TRIDONIC 28002681 Scenecom xl Instruction Manual
- June 8, 2024
- TRIDONIC
Table of Contents
28002681 Scenecom xl
Instruction Manual
INSTALLATION
Topology A
Installation types
Application area
Control device with 3 DALI-compliant outputs for controlling a maximum of 192 luminaires.
Technical data
Nominal voltage | 110–240 V, 50–60 Hz |
---|---|
Permissible input voltage | 100–260 V, 50–60 Hz |
Power dissipation | Max. 20 W |
Outputs | 3 DALI-compliant outputs (DALI BUS 1 – 3); per output: max. 64 DALI |
addresses;
Ports| 1 Ethernet port (Ethernet): RJ45 plug; speed of data transfer: 10/100
Mbit/s
Interface| Service Interface
Terminals| 0.5 – 2.5 mm² (solid or fine-stranded)
Degree of protection| IP20
Protection class| Protection class II (only with correctly installed terminal
covering)
Housing material| Polycarbonate (PC), flame-retardant, halogen-free
Installation| On top-hat rail, 35 mm in accordance with EN 50022
Dimensions| 160 × 91 × 62 (W × H × D, in mm), 9 HP every 17.8 mm
Permissible ambient temperature| 0–50°C, installation type 1 (e.g. in
distribution board) 0–40°C, installation types 2 and 3
Permissible relative humidity| 20–90%, non-condensing
Weight| Approx. 600 g
System design and installation notes
- Installation: fixed only, in a clean and dry environment, access only possible with tools; in solid distribution board or solid, closed distribution unit only, requirements given in standards for fire and contact safety must be met
- Topology: connect sceneCOM XL and display device (touch panel, computer) via Ethernet cable (topology A) or connect sceneCOM XL and display device (touch panel, computer, mobile device) via a wireless access point (topology B)
- Mains line: must not be interrupted by control points
- Ethernet line: at least CAT5 cable, shielded
- Bus line and DALI control line: use standard installation materials for low-voltage systems (< 1,000 V); only tree, linear and star topologies permitted
- Bus cores: may be reverse connected
- DALI control line
Conductor cross-section | Maximum DALI line length |
---|---|
2 x 0.50 mm² | 100m |
2 x 0.75 mm² | 150m |
2 x 1.50 mm² | 300m |
Function key
The function key can be used to trigger certain functions
Triggering a function
- Press the function key.
- Release the function key in the desired orange phase.
→ Function is triggered.
Orange phases (status LED device)
Orange phase | Function |
---|---|
1 | Restart the sceneCOM XL. |
2 | Delete the addresses and short addresses of all control gear and input |
devices connected to the 3 DALI control lines.
3| Reset the IP address to the factory setting (10.10.40.254).
Test key
The test key can be used to trigger tests and certain functions for the related output (DALI BUS 1 – 3)
Triggering a function
- Press the test key.
- Release the test key in the desired orange phase.
→ Function is triggered
Orange phases (status LED DALI BUS 1 – 3)
Orange phase | Function |
---|---|
1 | Exit test mode for all outputs. |
2 | Delete the addresses and short addresses of all control gear and input |
devices connected to the corresponding DALI control line.
Test mode
- If the test key is pressed for less than 2 seconds, all connected luminaires are switched on.
- If the test key is then pressed again for less than 2 seconds, the luminaires alternate each time between on and off.
- To exit test mode, press the test key and release during the 1st orange phase
Status LED
Device
Status LED | Duration | Description |
---|---|---|
Green, intermittently flickering | Continuous | Fault-free operation |
Off | Continuous | No mains voltage (L, N) |
DALI BUS 1 – 3
Status LED | Duration | Description |
---|---|---|
Green, intermittently flickering | Continuous | Fault-free operation |
Green, flashing on/off every 0.5 s | Continuous | Test mode |
Orange, flashing on/off every 0.5 s | Continuous | Addressing (Exception: visual |
and acoustic sensor location) or DALI initialisation
Off| Continuous| No mains voltage (L, N)
Red| Continuous| More than 64 DALI-compliant devices connected
Red, intermittently flickering| Continuous| DALI control line short-circuited
or more than 120 DALI loads
Red, interrupted by intermittent green flickering| Continuous| Lamp failure
Safety instructions
- The device may only be used for the application area specified.
- Relevant health and safety regulations must be observed.
- When mounting and installing the device, the voltage supply must be disconnected.
- Only qualified personnel may mount, install and commission the device.
- Protection class II can only be guaranteed when the terminal covering has been correctly installed.
- If a fault occurs, dangerous voltage levels may be present at the DALI terminals and on the DALI control line.
Installation
- Disconnect the voltage supply.
- Press the black locking hook down.
Installation type 1 (e.g. in distribution board)
- First attach the top part and then the bottom part of the device to the top-hat rail.
Installation type 2
- First attach the top part and then the bottom part of the device to the top-hat rail.
Installation type 3
Depending on which side the black locking hook is situated:
-
First attach the left part and then the right part of the device to the top-hat rail.
— or — -
First attach the right part and then the left part of the device to the top-hat rail.
-
Fasten the locking hook again.
-
Reconnect the voltage supply.
Initial steps after installation
Requirement:
- The sceneCOM XL control device and display device (touch pane) computer) have been connected in accordance with topology A. -Or-
The sceneCOM XL control device and display device (touch panel, computer, mobile device) have been connected in accordance with topology B.
-
Ensure that the following settings are stored for the display device and the wireless access point:
– IP address 1010.40.2 – 10.10.40.253
– Subnet mask 255255.0.0 -
Open a browser (Google Chrome recommended).
-
Go to the IP address of the sceneCOM XL (1010.40.254).
→ The Tridonic system web application is displayed. -
Run the installation test (see Test key – Test mode).
-
Correct the installation faults.
-
Commission the Tridonic system.
Note: Detailed information on commissioning and configuration can be found in the commissioning instructions.
For latest software versions please access our WEB page: www.tridonic.com/software
PHASED OUT