TRIDONIC BasicDIM ILD 16DPI 69f Installation Guide

June 3, 2024
TRIDONIC

TRIDONIC Basic DIM ILD 16DPI 69f

BasicDIM ILD 16DPI 69f

Connection

Dimensions
Dimensions

h *

| Zoom| d
---|---|---
8 m| Low|

12.0 m

9 m

| Low| 13.5 m
10 m| Low|

15.0 m

11 m

| Low| 16.5 m
12 m| Low|

18.0 m

12 m

| High| 14.0 m
13 m| High|

15.2 m

14 m

| High| 16.4 m
15 m| High|

17.6 m

16 m

| High|

18.8 m

Sensor mounting

Sensor mounting

A:
All 6 snap-fits have to be snapped in
B:
To guarantee IP65 the distance between sensor surface and luminaire surface must be less than 8.5 mm
Sensor mounting

Shader mounting

Shader mounting

Zoom motion detection

To change from position Low to High rotate lens in arrow direction until it stops at High!
Zoom motion detection

Mounting box 16DPI

Zoom motion detection

  • Arrow shows the zoom position.
  • To change the zoom rotate the lens until it stops at High or Low position.

Compact control module with ambient light sensor and motion sensor.
For controlling up to 10 DALI or DSI ballasts.

Technical Data

  • Nominal voltage 220-240 VAC, 50 / 60 Hz
  • Power loss 2 W (standby 0.5 W)
  • Inputs 1 single switch (max. 100 m, 1.5 mm2), 1 sensor input)
  • Outputs 2 DALI/OSI outputs (max. 10 Dall/0S1 ballasts, max. 100 m, 1.5 mm2)
  • Dimming range 1-100 ‘%
  • Connecting terminals 0.5-1.5 mm2
  • Mounting luminaire installation
  • Dimensions 120 x 30 x 21 mm
  • Case material plastic
  • Permitted operating temp. 0 “” +60 °C
  • Type of protection controller P20
  • Type of protection sensor IP65 ready
Safety instructions
  • Installation of this device may only be carried out by specialist staff who have provided proof of their skills.
  • The power supply must be switched off before handling the device.
  • The relevant safety and accident prevention regulations must be observed.
Areas of application

The device may only

  • be used for the applications specified.
  • be used for safe installation in dry, clean environment.
  • be installed in such a way that access is only possible using a tool.

Installation

  • Don’t use the basic DIM ILD without a sensor.

  • OSI/DALI is not SELV. The installation instructions for mains voltage therefore apply.

  • The cable between the luminaire installation sensor and the base module must not be extended.

  • A synchronous operation of DALI and OSI ballasts at the same control gear is not possible.

  • Any number of push to make switches may be connected in parallel to the inputs.

  • Do not connect standard switches to the input.

  • Please ensure that the detection range of the sensor lies in the lighting area of the controlled luminaires.

  • Please ensure that the detection ranges of the sensors do not overlap.
    This may have influence to the lighting control.

  • Heaters, fans, printers and copiers located in the detection zone may cause incorrect presence detection.

  • Surface temperature is detected by the sensor. Clothing or covers which reduce the surface temperature affect the detection.

  • To avoid false readings, the sensor should be installed so there is no direct light from the lamp in the detection zone. Reflections can disturb the measurement results as well (e.g. high-bay warehouse of metal shelfs).

  • To avoid false measurements caused by the light from other luminaires we recommend that the sensor should be located centrally in the luminaire.

  • Sensor wires must be routed separately from the lamp wires and mains cables, otherwise the lighting control system may malfunction.
    If separate routing is not possible (for reasons of space) shielded lamp wires and mains cables must be used.

  • By repeatedly adjusting the zoom (> 10), the IP protection may be impaired.

  • Sensor must be installed according to the installation instructions to ensure the IP protection.

TRIDONIC-Logo.png

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals