TRIDONIC 28000882 Control Module DSI Signal Instruction Manual
- June 8, 2024
- TRIDONIC
Table of Contents
- Installation Instruction
- Cable types
- Function selection DSI-V/T
- Standard function
- PC function
- Technical data
- Cable lengths
- Tunnel function
- PD on/off function (Presence Detection)
- PD only off (Presence Detection)
- PD never off (Presence Detection)
- Scene function
- Saving a scene
- Retrieving a scene
- Customer support
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
TRIDONIC 28000882 Control Module DSI Signal
Installation Instruction
The digital DSI control module is designed to control up to 50 digital units such as electronic control gear, transformers and phase dimmers. It therefore has all the properties shared by all DSI units so far and enables PCA/TE one4all/PCD digital electronic control gear to be automatically switched and controlled via the control line
Cable types
Standard installation and wiring material is used.
According to DIN VDE 0100/T520/Part 6, main circuits and associated auxiliary
circuits may be laid together even if the auxiliary circuits carry a lower
voltage than the main circuits. Make sure to use cable designed to take the
maximum operating voltage.
A twisted or stranded 2-core cable approved for lowvoltage systems is used as
the bus line (2×1.5 mm² is recommended). The cable must be designed for a test
voltage of 4 kV between the wires and external sheath surface (test in
accordance with DIN VDE 0472/Part 508). The cables are not shielded. One twist
per metre is recommended; on per 5 metres is the minimum. e.g.:
H 05 VV-U 2×0.75 (NYM 2×0.75 mm² twisted)
H 05 VV-U 2×1.5 (NYM 2×1.5 mm² twisted)
J-Y(ST)Y tested to 4 kV
PYCYM 2 x 2 x 0.8 (diameter) Note: this corresponds to 2 x 2 x 0.5 mm²
Function selection DSI-V/T
DIP switch for selecting DSI-V or DSI-T
Standard function
- Standard: The DSI signal is received, amplified (signal amplitude), refreshed (on a time basis) and output again.
PC function
- PC: The return channel is deactivated at the input for connection of the serial RS232 interface of winDIM
Technical data
Type
| | DSI-T mode| DSI-V mode
---|---|---|---
Article number:| | 28000882|
28000882
Power supply:
| Mains voltage| V| 120–277| 120–277
Frequency
| Hz| 50/60|
50/60
Maximum output| VA (W)| < 1,0|
< 1,0
Inputs:
|
Switch
| –| one-way/two-way|
–
Presence detector
| –| yes| –
Max. cable length to the switches| m| 100|
–
Input voltage switch/PD
| V| 120–277| –
Frequency| Hz| 50/60|
–
DSI signal
| –| –| DSI/winDIM
Outputs:
| DSI controller| –| 1|
1
Signal
| –| digital/serial| digital/serial
Voltage| V| 12 ±10 %|
12 ±10 %
Data rate
| Bd| 1200| 1200
Control power per output| PCA/TE one4all/PCD| 50|
50
Maximum cable length
| m| 250|
250
Cable length definition:
| Max. cable length for bridging in tunnel mode (otherwise 250 m) for min. 1.5 mm²| m| –|
500
Temperature:
| Permissible ambient temperature| °C| -25 → +60|
-25 → +60
Cable lengths
| 0.5 mm²| 0.75 mm²| 1.5 mm²
---|---|---|---
Built-in ceiling/luminaire modules| 125 m| 125 m|
250 m
DSI signal amplifier (DSI-V)
| 125 m| 125 m|
250 m
Tunnel function
- Safety mode specifically for tunnel applications. If a DSI signal is not received within a period of 60 seconds, the DSI-V/T will fade up to 100 % brightness. A DSI value of 0 is forwarded only if the signal is received three times in succession (this enhances the fault tolerance of the system). This makes it difficult to switch off the system inadvertently. Fault reporting is also suppressed
PD on/off function (Presence Detection)
- The PD input is closed: The lighting is switched on immediately. The OSI value fades to the memory value.
- The PD input is opened: The lighting fades down and switches off with a fade time of 60 seconds (for a OSI value of 255).
PD only off (Presence Detection)
- The PD input is closed: The lighting is switched on immediately. The OSI value fades to the memory value.
- The PD input is opened: The lighting fades down and switches off with a fade time of 60 seconds (for a OSI value of 255). If the presence detector now detects activity again and therefore closes the PD input, the lighting will still remain dark. The lighting can only be switched on by means of the external switch. If this switch is now actuated the lighting will fade up to the last OSI value set
PD never off (Presence Detection)
- The PD input is closed. The lighting is switched on.
- The lighting fades up to the last OSI value set.
- The PD input is opened. The lighting fades down to 3 %; it is not switch off.
- ON/OFF switching is possible only with the one-way/two-way switch.
Scene function
- The PD input is closed: A switch for retrieving scenes is connected to the PD input.
Saving a scene
- Long press (> 1 O seconds): The current OSI value is saved as the memory value.
- This is signalled by double flashing for 0.7 seconds (min. -max. -min. -max.).
Retrieving a scene
- Short press (50-600ms): The saved scene (memory value) is retrieved.
Customer support
11/14-1005-3 We reserve the right to make technical changes without prior
notice.
Tridonic GmbH & Co KG, www.tridonic.com,
info@tridonic.com, Tel. +43 5572 395-0