TRIDONIC 28003498 SmartSWITCH HF 12DP MB S f Instruction Manual

June 9, 2024
TRIDONIC

**TRIDONIC 28003498 SmartSWITCH HF 12DP MB S f Instruction Manual

**

Diminsions

Diminsions

smartSWITCH HF 12DP MB f (28003498)

Diminsions

smartSWITCH HF 12DP MB S f (28003499)

Diminsions

fine-stranded monobrin

Ceiling mounted
Diminsions

Wall mounted
Diminsions

Distance
Diminsions

Detection range

h 100 % 75 % 50 % 30 % 10 %

d
5 m| 12 m| 9 m| 6 m| 3 m| 1 m
6 m| 12 m| 8 m| 3 m| 1 m| –
7 m| 12 m| 6 m| 3 m| –| –
8 m| 12 m| 5 m| 2 m| –| –
9 m| 12 m| 4 m| 1 m| –| –
10 m| 12 m| 3 m| –| –| –
11 m| 10 m| 2 m| –| –| –
12 m| 10 m| 1 m| –| –| –

Technical Data

  • Rated supply voltage :  220 – 240 V
  • Mains frequency: 50 Hz
  • Power consumption: < 0.6 W
  • Frequency: 5.8 GHz (± 75 MHz)
  • Transmission power: < 0.1 mW
  • Load resistive: 800 W
  • Load capacitive: 400 VA
  • Detection angle : 30 – 150°

Max. detection area at 10 / 12 m

  • mounting height: ø = 10 m
  • Max. mounting height: 12 m
  • Dimension L x W x H (28003498): 70 x 36.5 x 24.5 mm
  • Dimension L x W x H (28003499): 58 x 52 x 24.5 mm
  • tc temperature :  85 °C
  • Ambient temperature ta: -20 … +70 °C
  • Storage temperature ts: -20 … +70 °C
  • Humidity :  min. 5 % … max. 85 % at 30 °C
  • Type of protection: IP20
  • Protection class: Reinforced insulation
  • Casing material: PC, halogen free
  • Casing colour: RAL 9016 (white)

Installation

  • Not for use with phase cut dimmers
  • The sensor must protrude over the light sources
  • The power supply must be disconnected before installation
  • Suitable for installation only in indoor luminaires (e.g. corridors and closed parking garage) without vibrations
  • Opening angle of the sensor: must be at least 45 %
  • Motion detection: only possible when thin housing material is used (e.g. plastic or glass), do not use metal housing
  • Light sensor: must be able to detect reflected artificial light and reflected daylight
  • Reflected HF waves (e.g. of walls, floors, ceilings or furniture) from other transmitters affect motion detection

Setting up

Setting the detection area

The detection area can be restricted to prevent the lighting system being switched on unnecessarily, as would be the case if the area was too large. The detection area indicates the diameter within which motion is detected.

| 1| 2| 3| Sensitivity
---|---|---|---|---
I| ●| ●| ●| 100 % (default)
II| ○| ●| ●| 75 %
III| ○| ●| ○| 50 %
IV| ○| ○| ●| 30 %
V| ○| ○| ○| 10 %

Setting the switch-off delay

To prevent the lighting system being switched on and off unnecessarily you can set a switch-off delay. The delay starts after the last motion in the detection area. If a further motion is detected in the detection area during this delay then the delay is retriggered. At the end of the delay the light will be switched off or the corridorFUNCTION is started.

| 4| 5| 6| Hold time
---|---|---|---|---
I| ●| ●| ●| 5 s (default)
II| ●| ○| ●| 30 s
III| ●| ○| ○| 1 min
IV| ○| ●| ●| 5 min
V| ○| ●| ○| 10 min
VI| ○| ○| ●| 20 min
VII| ○| ○| ○| 30 min

Setting the daylight threshold value

A threshold value can be set to prevent the lighting system from being switched on when there is already adequate illuminance. The threshold value indicates the illuminance value below which detected motion causes the lighting system to be switched on.

| 7| 8| 9| Daylight sensor
---|---|---|---|---
I| ●| ●| ●| Disable (default)
II| ○| ●| ●| 50 Lux
III| ○| ●| ○| 20 Lux
IV| ○| ○| ●| 5 Lux
V| ○| ○| ○| 2 Lux

Note:

To ensure the sensor switches on in conjunction with the corridorFUNCTION you should set the threshold value to I = Disable. If the threshold value disabled the sensor will always switch on.

corridorFUNCTION

The corridorFUNCTION can be activated by applying a voltage of 230 V for 5 minutes at the switchDIM connection of the control gear or via corridorFUNCTION Plug.
Note: To apply a voltage of 230 V for 5 minutes at the switchDIM input of the control gear the sensor must detect motion for more than 5 minutes or a switch-off delay longer than 5 minutes must be set.

Hereby, Tridonic declares that the radio equipment type smartSWITCH HF 12DP MB S f is in compliance with Directive 2014/53/EU.

Hereby, Tridonic declares that the radio equipment type smartSWITCH HF 12DP MB S f is in compliance with Directive UK SI 2017 No. 1206.

The full text is available at the following internet address:
https://trid.help/en28003498cer
https://trid.help/en28003499cer

Safety instructions

  • The device may only be used for the applications specified.
  • The relevant safety and accident prevention regulations must be observed.
  • The power supply must be switched off before handling the device.
  • Installation of this device may only be carried out by specialist staff who have provided proof of their skills.

04/22-15013823-2 We reserve the right to make technical changes without prior notice.
Tridonic GmbH & Co KG, www.tridonic.com, [email protected],
Tel. +43 5572 395-0

References