DALI-PCD Tridonic Actuator Instruction Manual
- June 16, 2024
- TRIDONIC
Table of Contents
DALI-PCD 1-380 one4all G3
article number: 28004625 – TRI
INSTALLATION
Digital leading- edge or trailing-edge phase control dimmer with one4all interface to control dimmable LED retrofit bulbs, phase cut dimmable LED drivers and dimmable halogen transformers with a total power of 1 to 380 VA.
Technical data
Rated voltage | 220–240 V AC, 50/60 Hz |
---|---|
Connected load | 1–380 VA |
Power loss | 0.4 W (1.5 W at full load) |
Inputs | DALI/DSI and switchDIM control input |
Outputs | 1 dimmed phase |
DSI signal | 12 V (Manchester Code) |
DALI signal | 16 V (9.5–22.5 V Manchester |
Code)
DALI/DSI control line| NYM 2×1.5 mm² (H05VV 2×1.5 mm²)
Control range| 1–100 % DSI/switchDIM 0.1–100 % DALI (rel. illuminance)
Terminals| 0.5–1.5 mm²
Dimensions| 101.5 x 51 x 29.5 mm
Casing material| Polycarbonate
Weight| approx. 85 g
Perm. ambient temperature| 0–50 °C
Type of protection| IP 20
Mounting position| Universal
Miscellaneous| Thermal cutout (electronic 80 °C, bimetal 115 °C)
Installation instructions
- The power supply is connected, unswitched, to the L and N terminals.
- Only plastic screws may be used for fastening.
- At full load the anticipated power draw from the DALI-PCD 1-380 one4all is up to 1.5 W. There must be adequate heat removal as the ambient temperature of the DALI-PCD 1-380 one4all must not exceed 50 °C.
- For use with switchDIM function we recommend connecting the neutral conductor to DA/D1 because if a second phase is used there is a possibility of 400 V being applied between L and DA/D1. This prevents 400 V being applied between adjacent terminals if a different phase is used for the control input.
Safety instructions
- Installation of this device may only be carried out by specialist staff who have provided proof of their skills
- The power supply must be switched off before handling the device
- The relevant safety and accident prevention regulations must be observed.
Areas of application
The device may only
- be used for the applications specified
- for safe installation in dry, clean environment
- be installed in such a way that access is only possible using a tool.
01/23-15015405-0
We reserve the right to make technical changes without prior notice.
Tridonic GmbH & Co KG,
www.tridonic.com,
info@tridonic.com,
Tel. +43 5572 395-0