Bardac drives dw250 Smarty Universal Automation Controller Instruction Manual
- June 12, 2024
- Bardac drives
Table of Contents
- Design Statements
- Product Identification – smarty7
- Product Identification – Part Numbers
- smarty7 Installation
- Front Panel
- Dimensions, Overview, and Terminal Map
- Frequency Input Notes (FI Terminals)
- Programming
- Get started with savvy
- Upgrade savvy and smarty
- Operator Station
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
Universal Automation Controller
models
dw250, dw254,
dw258, & dw259
Installation & Operation Manual
Design Statements
This process control equipment to be supplied by Class2, LPS, limited power supply.
EMC Standard, EN 61326-1: 2006, Electrical Equipment for Measurement, Control and Laboratory Use.
Emissions Class A, Commercial Equipment.
Immunity Table 2, Industrial Equipment.
LVD Standards, EN 61010-1: 2010, Safety Requirements for Electrical Equipment for Measurement, Control and Laboratory Use and;
EN 61010-2-030: Particular Requirements for Testing and Measuring Circuits.
smarty is an industrial controller designed for permanent installation by qualified professionals.
If it is used in a manner not specified herein the protection provided may be impaired.
smarty and its packaging contain recyclable materials
This device is designed to comply with Part 15 of the FCC Rules. Operation is subject to the following two conditions: (1)This device may not cause harmful interference, and (2)this device must accept any interference received, including interference that may cause undesired operation.
This Class [A] digital apparatus is designed to comply with Canadian ICES-003.
Warning! It is essential that you read and understand this entire manual and the entire contents of the savvy software Help menu before proceeding with your installation and configuration. See page 6 for savvy installation instructions. For more information and to download manuals and software, go to www.driveweb.com or contact us. See page 12.
Warning! Your use of savvy software and drive.web devices may cause
motors and machinery to power up with high Voltages or start or operate in an
unexpected, dangerous or lethal way. It is essential that you are completely
familiar with all of the equipment and the system design before attempting
to program or edit a program or connect to any live device. It is also
essential that a risk assessment is conducted to identify hazards.
Risks must be reduced to tolerable levels.
Warning! You are entirely responsible for the configuration or use of any drive.web product. By configuring or using these products you agree to indemnify and hold harmless Bardac Corporation, its employees, directors, officers, distributors, and resellers against the consequences of your configuration or use of the products.
Warning! Information in this manual is subject to change without notice. You are responsible for verifying the proper operation of your smarty. Special care must be taken after loading new firmware or installing new options.
SMARTY, SAVVY, SAVVYPANEL, SPEEDY, BARDAC, and DRIVE.WEB are trade marks of Bardac smarty HG504266Iss1.2
Corporation, registered in the U.S. and other countries.
Warning! Avoid permanent damage to your smarty, never exceed any min or
max values. Do not connect any smarty terminal to mains circuits. See page 5
for IO ratings.
lwIP is incorporated into smarty firmware. lwIP Copyright (c) 2001-2004 Swedish
Institute of Computer Science. All rights reserved.
Redistribution and use in source and binary forms, with or without
modification, are permitted provided that the following conditions are met:
- Redistributions of source code must retain the above copyright notice, this list of conditions and the following disclaimer.
- Redistributions in binary form must reproduce the above copyright notice, this list of conditions and the following disclaimer in the documentation and/or other materials provided with the distribution.
- The name of the author may not be used to endorse or promote products derived from this software without specific prior written permission.
THIS SOFTWARE IS PROVIDED BY THE AUTHOR “AS IS” AND ANY EXPRESS OR IMPLIED WARRANTIES, INCLUDING, BUT NOT LIMITED TO, THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE ARE DISCLAIMED. IN NO EVENT SHALL THE AUTHOR BE LIABLE FOR ANY DIRECT, INDIRECT, INCIDENTAL, SPECIAL, EXEMPLARY, OR CONSEQUENTIAL DAMAGES (INCLUDING, BUT NOT LIMITED TO, PROCUREMENT OF SUBSTITUTE GOODS OR SERVICES; LOSS OF USE, DATA, OR PROFITS; OR BUSINESS INTERRUPTION) HOWEVER CAUSED AND ON ANY THEORY OF LIABILITY, WHETHER IN CONTRACT, STRICT LIABILITY, OR TORT (INCLUDING NEGLIGENCE OR OTHERWISE) ARISING IN ANY WAY OUT OF THE USE OF THIS SOFTWARE, EVEN IF ADVISED OF THE POSSIBILITY OF SUCH DAMAGE.
