IP 65
48.23 ·Technical amendments reserved 33 018
Recessed luminaire
Instructions for use
Application
Shielded luminaire for walls and stairs.
The colour temperature of the luminaire can be set optionally to 3000 K and
4000 K.
Product description
Luminaire made of aluminium alloy, aluminium and stainless steel BEGA Tricoat
® coating technology Colour graphite or silver Safety glass, white Silicone
gasket Fixing is achieved by using two adjustable wedge-shaped claws Required
recessed opening 245 x 60 mm Recessed depth 70 mm 2 cable entries for through-
wiring of mains supply cable ø 7-10.5 mm Connection terminal 2.5@ Earth
conductor connection BEGA Ultimate Driver ® Complies with flicker requirements
in accordance with IEEE 1789, DIN IEC/TR 63158, DIN IEC/TR 61547-1 LED power
supply unit 220-240 V x 0/50-60 Hz DC 176-280 V BEGA Thermal Control ®
Temporary thermal regulation to protect temperature-sensitive components
without switching off the luminaire
Safety class I
Protection class IP 65
Dust-tight and protection against water jets
Impact strength IK09
Protection against mechanical impacts < 10 joule
– Safety mark
c – Conformity mark
Weight: 0.8 kg
This product contains light sources of energy efficiency class(es) B
Safety
The installation and operation of this luminaire are subject to national
safety regulations.
Installation and commissioning may only be carried out by a qualified
electrician.
The manufacturer accepts no liability for damage caused by improper use or
installation.
If subsequent modifications are made to the luminaire, the person responsible
for these modifications shall be considered the manufacturer.
Overvoltage protection
The electronic components installed in the luminaire are protected against
overvoltage in accordance with DIN EN 61547.
To achieve an additional protection against e. g. transients, etc. we
recommend separate overvoltage protection components.
You can find them on our website at www.bega.com.
The ideal protection of all electronic components installed in the luminaires
is achieved by using bounce-free switching contacts such as an electronic
relay (solid-state relay), e.g. BEGA 71 320.
Please note:
This luminaire is coated with BEGA Tricoatb.
BEGA Tricoatb is a registered trademark for a technology that we use to
achieve optimal corrosion resistance.
Even the best possible surface protection and the highest corrosion resistance
can be rendered almost ineffective in some cases by aggressive media caused by
leaching of building materials.
Where such media are suspected, a material analysis must be carried out before
installation. Always avoid excessive use of chemical cleaning agents in the
vicinity of the luminaire.
Installation
The recessed opening will be covered by the frame of the luminaire housing.
Fixing of the luminaire is achieved by using two adjustable wedge-shaped
claws.
Installation in solid, plastered walls:
The installation housing 10 425 is available for this purpose. If this is not
used, an exact recessed opening of 245 x 60 mm with a minimum depth of 70 mm
is required.
Installation in exposed brickwork:
The construction of an on-site recessed opening with the exact installation
dimensions of 245 x 60 mm with a minimum depth of 70 mm is required. An
installation housing cannot be used.
Installation in drywalling:
A recessed opening of 245 x 60 mm with a minimum depth of 70 mm is required.
The claws grip behind drywall.
Installation into insulated façades:
For installation in EWIS external wall insulation systems please use
installation housing 13 520 in combination with a plaster frame 10 025 or 13
504.
Open luminaire:
Undo hexagon socket screws (SW 3) and remove housing cover.
Disconnect plug-connection of the LED connecting cable.
Disconnect the earth conductor connection from the plug connection.
Lead the mains supply cable through the cable entry into the luminaire
housing.
Make earth conductor connection.
Push silicone sleeves over the lines and make electrical connection.
In order to guarantee the maximum service
life of the electrical components, the enclosed desiccant pouch must be placed
in the luminaire.
Remove the desiccant pouch from the foil packaging and place it in the
position marked by the red information label immediately before finally
closing the luminaire.
The LED module can optionally be operated with a colour temperature of 3000 K
or 4000 K.
Check the labelling to ensure a correct socket match when connecting the plug-
in device to the LED connecting cable.
Switching may only be carried out when disconnected from the power supply!
Put on earth conductor connection of the housing cover. Assemble housing
cover.
Make sure that gasket is positioned correctly.
Tighten the screws evenly.
Insert luminaire housing into the recessed opening. Hand-tighten screws of the
claw fastener (torx drive T10) evenly. Do not use an electric screwdriver!
Lamp
Module connected wattage | 2.8 W |
---|---|
Luminaire connected wattage | 3.8 W |
Module designation | LED-1533/83040 |
Colour rendering index | CRI > 80 |
Rated temperature | t a = 25 °C |
Ambient temperature | t a max= 60 °C |
When installed in heat-insulating material | t a max = 55 °C |
Operation at colour temperature | 3000 K |
Module luminous flux | 580 lm |
Luminaire luminous flux | 47 lm |
Luminaire luminous efficiency | 12,4 lm / W |
Operation at colour temperature | 4000 K |
Module luminous flux | 595 lm |
Luminaire luminous flux | 48 lm |
Luminaire luminous efficiency | 12,6 lm / W |
Cleaning · Maintenance
Clean luminaire regularly with solvent-free cleansers from dirt and deposits.
Do not use high pressure cleaners.
Replacing the LED module
The designation of the LED module is noted on a label in the luminaire.
The light colour and light output of BEGA replacement modules correspond to
those of the modules originally fitted.
The module can be replaced by qualified persons using standard tools.
Disconnect the system and open the luminaire.
Please follow the installation instructions for the LED module.
Inspect and, if necessary, replace the luminaire gaskets.
Defective glass must be replaced.
Close the luminaire.
Accessories
10 425 Installation housing
13 520 Installation housing for installation in insulated façades (EWIS)
10 025 Plaster frame
13 504 Plaster frame flush
A separate instructions for use can be provided upon request.
Spares
LED power supply unit | DEV-0450/350 |
---|---|
LED module | LED-1533/83040 |
Gasket | 83 001 526 |
BEGA Gantenbrink-Leuchten KG · Postfach 31 60 · 58689 Menden
info@bega.com
www.bega.com
Documents / Resources
| BEGA
33018 Shielded
Luminaire
[pdf] Instruction Manual
33018, 71320, 33018 Shielded Luminaire, Shielded Luminaire, Luminaire
---|---
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>