**SALTO CUC1B0 BLUEnet Door Controller

**

DIMENSIONS

CUC1B0 series

Wireless door controller for 1 door access control with BLE.

Installation

ELECTRICAL CABINET WITH DIN RAIL

ELECTRICAL CABINET WITH DIN RAIL AND TAMPER

In the software, set the connection that you’ve connected the tamper wire to as “Tamper input”.

Wiring

  1. Input/Output: power input/output and proprietary serial bus for communication with expansion boards. There are two groups of connections that are %100 identical.
  2. Relay outputs: (1A/30VDC).
  3. Connection with the wall reader: consult the wall reader installation guide for more detailed information about the type of recommended wiring, connections and maximum distances.
  4. Inputs: inputs for external configuration (default, IN2, tamper).
  5. CLEAR button: short press to pair with the connected wall reader and discover and pair devices on the proprietary serial bus; long press will accept a new Portable Programmer (PPD), only in the Space platform.

Factory configuration inputs and relays

FACTORY CONFIGURATION

IN1| Door status *| Unsupervised NC
IN2| Exit| Unsupervised NO
RL1| Door relay|
RL2| Tamper alarms, loss of communication, DLO and intrusion|

CUAPAC or third party readers

| WIEGAND
---|---
IN1| Input D0
IN2| Input D1

POWER Min Max Typ
Input voltage 10V 30V 12V
Max Current Consumption* 700mA
Reader output Voltage 12V

  * This is the consumption of the CUC1B0 series, installer must calculate the power supply needed

| INPUT
---|---
Electrical characteristics| 5V
Configuration| Via Software

CABLE REQUIREMENTS

EXT BUS| 22 – 16 AWG (≤1m)|
Inputs| AWG24|
Readers| AWG18|

| INPUT
---|---
Electrical characteristics| 5V
Configuration| Via Software

OPERATING CONDITIONS

Temperature| -35ºC| 70ºC
Humidity| 0| 95% (Non condensing)

OUTPUT RELAYS

Rated load (resistive)| 1A – 30Vdc

  Applies to CUC1B0 model only!

SALTO BLUEnet CHARACTERISTICS

Frequency Range| 2400 MHz to 2483.5 MHz
Standard| Bluetooth 4.2
TX power| 6dBm
Indoor Range| 5-10m *

*The environment has a direct impact on the BLUEnet range radiation (metal, concrete walls…). The receiver device must be located facing the product antenna.
Please check your product´s BLUEnet antenna position. Recommended connectivity distance 5-10m.

Installation example

Cable connection

B Green
A White
Black
+ Red
  1. NC Switch Door
  2. NO Switch RTE
  3. Electric Strike
  4. Strike Protection Varistor

Installation example

Signaling

LED STATUS CUC1B0 CUCEB122
BLINKING YELLOW Long press off CLR Not paired with CUC180
OFF No power
SOLID GREEN All internal communications established and working correctly

(serial Bus owner WRs)
SOLID RED| After booting device indicates if it was powered correctly. The light will remain red if there are no internal communications established
BLINKING RED| Communication problems (serial Busowner WR)

 Operational test

Once the control unit has been installed, to check it has been installed correctly, make sure that when powering the device, the LED is solid green.