Product Identification – smarty7
The smarty7 dw25x Series are Universal Automation Controllers (UAC)
Find smarty model and firmware version. Use savvy, Get Detailed Info from
smarty contextual menu. See page 6.
Product Identification – Part Numbers
Model number dw25x is appended with a three character extension.
smarty7 Models
dw250 Universal Automation Controller, (UAC).
dw254 UAC for P2 industrial vector drive.
dw258 UAC for E3 open-loop vector drive.
dw259 UAC for CANopen server devices.
Build Standard A, B, C, and D – Software Options
A=04 and 26, B adds 05 and 25, C adds 06 and 39, D adds 10 and 29.
04 ModbusTCP/IP – Server-slave. See page 12.
05 Process Control – Recommended for most applications.
06 Winder Control – Diameter Calc., Taper Tension, Torque Comp.
10 Math – With advanced math functions.
25 EIP/PCCC – Slave/server. See page 12.
26 savvyPanel – Operator station interface. See pages 8, 9.
29 Solar – Calculates sun position azimuth and zenith.
39 Precision Motion – With event, length, position, shaft-lock, indexing,
motion control, cam profile, and more. Page 12.
ModbusRTU Type, Options M, S, X
M – ModbusRTU Client-Master with speeds up to 500kbps. See page 12
S – ModbusRTU Server-Slave. Read or write any parameter in the device
remotely. See page 12.
X – No ModbusRTU capability.
XIO Build S7, HV, CL, XD, XA
S7 – Standard, no XIO option installed.
HV – Ten Digital Inputs, presets for 24VAC, 120VAC, or 240VAC.
Six Digital Outputs, 24VAC to 240VAC, 0.5A with ZVS.
CL – Sixteen 4-20mA inputs.
Eight 4-20mA outputs.
Eight digital out/in, separate source up to 24VDC, 300mA shared.
XD – Sixteen digital inputs, 3V to 30V logic with 5V and 24V enumeration.
Sixteen digital outputs/inputs, separate source up to 24VDC, two 300mA shared
banks.
XA – Four separately-isolated, milliVolt analog inputs w/ 5V excitation and
cold-junction compensation for load-cell, thermocouples, RTDs, 2V max.
Terminal Type P
P – Plug-in screw terminals; six blocks of 10 terminals; 60 total. See page 4.
Mounting D, S, F, A, 4
D – DIN rail edge mounting without flex clip.
S – DIN rail side, flat mounting using standard clips.
F – Flex mounting; DIN rail edge or DIN rail flat with flex clip.
A- Spacer mounting with four bolt holes, see page 5.
4 – NEMA4X enclosed.
smarty7 Installation
smarty is designed for permanent installation by qualified professionals.
Install smarty in metal enclosure with no RF noise source.
DIN rail mounting – Use 35×7.5mm rail per IEC 60715 or EN50022.
Environment – UL/IEC Pollution Degree 2.
Operating temperature, 0°C min., 50°C max.
Storage temperature, -20°C to 50°C.
Altitude 3000m max.
Humidity 95% max. non-condensing.
Clearances must be provided all around to promote airflow, 5mm (0.2”) sides,
25mm (1”) above and below.
smarty7
Terminal Naming and Ratings
Ter minal names are consistent in the drive.web savvy software, on the
terminal, and on the cover plate next to the terminal.
24VDC and 0V Terminals are internally connected.
Regulated DC Supply, 25.2Vmax, 22.8Vmin, 1A.
External 1A fast-acting fuse or current-limiting is required!
Do not connect to a distributed DC power network.
Supply from Class 2, LPS, limited power supply, from within the same
electrical enclosure, only.
AI – Analog inputs. -11VDC to +11VDC, 100kΩ, 1kHz, 16-bit. Also configurable
for 5V or 24V logic digital input. 30V max.
AO – Analog outputs. Bipolar, -10.5VDC to +10.5VDC. 10mA.
DI – Digital inputs. 50VDCmax, 8VDC threshold, 3V hysteresis. 1kHz.
Configurable as event inputs.
DO – Digital outputs. 24VDC source, up to 300mA, shared.
Resistive, general use, and pilot duty. Overcurrent protection and software
indication. Also configurable as digital inputs.
Maximum Voltage is 25.2VDC.
1A+ – Example: Encoder 1 Channel A+. Differential or singleended, incremental,
quadrature encoder input.
24VDC max, -0.5VDC min., Up to 1MHz. 2A and 2B can be configured as marker
inputs.
FT – Frequency, timing, event, stepper, or digital input and output. 30Vmax.
Use FI function blocks for inputs 100kHz. Configurable for 24V logic or 5V
logic with pull-up or pull-down. Configurable for frequency, counter, event,
or digital input.
