TRIDONIC NiMH 50 V Emergency Light LED Driver EM ConverterLED Instruction Manual
- June 4, 2024
- TRIDONIC
Table of Contents
NiMH 50 V Emergency Light LED Driver EM ConverterLED
Instruction Manual
NiMH 50 V Emergency Light LED Driver EM ConverterLED
EM converterLED BASIC NiCd/NiMH 50 V
BASIC version
Product Description
- Emergency lighting LED Driver for manual testing
- For self-contained emergency lighting
- For LED modules with a forward voltage of 10 – 54 V
- SELV for output voltage < 60 V DC
- Low profile casing (21 x 30 mm cross-section)
- For luminaire installation
- Nominal lifetime up to 100,000 h
- 5 years guarantee
Properties
- Non maintained operation
- 1 or 3 h rated duration
- Operating time selectable with plug (duration link)
- Compatible with all dimmable and non-dimmable constant current LED Driver (see data sheet, LED Driver compatibility)
- 3-pole technology: 2-pole LED module changeover and delayed power switching for the LED Driver
- Automatic shutdown of output if LED load is out of range
- Constant power output
- Maximum light output for all LED modules
- Electronic charge system
- Deep discharge protection
- Short-circuit-proof battery connection
- Polarity reversal protection for battery
Batteries
- High-temperature cells
- NiCd or NiMH batteries
- D, Cs, or LA cells
- 4-year design life
- 1-year guarantee
- For battery, compatibility refer to the datasheet
Website
http://www.tridonic.com/qr/89800559
The complete data sheet for this product is available in the Downloads section.
Note: Supply of control gear with duration link in 3 hours position.
Remove the duration link for a duration of 1 h. Duration link must be set
before battery and mains connection.
Ordering data
Type 3| Article number| Rated duration| Number of cells|
Packaging, carton| Packaging, pallet| Weight per pc.|
Dimensions L x W x H
---|---|---|---|---|---|---|---
EM converterLED BASIC 203 NiCd/NiMH 50V| 89800559| 1/3 h| 3| 10 pc(s).| 1,600
pc(s).| 0.065 kg| 179 x 30 x 21 mm
Technical data
Rated supply voltage | 220 – 240 V |
---|---|
AC voltage range | 198 – 264 V |
Mains frequency | 50 / 60 Hz |
Typ. λ (at 230 V, 50 Hz) | 0.6C |
Forward voltage range LED module | 10 – 54 V |
Output current | See datasheet |
Starting time | < 0.25 s from detection of emergency event |
Overvoltage protection | 320 V (for 48 h) |
U-OUT (including open- / short-circuit and double load) | 60 V |
Max. open circuit voltage | 60 V |
Battery charging time ①② | 24 h |
Ambient temperature ta | -5 … +55 °C |
Max. casing temperature tc | 75 °C |
Mains voltage changeover threshold | According to EN 60598-2-22 |
Mains surge capability (between L – N) | 1 kV |
Mains surge capability (between L/N – PE) | 2 kV |
Type of protection | IP20 |
Lifetime | up to 100,000 h |
Guarantee | 5 Year(s) |
Dimensions L x W x H | 179 x 30 x 21 mm |
Approval marks
Standards
according to EN 50172, according to EN 60598-2-22, EN 61347-1, EN 61347-2-13,
EN 61347-2-7, EN 55015, EN 61000-3-2, EN 61000-3-3, EN 61547, EN 60068-2-64,
EN 60068-2-29, EN 60068-2-30, EN 62384
Specific technical data
Type| Battery technology| Rated duration| Typ. output
power P emergency| Mains current in charging operation| Mains
power in charging operation
---|---|---|---|---|---
Initial
charge| Fast
recharge| Trickle
charge| Initial
charge| Fast
recharge| Trickle
charge
EM converterLED BASIC 203 NiCd/NiMH 50V| NiCd| 1 / -1 h| 2.4 W| 17 mA| 17 mA|
16 mA| 2.3 W| 2.3 W| 1.7 W
EM converterLED BASIC 203 NiCd/NiMH 50V| NiCd| 3 / -1 h| 2.4 W| 22 mA| 22 mA|
18 mA| 3.4 W| 3.4 W| 2.3 W
- 16 h battery charging time for 2 h emergency lighting function according to AS 2293.
- 12 h battery charging time for 2 h emergency lighting function when used with NiCd and NiMH batteries.
- EM = Emergency
Article information 06/21
Subject to change without notice.
www.tridonic.com
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>