TRIDONIC 28002681 Scenecom xl Instruction Manual

June 8, 2024
TRIDONIC

28002681 Scenecom xl
Instruction Manual

INSTALLATION

Topology A

Installation types

Application area

Control device with 3 DALI-compliant outputs for controlling a maximum of 192 luminaires.

Technical data

Nominal voltage 110–240 V, 50–60 Hz
Permissible input voltage 100–260 V, 50–60 Hz
Power dissipation Max. 20 W
Outputs 3 DALI-compliant outputs (DALI BUS 1 – 3); per output: max. 64 DALI

addresses;
Ports| 1 Ethernet port (Ethernet): RJ45 plug; speed of data transfer: 10/100 Mbit/s
Interface| Service Interface
Terminals| 0.5 – 2.5 mm²  (solid or fine-stranded)
Degree of protection| IP20
Protection class| Protection class II (only with correctly installed terminal covering)
Housing material| Polycarbonate (PC), flame-retardant, halogen-free
Installation| On top-hat rail, 35 mm in accordance with EN 50022
Dimensions| 160 × 91 × 62 (W × H × D, in mm), 9 HP every 17.8 mm
Permissible ambient temperature| 0–50°C, installation type 1 (e.g. in distribution board) 0–40°C, installation types 2 and 3
Permissible relative humidity| 20–90%, non-condensing
Weight| Approx. 600 g

System design and installation notes

  • Installation: fixed only, in a clean and dry environment, access only possible with tools; in solid distribution board or solid, closed distribution unit only, requirements given in standards for fire and contact safety must be met
  • Topology: connect sceneCOM XL and display device (touch panel, computer) via Ethernet cable (topology A) or connect sceneCOM XL and display device (touch panel, computer, mobile device) via a wireless access point (topology B)
  • Mains line: must not be interrupted by control points
  • Ethernet line: at least CAT5 cable, shielded
  • Bus line and DALI control line: use standard installation materials for low-voltage systems (< 1,000 V); only tree, linear and star topologies permitted
  • Bus cores: may be reverse connected
  • DALI control line
Conductor cross-section Maximum DALI line length
2 x 0.50 mm² 100m
2 x 0.75 mm² 150m
2 x 1.50 mm² 300m

Function key

The function key can be used to trigger certain functions

Triggering a function

  1. Press the function key.
  2. Release the function key in the desired orange phase.
    Function is triggered.

Orange phases (status LED device)

Orange phase Function
1 Restart the sceneCOM XL.
2 Delete the addresses and short addresses of all control gear and input

devices connected to the 3 DALI control lines.
3| Reset the IP address to the factory setting (10.10.40.254).

Test key

The test key can be used to trigger tests and certain functions for the related output (DALI BUS 1 – 3)

Triggering a function

  1. Press the test key.
  2. Release the test key in the desired orange phase.
    Function is triggered

Orange phases (status LED DALI BUS 1 – 3)

Orange phase Function
1 Exit test mode for all outputs.
2 Delete the addresses and short addresses of all control gear and input

devices connected to the corresponding DALI control line.

Test mode

  1. If the test key is pressed for less than 2 seconds, all connected luminaires are switched on.
  2. If the test key is then pressed again for less than 2 seconds, the luminaires alternate each time between on and off.
  3. To exit test mode, press the test key and release during the 1st orange phase

Status LED

Device

Status LED Duration Description
Green, intermittently flickering Continuous Fault-free operation
Off Continuous No mains voltage (L, N)

DALI BUS 1 – 3

Status LED Duration Description
Green, intermittently flickering Continuous Fault-free operation
Green, flashing on/off every 0.5 s Continuous Test mode
Orange, flashing on/off every 0.5 s Continuous Addressing (Exception: visual

and acoustic sensor location) or DALI initialisation
Off| Continuous| No mains voltage (L, N)
Red| Continuous| More than 64 DALI-compliant devices connected
Red, intermittently flickering| Continuous| DALI control line short-circuited or more than 120 DALI loads
Red, interrupted by intermittent green flickering| Continuous| Lamp failure

Safety instructions

  •  The device may only be used for the application area specified.
  • Relevant health and safety regulations must be observed.
  • When mounting and installing the device, the voltage supply must be disconnected.
  • Only qualified personnel may mount, install and commission the device.
  • Protection class II can only be guaranteed when the terminal covering has been correctly installed.
  • If a fault occurs, dangerous voltage levels may be present at the DALI terminals and on the DALI control line.

Installation

  • Disconnect the voltage supply.
  • Press the black locking hook down.

Installation type 1 (e.g. in distribution board)

  • First attach the top part and then the bottom part of the device to the top-hat rail.

Installation type 2

  •  First attach the top part and then the bottom part of the device to the top-hat rail.

Installation type 3
Depending on which side the black locking hook is situated:

  •  First attach the left part and then the right part of the device to the top-hat rail.
    — or —

  • First attach the right part and then the left part of the device to the top-hat rail.

  •  Fasten the locking hook again.

  •  Reconnect the voltage supply.

Initial steps after installation

Requirement:

  • The sceneCOM XL control device and display device (touch pane) computer) have been connected in accordance with topology A. -Or-
    The sceneCOM XL control device and display device (touch panel, computer, mobile device) have been connected in accordance with topology B.
  1. Ensure that the following settings are stored for the display device and the wireless access point:
    – IP address 1010.40.2 – 10.10.40.253
    – Subnet mask 255255.0.0

  2. Open a browser (Google Chrome recommended).

  3. Go to the IP address of the sceneCOM XL (1010.40.254).
    → The Tridonic system web application is displayed.

  4. Run the installation test (see Test key – Test mode).

  5. Correct the installation faults.

  6. Commission the Tridonic system.
    Note: Detailed information on commissioning and configuration can be found in the commissioning instructions.

For latest software versions please access our WEB page: www.tridonic.com/software

PHASED OUT
Tridonic GmbH & Co KG
Faerbergasse 15
6850 Dornbirn AUSTRIA
www.tridonic.com
sceneCOM XL_IA_190212 ©

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals