HTW A3 Dehumidifier Owner’s Manual
- June 17, 2024
- HTW
Table of Contents
OWNER’S AND INSTALLATION MANUAL
DEHUMIDIFIER
A3
HTWD010A3 – HTWD012A3 – HTWD016A3
Please, read carefully this manual before using the product.
Thank you
Thank you for choosing a dehumidifier to provide you and your family with your home comfort needs. This user manual will provide you with valuable information necessary for the proper care and maintenance of your new dehumidifier. Please take a few minutes to carefully read the instructions and familiarize yourself with all operational aspects of this dehumidifier.
This unit removes unwanted moisture from the air to create a more comfortable environment in your home or office. It can be conveniently moved from room to room within your home.
Characteristics
Powerful dehumidification capacity
Taking advantage of refrigeration technology, the dehumidifier removes
moisture from the air at a high level, thus reducing the level of humidity in
the room and keeping it dry and comfortable.
Portable and lightweight design
The dehumidifier is built to be compact and lightweight.
quiet operation
The dehumidifier works with a low noise level.
Energy efficiency
The power consumption of the unit is low.
2. Safety warning
VERY IMPORTANT!
Please do not install or use your mobile air conditioner before carefully
reading this manual. Keep this instruction manual for eventual product
warranty and future reference.
Warning
Do not use means to accelerate the defrosting or cleaning process, other than
those recommended by the manufacturer.
The appliance should be stored in a place without continuously operating
sources of ignition (for example: open flames, a running gas appliance or a
running electric heater).
Do not pierce or burn.
Please note that refrigerants may be odorless.
The appliance must be installed, used and stored in a room with a surface area greater than 4 m2.
Maintenance shall be performed only as recommended by the manufacturer.
The appliance shall be stored in a well-ventilated area in which the size of
the room corresponds to the area of the room specified for its operation.
Any work procedure that affects the security means must only be carried out by
competent persons.
WARNING
Specific information on appliances with refrigerant gas R 290.
- Please read all warnings carefully.
- When defrosting and cleaning the device, do not use any tools other than those recommended by the manufacturer.
- The appliance should be placed in an area without continuous sources of ignition (for example: open flames, operating gas or electrical appliances).
- Do not pierce and do not burn.
- This appliance contains Y g (see the classification label on the back of the unit) of R290 refrigerant gas.
- R290 is a refrigerant gas that complies with European environmental directives. Do not pierce any part of the refrigerant circuit.
- If the appliance is installed, operated or stored in a non-ventilated area, the room must be designed to prevent the accumulation of refrigerant leaks resulting in a risk of fire or explosion due to ignition of refrigerant caused by electric heaters, stoves or other sources of ignition.
- The device must be stored in such a way as to avoid mechanical failures.
- The people who operate or work in the refrigerant circuit must have the appropriate certification issued by an accredited organization that guarantees competence in the handling of refrigerants according to a specific evaluation recognized by industry associations.
- The appliance shall be stored in a well-ventilated area in which the size of the premises corresponds to the area of the room specified for operation:
- Repairs must be carried out based on the recommendation of the manufacturing company. Maintenance and repairs that require the assistance of other qualified personnel must be performed under the supervision of a person specified in the use of flammable refrigerants.
- Do not use a defective or inappropriate plug.
- Do not use machines in the following situations
- A: Close to the fire source.
- B: An area where oil is likely to splash.
- C: An area exposed to direct sunlight.
- D: An area where water is likely to splash.
- E: Near a bathtub, shower, or swimming pool.
- Never insert your fingers into the air vent. Take special care to warn children of these dangers.
- Keep the unit upright during transport and storage as the compressor is located correctly.
- Before cleaning the appliance, always switch off or disconnect the power supply.
- When moving the appliance, always turn off and disconnect the power supply, and move it slowly.
- To avoid the possibility of a fire disaster, the appliance will not be covered.
- All appliance plugs must meet local electrical safety requirements. If necessary, check the requirements.
- Young children should be supervised to ensure that they do not play with the appliance.
- This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for your safety.
- If the power cord is damaged, it must be replaced by the manufacturer, its service agent, or similarly qualified persons to avoid a hazard.
- This appliance can be used by children aged 8 years and over and persons with reduced physical, sensory or mental capabilities or lack of experience and knowledge if they have been given supervision or instruction concerning safe use of the appliance and understand the hazards involved. Children must not play with the appliance. Cleaning and user maintenance shall not be made by children without supervision.
- The appliance shall be installed in accordance with the national wiring regulations.
- Fuse type and rating details: T, 250V AC, 2A. or bigger
- Recycling
This marking indicates that this product should not be disposed of with other household waste throughout the EU. To prevent possible damage to the environment or human health from the uncontrolled disposal of waste, recycle it responsibly to promote the sustainable reuse of material resources. To return your used device, please use the return and collection systems or contact the retailer where you purchased the product. They can take this product for environmentally safe recycling.
- GWP: R290: 3
- Contact the authorized service technician for repair or maintenance of this unit.
- Do not pull, deform. or modify the power cord, or immerse it in water. Pulling or misusing the power supply cord can damage the unit and cause electric shock.
- Compliance with national gas regulations will be observed.
- Keep ventilation openings free from obstruction.
- Anyone who is involved in working on or entering a refrigerant circuit must have a currently valid certificate from an industry-accredited testing authority, authorizing their competence to handle refrigerants safely in accordance with an industry-recognized testing specification. industry.
- Maintenance will only be performed as recommended by the equipment manufacturer. Maintenance and repair that require the assistance of other qualified personnel shall be carried out under the supervision of the person competent in the use of flammable refrigerants.
- Do not operate or stop the unit by inserting or removing the power plug from the die, it may cause electric shock or fire due to heat generation.
- Unplug the unit if there are strange sounds, smells or smoke coming from it.
Grades:
- If any part is damaged, please contact the dealer or a designated repair shop;
- In case of any damage, turn off the air switch, disconnect the power supply, and contact the dealer or a designated repair shop;
- In any case, the power cord must be firmly grounded.
- To avoid the possibility of danger, if the power cord is damaged, turn off the air switch and disconnect the power supply. It must be replaced by the dealer or a designated repair shop.
INSTRUCTIONS FOR REPAIRING APPLIANCES CONTAINING R290
1 GENERAL INSTRUCTIONS
1.1 Zone control
Before starting work on systems containing flammable refrigerants, safety
checks are necessary to ensure that the risk of ignition is minimized. For
refrigeration system repair, the following precautions must be observed before
conducting work on the system.
1.2 Work procedure
The work will be carried out in accordance with a controlled procedure that
minimizes the risk of the presence of flammable gas or vapor during the
execution of the work.
1.3 General area of work
All maintenance personnel and others working in the local area will receive
instructions on the nature of the work being carried out. Work in confined
spaces will be avoided. The area around the workspace will be sectioned off.
Ensure that conditions within the area have been made safe by controlling
flammable material.
1.4 Checking for the presence of refrigerant
The area will be checked with a suitable refrigerant detector before and
during the work, to ensure that the technician is aware of the existence of
potentially flammable atmospheres. Make sure that the leak detection equipment
used is suitable for use with flammable refrigerants, ie non-sparking,
properly sealed, or intrinsically safe.
1.5 Presence of fire extinguisher
If any hot work is to be carried out on the refrigeration equipment or any
associated part, adequate fire extinguishing equipment must be available. Have
a dry powder or CO2 fire extinguisher adjacent to the charging area.
1.6 Without sources of ignition
No person performing work in connection with a refrigeration system that
involves exposing any piping that contains or has contained flammable
refrigerant shall use any source of ignition in such a manner as to create a
risk of fire or explosion. All possible sources of ignition, including
smoking, must be kept far enough from the place of installation, repair,
removal and disposal, during which flammable refrigerant may be released into
the surrounding space. Before work is carried out, the area around the
equipment should be inspected to ensure that there are no flammable hazards or
ignition risks. “No Smoking” signs will be posted.
1.7 Ventilated area
Make sure the area is open or adequately ventilated before entering the system
or doing any hot work. A certain degree of ventilation will be maintained
during the period of carrying out the work. Ventilation must safely disperse
any released refrigerant and preferably exhaust it externally to the
atmosphere.
1.8 Refrigeration equipment controls
When electrical components are replaced, they must be fit for purpose and to
the correct specifications. The manufacturer’s maintenance and service
guidelines shall be followed at all times. If in doubt, consult the technical
department of the manufacturer for help. The following checks will be made for
installations that use flammable refrigerants: the size of the charge is
adjusted to the size of the room in which the parts containing refrigerant are
installed; the ventilation machine and the outlets work properly and are not
obstructed; if an indirect refrigeration circuit is used, the presence of
refrigerant in the secondary circuit shall be checked; equipment marking
remains visible and legible. It is necessary to correct the marks and signals
that are illegible;
1.9 Controls of electrical devices
Repair and maintenance of electrical components will include initial safety
checks and component inspection procedures. If there is a fault that could
compromise safety, no power supply will be connected to the circuit until it
is satisfactorily resolved. If the fault cannot be corrected immediately, but
it is necessary to continue operation, an appropriate temporary solution shall
be used. This will be reported to the equipment owner for all parties to be
informed.
Initial safety checks will include: discharging capacitors - this will be
done safely to avoid the possibility of sparks; that there are no live
electrical components and wiring exposed during system charging, recovery, or
purging; that there is continuity of the ground connection.
2 SEALED COMPONENT REPAIRS
2.1 During repairs to sealed components, all electrical supplies should
be disconnected from the equipment being worked on before removing sealed
covers, etc. If it is absolutely necessary to have a power supply to the
equipment during maintenance, then a permanently functioning form of leak
detection will be located at the most critical point to warn of a potentially
dangerous situation.
Maintenance shall be performed only as recommended by the manufacturer.
The appliance shall be stored in a well-ventilated area in which the size of
the room corresponds to the area of the room specified for operation.
2.2 Special attention shall be paid to the following to ensure that when
working on electrical components, the casing is not disturbed in such a way
that the level of protection is affected. This will include damaged cables, an
excessive number of connections, terminals not conforming to original
specifications, damaged gaskets, improper cable gland mounting, etc. Make sure
the appliance is securely mounted. Make sure that gaskets or sealing materials
have not degraded to the point that they are no longer effective in preventing
the ingress of flammable atmospheres. Replacement parts must conform to the
manufacturer’s specifications.
NOTE The use of silicone sealant may inhibit the effectiveness of some types
of leak detection equipment.
It is not necessary to isolate intrinsically safe components before working on them
3 REPAIR OF INTRINSICALLY SAFE COMPONENTS
Do not apply any permanent inductive load to the circuit without ensuring that
this does not exceed the allowable voltage and current for the equipment in
use.
Intrinsically safe components are the only ones that can be worked with while
living in the presence of a flammable atmosphere. The test apparatus shall
have the correct classification. Replace components only with parts specified
by the manufacturer. Other parts can ignite refrigerant in the atmosphere from
a leak.
4 WIRING
Check that the wiring will not be subjected to wear, corrosion, excessive pressure, vibration, sharp edges, or any other adverse environmental effects. The control will also take into account the effects of aging or continuous vibration from sources such as compressors or fans.
5 DETECTION OF FLAMMABLE REFRIGERANTS
In no case will potential sources of ignition be used in the search or detection of refrigerant leaks. A halide torch (or any other detector that uses a naked flame) will not be used.
6 LEAK DETECTION METHODS
The following leak detection methods are considered acceptable for systems containing flammable refrigerants. Electronic leak detectors should be used to detect flammable refrigerants, but the sensitivity may not be adequate or may require recalibration. (The detection equipment must be calibrated in an area free of refrigerant). Make sure the detector is not a potential source of ignition and is suitable for the refrigerant used. Leak detection equipment must be set to a percentage of the LFL of the refrigerant and will be calibrated for the refrigerant used and the appropriate percentage of gas confirmed (25% maximum). Leak detection fluids are suitable for use with most refrigerants, but the use of chlorine-containing detergents should be avoided, since chlorine can react with the refrigerant and corrode copper pipes. If a leak is suspected, all open flames must be removed/extinguished. If a refrigerant leak that requires brazing is found, all refrigerant must be recovered from the system or isolated (by means of shut-off valves) in a part of the system remote from the leak. Oxygen Free Nitrogen (OFN) will then be purged through the system before and during the brazing process.
7 REMOVAL AND EVACUATION
When breaking into the refrigerant circuit to make repairs, or for any other
purpose, conventional procedures will be used. However, it is important that
best practices are followed as it is in danger of being flammable. The
following procedure will be respected: eliminate the refrigerant; purge the
circuit with inert gas; evacuate; purge again with inert gas; open the circuit
by cutting or soldering. The refrigerant charge will be recovered into the
correct recovery cylinders. The system must be “flushed” with OFN for the
drive to be safe. This process may need to be repeated several times. No
compressed air or oxygen will be used for this task. Flushing will be
accomplished by breaking the vacuum in the system with OFN and continuing to
fill until working pressure is reached, then venting to the atmosphere and
finally going down into a vacuum. This process will repeat until there is no
refrigerant in the system. When the final OFN charge is used, the system will
be vented to atmospheric pressure to allow work to be carried out. This
operation is absolutely vital if brazing operations are to be carried out on
the pipes.
Make sure the vacuum pump outlet is not close to any ignition source and that
ventilation is available.
8 LOADING PROCEDURES
In addition to conventional charging procedures, the following requirements
shall be followed.
– Make sure that contamination of different refrigerants does not occur when
charging equipment is used. Hoses or lines should be as short as possible to
minimize the amount of refrigerant they contain.
– The cylinders will remain in a vertical position.
– Make sure the refrigeration system is grounded before charging the system
with refrigerant.
– Label the system when the upload is complete (if it has not already been
done).
– Extreme care should be taken not to overfill the refrigeration system.
Before recharging the system, it will be pressure tested with OFN. The system
must be leak checked at the end of the charge and before start-up. In
addition, a follow-up leak test will be performed before leaving the site.
9 DISASSEMBLY
Before carrying out this procedure, it is essential that the technician is
fully familiar with the equipment and all its details. It is recommended good
practice that all refrigerants are safely recovered. Before carrying out the
task, an oil and refrigerant sample will be taken in case an analysis is
necessary before the reuse of the regenerated refrigerant. It is essential
that electrical power is available before beginning the task.
a) Familiarize yourself with the equipment and its operation.
b) Electrically isolate the system.
c) Before attempting the procedure, ensure that mechanical handling equipment
is available, if necessary, to handle the refrigerant cylinders; all personal
protective equipment is available and used correctly; the recovery process is
supervised at all times by a competent person; Recovery equipment and
cylinders meet appropriate standards.
d) Pump down the refrigerant system, if possible.
e) If a vacuum is not possible, make a manifold so that refrigerant can be
removed from various parts of the system.
f) Make sure the cylinder is positioned on the scale before recovery occurs.
g) Start the recovery machine and run it according to the manufacturer’s
instructions.
h) Do not overfill cylinders. (No more than 80% liquid cargo by volume).
i) Do not exceed the maximum working pressure of the cylinder, even
temporarily.
j) When the cylinders have been filled correctly and the process is complete,
ensure that the cylinders and equipment are promptly removed from the site and
all insulation Equipment valves are closed.
k) Recovered refrigerant shall not be charged to another refrigeration system
unless it has been cleaned and checked.
10 LABELING
The equipment must be labeled indicating that it has been discharged and
emptied of refrigerant.
The label must be dated and signed.
Make sure there are labels on the equipment indicating that the equipment
contains flammable refrigerant.
11 RECOVERY
When removing refrigerant from a system, whether for maintenance or
disassembly, it is recommended good practice that all refrigerants be safely
disposed of. When transferring refrigerant to cylinders, ensure that only
suitable refrigerant recovery cylinders are used. Make sure the correct number
of cylinders to maintain the full system charge is available. All cylinders to
be used are designated for the recovered refrigerant and labeled for that
refrigerant (ie special refrigerant recovery cylinders). Cylinders shall be
complete with pressure relief valve and associated shut-off valves in good
working order. Empty recovery cylinders are evacuated and, if possible, cooled
before recovery occurs.
Recovery equipment should be in good working order with a set of instructions
relating to the equipment available and suitable for the recovery of flammable
refrigerants. In addition, there will be a set of calibrated scales in good
working order. Hoses shall be complete with disconnect couplings that are leak
free and in good condition. Before using the recovery machine, check that it
is in good working order, that it has been properly maintained and that all
associated electrical components are sealed to prevent ignition in the event
of a release of refrigerant. Consult the manufacturer if in doubt.
Leftover coolant will be returned to the coolant supplier with the
corresponding waste transfer note provided. Do not mix refrigerants in
recovery units and especially not in cylinders.
If compressors or compressor oils are to be removed, ensure they have been
evacuated to an acceptable level to ensure that flammable refrigerant does not
remain within the lubricant. The evacuation process will be carried out before
the compressor is returned to the suppliers. Only electric heating to the
compressor body will be used to speed up this process. When oil is drained
from a system, it will be done safely.
Competence of service personnel
General
Special training in addition to normal refrigeration equipment repair
procedures is required when equipment with refrigerants may be affected.
In many countries, this training is carried out by national training
organizations that are accredited to teach the relevant national competency
standards that may be set out in legislation.
The competence achieved must be documented by means of a certificate.
Training
The training must include the content of the following:
Information on the explosion potential of flammable refrigerants to
demonstrate that flammables can be dangerous when handled carelessly.
Information about possible sources of ignition, especially those that are not
obvious, such as cigarette lighters, light switches, vacuum cleaners, electric
heaters.
Information on the different security concepts:
Without ventilation - (see clause GG.2) The safety of the appliance does not
depend on the ventilation of the house. Switching off the device or opening
the casing does not have a significant effect on safety. However, it is
possible for leaking refrigerant to accumulate inside the The enclosure and
flammable atmosphere will be released when the enclosure is opened.
Ventilated enclosure - (see clause GG.4) The safety of the appliance depends
on the ventilation of the House. Switching off the device or opening the
casing has a significant effect on security. Care must be taken to ensure
sufficient ventilation beforehand.
Ventilated room - (see clause GG.5) The safety of the appliance depends on
the ventilation of the room. Switching off the device or opening the casing
does not have a significant effect on safety. Room ventilation should not be
turned off during repair procedures.
Information on the concept of sealed components and sealed enclosures
according to IEC 6007915:2010.
Information on correct work procedures:
a) Commissioning
• Make sure that the floor area is sufficient for the refrigerant charge or
that the ventilation The duct is assembled correctly.
• Connect the pipes and perform a leak test before charging with refrigerant.
• Check the equipment for safety before putting it into service.
b) Maintenance
• Portable equipment must be repaired outside or in a workshop specially
equipped for service units with flammable refrigerants.
• Ensure sufficient ventilation at the place of repair.
• Please note that equipment malfunction may be caused by loss of refrigerant.
• Discharge the capacitors in such a way that they do not cause sparks. The
standard procedure for shorting the capacitor terminals usually creates
sparks.
Shorting the capacitor terminals usually creates sparks.
• Reassemble sealed enclosures with precision. If the seals are worn, replace
them.
• Check the equipment for safety before putting it into service.
c) Repair
• Portable equipment must be repaired outside or in a workshop specially
equipped for service units with flammable refrigerants.
• Ensure sufficient ventilation at the place of repair.
• Please note that equipment malfunction may be caused by loss of refrigerant,
and refrigerant leakage may occur.
• Discharge the capacitors in a way that does not cause any sparks.
• When brazing is required, the following procedures shall be carried out in
due order:
- Remove the coolant. If recovery is not required by national regulations, drain the refrigerant outside. Take care that the drained coolant does not cause any danger. In case of doubt, one person should guard the exit. Be especially careful that the drained coolant does not float back into the building.
- Evacuate the refrigerant circuit.
- Purge the refrigerant circuit with nitrogen for 5 min.
- Evacuate again.
- Remove the parts to be replaced by cutting them, not with a flame.
– Purge the weld spot with nitrogen during the welding procedure.
– Carry out a tightness test before charging with refrigerant.
– Reassemble the sealed boxes with precision. If the seals are worn, replace
them.
– Check the safety equipment before commissioning.
d) Disassembly
• If safety is affected when the equipment is out of service, the refrigerant
The charge will be removed before disassembly.
• Ensure sufficient ventilation at the location of the equipment.
• Please note that equipment malfunction may be caused by loss of refrigerant.
Refrigerant leakage is possible.
• Discharge the capacitors in a way that does not cause any sparks.
• Remove the coolant. If recovery is not required by national regulations,
drain the refrigerant outside. Take care that the drained coolant does not
cause any danger. In case of doubt, one person should guard the exit. Be
especially careful that drained The refrigerant will not float back into the
building.
• Evacuate the refrigerant circuit.
• Purge the refrigerant circuit with nitrogen for 5 min.
• Evacuate again.
• Fill with nitrogen up to atmospheric pressure.
• Place a label on the equipment that removes the refrigerant.
d) Elimination
– Make sure there is sufficient ventilation in the workplace.
– Eliminate the refrigerant. If recovery is not required by national
regulations, drain the refrigerant outside. Take care that the drained coolant
does not cause any danger. In case of doubt, one person should guard the exit.
Be especially careful that the drained coolant does not float back into the
building.
– Evacuate the refrigerant circuit.