Use TO function blocks for outputs. Configurable for stepper, frequency, or
digital sinking output. 20mA, 500kHz max.
TO7 – Same as FT TO above but also configurable as a digital input and a
unipolar analog input with settable range.
+5V Power supply output for use with encoders, sensors, etc, 250mA max.
smarty Terminal Wiring
Strip 7mm(0.28”). 1.5mm2 (AWG16) max. One wire with ferrule, 0.8mm2 (AWG18)
maximum.
Use shielded cable for runs over 30 meters.
Fast transient over-Voltage 1kV per EN 61000-4-4.
Signal Wiring Notes
Use twisted-pair wiring for encoder and serial differential signals.
Outside metal enclosure, use shielded cable with individually shielded
twisted-pairs such as Belden 8163. Ground shield at one end with a 360° ground
clamp where cable drive.web smarty enters “quiet” metal enclosure.
drive.web
Separate wiring from AC power cables or RF noise sources.
Front Panel
USB port – USB-C jack. Full/high speed. Can be used for backup power to
maintain the real-time clock.
drive.web
Ethernet port – MDI 8P8C, “RJ45” jack, 100baseTX and 10BaseT, Full Duplex,
Auto Negotiation, Auto-MDIX, IEEE 802.3ab.
smarty ebarty Indicator LEDs in front panel:
Status – Blue LED. Status heartbeat pulses twice a second.
Fault – Red LED indicates a fault. Check power supply, connect with savvy, or
contact us at drive.web for more info.
Ethernet link/activity – Orange LED indicates Ethernet connection and blinks
for activity.
100BaseTX – Green LED when connection is 100BaseTX.
DRIVE Serial Port
- AMPMODU 104257-4 socket marked ‘10101’
- ModbusRTU EIA485. Optional cable assembly, LA504452, required.
- dw254 and dw258 include 1m cable assembly, LA504451, for CANbus connection to P2 and E3 drives.
- dw259. Includes 1m cable assembly, LA504452. Do not add termination resistors for CANbus. These are built-in.
Dimensions, Overview, and Terminal Map
Spacer Panel Mount Option -A
Real-time Clock
- The real-time clock is only used for time of day and calendar functions. It can be set automatically by PTP to other drive.web devices, automatically upon discovery in the drive.web savvy software, per preferences, or via SNTP network time server protocol. See the savvy user manual for details.
- The real-time clock will be maintained for approximately 24hrs after supply power loss with no backup battery.
- Alternatively the clock can be powered by the USB port.
- Lithium button cell battery, CR2032, 3VDC, commonly found in convenience stores, is not provided from the factory due to shipping restrictions.
Frequency Input Notes (FI Terminals)
FI Digital and Event Input Function Blocks
Maximum event frequency is 1/(2*FBE cycle (s)) Hz. E.g., for 5ms FBE cycle,
the max event frequency is 1/10ms = 100Hz.
Use Digital Input function block Input Type parameter to configure;
FI Input
Type| Threshold
VDC| Threshold
Min. VDC| Threshold
Max. VDC
---|---|---|---
5V Logic with pulldown| 2.0| 1.0| 3.0
5V Logic with pull-up| 1.4| 0.4| 2.4
5V Logic| 1.7| 1| 2.4
24V Logic with pulldown| 8.4| 5| 11.8
FI Counter Inputs – Provide frequency data with adjustable moving-average
filter and count outputs for use with motion control function blocks.
FI Frequency Inputs – Useful for lower frequencies ~<10kHz. Duty cycle is also
measured. Updates every FBE cycle or two-edge cycle.
Programming
Set up your computer – Get savvy
With free drive.web savvy software, easily program and
monitor your smarty, perform data trending, and create distributed control
systems.
Go to www.driveweb.com and click on Get savvy, or
contact us to get the latest version of savvy.
smarty USB – Plug and Play
Plug-and-play access to smarty and its local Ethernet network.
smarty Ethernet Networking & Programming
Assigning an invalid or duplicate IP address will cause serious network
malfunctions!
Find useful networking information. Under the Help menu click on Getting
Started with savvy section.
-
smartys are shipped with an IP address, 10.189.x.x, derived from the serial number. The six-octet serial number always starts with 0-4-bb-x. The last two octets are used to assign the as-shipped IP address; Example, if the serial number is 0-4-bb-00-1a-2b, 1a is converted from hexadecimal to decimal, 26. 2b, similarly, is 43, decimal.
The as-shipped address is 10.189.26.43. -
Use Category 5e cable or better, with 8P8C/RJ-45 connectors for each drive.web device and the host computer.
