanical Specification
( Unit: mm , tolerance ± 0.5mm)
Installation Manual
Please refer to : http://www.meanwell.com/manual.html
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>