– Purge the refrigerant circuit with nitrogen for 5 minutes.
– Evacuate again.
– Disconnect the compressor and drain the oil.
Transport, marking and storage of units that use flammable refrigerants
Transportation of equipment containing flammable refrigerants
Special attention must be paid to the fact that there may be additional
transport regulations regarding appliances containing flammable gas. The
maximum number of equipment or the configuration allowed to be transported
together will be determined by the applicable transport regulations.
Equipment marking by signs
Signs for similar appliances used in a work area are generally addressed in
local regulations. and give the minimum requirements for the provision of
safety and/or health signs for a work location.
All required signs must be maintained and employers must ensure that employees
receive adequate and sufficient instruction and training on the meaning of the
appropriate safety signs and the actions to be taken in relation to these
signs.
The effectiveness of the signs should not be diminished by too many signs
being placed together. Any pictogram used should be as simple as possible and
contain only essential details.
Disposal of equipment using flammable refrigerants
See national regulations.
Equipment/Appliance Storage
Storage of equipment must be done in accordance with the manufacturer’s
instructions. Storage of packaged equipment (unsold)
The protection of storage packages must be constructed in such a way that
mechanical damage to the equipment inside the package does not cause a leakage
of the refrigerant charge.
The maximum number of devices that are allowed to be stored together will be
determined by local regulations.
General safety instruction
Before using the machine, read the instructions carefully so that you can take full advantage of all the functions of the machine. These instructions are indicative and do not form part of the contract, we reserve the right to make technical changes and we will not notify you before the modification.
Notice before using
- ” PLEASE MAKE SURE THE PRODUCT IS VENTILATED ALL THE TIME “! Make sure the intake and exhaust ventilation is not blocked at all times.
- Please operate this unit on a horizontal surface to avoid water leakage.
- Do not use this unit in an explosive or corrosive atmosphere.
- Machine working environment temperature: cooling at 5°C-35°C.
- When the unit is off, please wait at least 3 minutes before restarting, this is to avoid damaging the compressor.
- Use a separate power supply, prohibit sharing a plug with other electrical appliances, Power socket specifications should not be less than 10A, and plugs must be firmly secure.
- Power: 220-240V/50hz.
- Dispose of the water that has been collected in the tank as needed.
- Do not immerse the unit in water, or place the unit near water.
- Do not sit or stand on the unit.
- Dispose of the water that has been collected in the tank as needed.
- Do not operate the dehumidifier in an enclosed area, such as inside a closet, as it may cause a fire.
- Install drainage pipes on a downward slope to ensure that condensed water can be continuously drained.
3. Product diagram
- Front casing
- Outlet
- Handle
- Control panel
- Filter box
- Back cover
- Tank
- Rubber base
- Power cord
4. Operating Instructions
4.1 LED INDICATORS
- WATER FULL-LED
- COMP-LED
- DEFROST
- TIMER-LED
4.2 HUMIDITY LEVEL AND TIMER 2 DIGITAL DISPLAY
The indicator has 3 functions:
- When you set the humidity, it will indicate the humidity you have selected
- When you set the time for the unit to turn on and off, it will display the hours.
- When the ambient humidity is less than 35%, it will display “LO”
- When the environmental humidity is higher than 95%, it will display “HI”
4.3 BUTTON FUNCTIONS
A – Power button
B- Button down (DOWN) **
C- Up button (UP) **
D- TIMER button
4.4 OPERATING INSTRUCTIONS
1. Plug in the unit.
2. Press the **** button to start the operation, the power indicator will be on. Press it again to stop the operation.
3. Press or button to set the desired humidity level in the room, which
can be set from 30% to 90% at 5% intervals or “CO”.
After a period of work, when the ambient humidity is lower than the selected
humidity by 2%, the compressor will stop; When the ambient humidity equals or
exceeds the selected humidity by 3%, the compressor will restart after the
compressor protection time of 3 minutes ends. By setting the humidity to “CO”,
the compressor will run continuously.
4. The push button **** It can be the timer setting:
Press the button to set the time the unit turns on and off. If you want to
cancel the timer programming, please press the button to set the time to 0 and
press the button, it will cycle from 0-1-2 …… 23-24. Is the scheduled time to
change the machine. The programmed time will be canceled when the compressor
is changed manually each time. The programmed time remains unchanged if the
machine stops due to full water or during defrosting.
4.5 DRAINAGE OF COLLECTED WATER
When the drain tank is full, the full tank indicator light will turn on, the operation will stop automatically, and the buzzer will beep 15 times to alert the user that the water needs to be emptied from the drain tank.
Emptying the drain tank
1. Lightly press the sides of the tank with both hands and gently pull the tank out.
2. Dispose of collected water
NOTE
1. Do not remove the float from the water tank. The full water sensor will no longer be able to detect the water level correctly without the float and water may leak from the water tank.
2. If the drain tank is dirty, wash it with cold or lukewarm water. Do not
use detergent, scouring pads, chemically treated dust cloths, gasoline,
benzene, thinner, or other solvents as they may scratch and damage the tank
and cause water leakage.
3. When replacing the drain tank, press the tank firmly into place with both
hands. If the tank is not positioned correctly, the “TANK FULL” sensor will be
activated and the dehumidifier will not work.
4.6 CONTINUOUS DRAINAGE OF WATER
The unit has a continuous drain port. Using a plastic pipe (with an inner
diameter of 10mm) is inserted into the drain hole (on the intermediate plate),
extend from the side of the water tank, install it in place, and arrange the
drain pipe.
The water in the drain tank can be continuously drained from the continuous
port of the unit.
5.Maintenance
- Cleaning the dehumidifier
- to cleanse the body
- Clean it with a soft, damp cloth.
To clean the air filter
1. Open the intake grill first and remove the air filter
2. Clean the air filter
Lightly vacuum the surface of the air filter to remove dirt. If the air filter
is exceptionally dirty, wash it with warm water and a mild cleaner and dry it
well.
3.Connect the air filter
Insert the filter into the grill gently and place the inlet grill in the right
place.
Dehumidifier Storage
When the unit is not being used for a long period of time and you want to store it, please note the following steps:
- Empty any remaining water in the drain tank.
- Bend the power cord and put it into the water tank.
- Clean the air filter
- Discard in a cool, dry place.
Clear
Keep the minimum free space around the dehumidifier when the unit is running,
as shown in the drawing on the left.
6 Troubleshooting
If one of the following conditions occurs, check the following items before calling customer service.
Problem | Possible cause | Solution |
---|---|---|
The unit does not work | It has disconnected the power cord? | Plug the power |
cord into the power outlet.
Is the tank indicator light blinking? (The tank is full or in the wrong
position).| Empty the water in the drain tank and then put the tank back.
Is the room temperature above 35 °C or less than 5 °C?| The protection device
is activated and the unit cannot be started.
The dehumidification function does not work| Is the air filter clogged?| Clean
the air filter as indicated in “Cleaning the dehumidifier”.
Is the intake or discharge duct clogged?| Remove obstruction from intake or
discharge duct.
no air is discharged| Is the air filter clogged?| Clean the air filter as
indicated in “Cleaning the dehumidifier”.
Operation is noisy| Is the unit tilted or unstable?| Move the unit to a stable
and sturdy place.
Is the air filter clogged?| Clean the air filter as is indicated in “Cleaning
the dehumidifier”.
E1 code| Short circuit or open circuit of the coil sensor| Check if the line
is loose or replace the coil sensor.
C/ Can Cabanyes, 88, Polígono Industrial Can Gordi. 08403 Granollers.
Barcelona (Spain)
Tel (0034) 93 390 42 20 – Fax (0034) 93 390 42 05
info@htwspain.com –
www.htwspain.com
ESPAÑA FRANCE
info@htwspain.com
info@htwfrance.com
PORTUGAL ITALY
info@htw.pt
info.it@htwspain.com
INFORMACIÓN SAT
sat@groupgia.com
+34 933904220
sat.fr@groupgia.com
+33 465430168
sat.pt@groupgia.com
sat.it@groupgia.com
+39 05641715509
IMPORTANT INFORMATION FOR CORRECT DISPOSAL OF THE PRODUCT IN ACCORDANCE WITH
EC DIRECTIVE 2002/96/EC.
At the end of its working life, the product must not be disposed of as urban
waste. It must be taken to a special local authority deifferentiated waste
collection centre or to a dealer providing this service. Disposing of a
household appliance separately avoids possible negative consequences for the
environment and health deriving from inappropriate disposal and enables the
constituent materials to be recovered to obtain significant savings in energy
and resources. As a reminder of the need to dispose of household appliances
separately, the product is marked with a crossed-outwheeled dustbin.