-
For systems with more than one drive.web device, use an Ethernet switch for all drive.web devices and computer.
Get started with savvy
- We strongly recommend attending our free online training seminars. See page 12.
- We strongly recommend you read the User Manual and Getting Started Guides under the Help menu.
- Use Create Phantom in the Directory menu to explore drive.web products and options, design, and configure offline. Export Data to save your work. Import Data into phantoms to work offline.
savvy Window Title Bar indicates the current view.
Status Bar, above the viewing area, provides Navigation Arrows and object and
location data.
savvy views are hierarchical with the Device Directory View at top. Use the
Navigation Arrows to go up, back, or forward. Window menus change as you
navigate.
Hover cursor over active object, device, function block, connection, or
parameter icon to view object information in the Status Bar and reveal a Hover
Button.
Click a Hover Button or right-click an active object to access a Contextual
Menu. See below.
savvy functions are limited by password-protected capability level. See File >
Capability…
Device Directory Window
Warning! Changing a device IP address WILL disrupt its network connections! If
a smarty is communicating with other devices, be prepared for system
disruption. In the File menu choose Utility > Remap Export File to remap a dw-
system file with different IP address(es).
Select File>Administrate>Set IP Addresses for System.
smarty serial number is also its MAC Address.
Enter a valid IP address and click OK.
An icon appears with IP address beneath. Drive-dedicated models depict the
actual frame size of the drive.
If the icon at right appears, a network connection problem exists. Check
connections, LEDs, and that the smarty
IP address is within the computer’s Ethernet subnet mask.
Warning! Importing data into your smarty will result in immediate
execution of that configuration. Dangerous
****Voltages and rotating machinery may result! Use a phantom to preview a
configuration.
Directory > Import / Export Data. All device configurations and connections in
the directory in one .dw-system file. smarty Icon Contextual Menu
Change Name – Name your smarty for easy identification.
Import / Export Device Data… – Load / save configuration data to / from this
smarty only.
Unlock, Lock, Set Password – Choose Restrict
Modification to allow viewing the configuration, or Restrict All Access.
Click the smarty icon to view the device configuration.
Function Block Engine Window – FBE Menu
(Standard savvy, no SFD)
Add function blocks in the order to be processed. Processing order is left to
right, top to bottom.
Click function blocks to view parameters and details.
Connect between parameters and other drive.web devices.
Warning! Making a connection results in immediate execution of that
connection. Dangerous Voltages and rotating machinery may result!
Under the File menu, choose New Viewer… and then, File > Open Device
Directory.
With two viewer windows, click a parameter, drag and drop onto a parameter in
the other viewer.
Parameter Contextual Menu – Data is formatted, limited, and scaled depending
on the parameter. Use Get Info or Re-Scale… to verify or change.
Click parameters for the Setter Box – Increment, decrement, default, last
state, or keyboard entry.
Click blue connection block or arrow to jump to other end.
Upgrade savvy and smarty
Upgrade savvy with SFD Signal Flow Diagram.
Upgrade smarty with software options.
Process credit cards or Vouchers online or Coupons offline.
- To upgrade savvy, go to the Commerce menu, select
- Upgrade savvy, check desired options, click OK.
- To upgrade smarty, choose Upgrade Device… in its contextual menu, check desired options, click OK.
- To process Vouchers, choose Pay > Online Via Vouchers in the Shopping Cart. Enter Voucher codes on separate lines.
- To process Coupons, go to the Commerce menu and choose Coupon Manager. Enter codes in the top box and click the Add button and the coupon is recognized.
Click Apply.
savvy-SFD Signal Flow Diagram Upgrade
- With savvy-SFD, build systems graphically. The live drawings are stored in your smarty.
- Set drawing borders and annotate multi-page drawings.
- A filterable list of function blocks and connections is at the left of the Signal Flow Diagram showing program execution order from top down. Change execution order by dragging function blocks up or down the list. In this picture, ENC1 Speed function block is moved so that it is processed after ENC Phase Lock.
Operator Station
Computers, Apple®, and Android™ mobile digital devices are operator touch
stations with savvyPanel. Requires
Windows, Mac OS X, Linux-based Ubuntu, Android, or iOS®.
Configurations are stored in the drive.web devices.
savvy-SFD upgrade is required to edit or build savvyPanel systems.
dwOption-26 savvyPanel, must be installed in drive.web devices to enable the
full suite of tiles. A limited set is available without the option.
Get savvyPanel free from Apple App Store℠ and Google Play
- When your mobile digital device is connected to the internet via WiFi, demo mode connects to a live drive system in our plant in Maryland, USA.
- Explore the demo with savvy. Select File > Demo Mode > Discover Internet Demo DevicessavvyPanel Pages
Systems Page where multiple savvyPanel systems are present.
- A savvyPanel system may contain tiles from many drive.web devices.
- A drive.web device contributes to only one savvyPanel system.
- Touch the systems button , or , in the window bar to access the systems page from home page. Lock this button with home password.
Home Page is the first operator page in a savvyPanel system.
- Access home page from any operator page with the home button, . Lock with the home password.
Operator Pages show graphic, page-link, and parameter tiles.
- Pages can be renamed. Page name appears in window title bar.
Parameter Tiles – Touch a settable parameter to set. Setter includes slider,
keypad, lx and 10x increment and decrement, return-to-default, and revert.
Graphic Tiles – Create diagrams with process elements.
Page-Link Tiles – A graphic tile that is also a page-link.
Touch to change the view to that page.
Device Tiles – Link to device’s signal flow diagram in Java-based
savvyPanel. Appears as graphic tile in iOS.
Function blocks enable sawyPanel actions Alarm Annunciator – Provides
a system-wide alarm annunciation when active. Touch to view page 255.
Presence Monitor – Indicates the presence of a tagged savvyPanEl
application viewing a particular page.
Latch and SR Latch – For lighted start-stop pushbuttons.
_Setpoint & Monitor _– Adjust meter and setter range. Dual blocks enable
dual-display meters.
Enumerated Parameter – In Utility group. Only custom enumerations
appear in the setter and multi-position switch.
savvyPanel Launch, Setup, and Important Notes
- See the savvy user manual for detailed instructions.
- Launch savvyPanel via command line or batch file.
- Limit operators to savvyPanel only. Specify start system and page.
- Discover devices automatically, specifically by discovery file, or filtered by group and/or savvyPanel name.
- Operator’s note: If communication with a drive.web device is interrupted, affected tiles indicate a yellow bar with a warning symbol. The tile is not updated.
- Important Design Note – An over-range enumeration is required if an out-of-range value could cause a hazard.
smarty Precision Motion Parameters, Connections
Special parameter and connection types from I/O function blocks.
Connections may also be over Ethernet to other drive.web devices without
performance penalty.
Floating Point – IEEE-754 Binary32, wider range and resolution. Can be
connected to or from standard, 16-bit parameters; 1.0000 float equals 100.00%.
Event – Events are associated with exact count values.
Maximum event frequency is (1/(FBE Timebase seconds) Hz. Only the first event
is processed per FBE cycle.
Count – Position applications; shaft-lock, registration, motion control, etc.
64-bit internal values, precision timing data.
smarty Comms Interfaces-CANopen, Modbus, EIP/PCCC
Warning! Use of smarty comms interfaces may cause motors and machinery to
energize with high Voltages, or start, or operate in unexpected, dangerous, or
lethal ways.
For Modbus specs go to http://modbus.org/specs.php smarty Comms Server
dwOption-04 and -25
Note! You cannot write or force parameters that are read-only or have incoming
drive.web connections.
Click the Comms Server icon in the FBE or SFD view.
dwOption-04 ModbusTCP/IP slave/server
Supported Modbus Function Codes; 1 thru 6, 15, and 16.
Supports up to five simultaneous clients/masters.
dwOption-25 EIP/PCCC Server
Supports PLC5 Typed-Write and Typed-Read commands.
See Appendix B of the savvy User Manual for information and drive.web
parameter IDs mapping to PLC5.
Supports up to two simultaneous clients.
ModbusRTU
M=Master-Client, S=Slave-Server, X=None. See pages 2 and 4.
Modbus Function Codes FC 01 through 06 and 16 are supported. Also special
Yaskawa Holding Register.
Each server’s Modbus address must be unique on the network!
All devices on the network must have the same baud rate, up to 500.0kbps, and
the same character framing.
dw259 Generic CANopen Master
Dedicated to a single server device at speeds up to 1Mbps.
1m max cable length.
Do not use termination resistors. These are built-in.
Use CANopen Setup function block to configure.
drive.web Training Courses
Free online interactive training seminars take about one hour.
Specialized online and factory training sessions are also available.
To register email training@driveweb.com or
call.
drive.web 40 Log Canoe Circle, Stevensville, MD 21666 USA.
Ph. 410-604-3400, Fax
410-604-3500,
www.driveweb.com
smarty HG504266Iss1.2
www.driveweb.com
References
- Modbus Specifications and Implementation Guides
- Internet-Accessible Distributed Control Technology | drive.web
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>