MFZ12DBT-UC Digital Settable Multifunction Time Relay with Display and
Bluetooth
Instruction Manual
MFZ12DBT-UC Digital Settable Multifunction Time Relay with Display and
Bluetooth
Only skilled electricians may install this electrical equipment otherwise
there is the risk of fi re or electric shock! Temperature at mounting
location: -20°C up to +50°C.
Storage temperature: -25°C up to +70°C.
Relative humidity: annual average value <75%.
Eltako Connect app download:
https://eltako.com/redirect/eltako-connect
Digital settable multifunction time relay with display and Bluetooth with
Eltako Connect app. With 18 functions. 1 CO contact potential free 10 A/250 V
AC. 230 V LED lamps up to 200 W, incandescent lamps 2000 W*. With display
lighting. Standby loss 0.1-0.3 watt only. Modular device for DIN-EN 60715 TH35
rail mounting. 1 module = 18 mm wide, 58 mm deep. With the patented Eltako
Duplex technology (DX) the normally potential-free contacts can still switch
in zero passage when switching 230 V AC 50 Hz and therefore drastically reduce
wear. Simply con- nect the neutral conductor to the terminal (N) and L to 15
(L) for this. This gives an additional standby consumption of only 0.1 Watt.
Universal control voltage 12..230 V UC. Supply voltage same as the control
voltage. Both functions and times are entered at the touch of a key and
indicated digitally on an LC display. Only two keys are required for this
purpose. When setting the time all values can be entered within preset time
ranges (0.1 to 9.9 or 1 to 99 seconds, minutes or hours). The longest possible
setting is 99 hours. 600 settings are possible. The time setting is
continuously displayed digitally. By using a biostable relay coil power loss
and heating is avoided even in the on mode. The switched consumer may not be
connected to the mains before the short automatic synchronization after
installation has terminated.
Functions
RV = off delay
AV = operate delay
AV+ = operate delay additive
TI = clock generator starting with impulse
TP = clock generator starting with pause
IA = impulse controlled pickup delay (e.g. automatic door opener)
IF = pulse shaper
EW = fleeting NO contact
AW = fleeting NC contact
EAW = fleeting NO contact and fleeting NC contact
ARV = operate and release delay
ARV+ = operate and release delay additive
ES = impulse switch
SRV = release-delay impulse switch
ESV = impulse switch with release delay and switch-off early- warning function
ER = relay
ON = permanent ON
OFF = permanent OFF
With TI, TP, IA, EAW, ARV and ARV+ functions, a different second time can be
entered also with different time ranges.
The time relay is set either via Bluetooth with the app or with the MODE and
SET but- tons, a button lock is possible. The display lighting is switched on
by pressing MODE or SET for the first time.
20 seconds after you last press MODE or SET, the program returns automatically
to normal display and the display illumination goes off.
Connect the time relay to the app: Press SET, the display shows BLE
(Bluetooth) and the ID of the time relay. The connection to the app can now be
established (delivery state PIN 123123). Scan the QR code on the operating
instructions, the app guides you through the learning process. After the
connection to the app has been established, BLE+ appears in the display. The
MODE and SET buttons are now locked. After 20 minutes without interacting with
the time relay, the connection is automatically disconnected.
Change PIN : The PIN for the Bluetooth connection can be changed in the
app under the Device PIN entry.
Bluetooth reset (delete any changed PIN): The connection to the app must
be disconnected. Press MODE and SET simultaneously for 2 seconds, RES fl ashes
in the display. Now press SET for 2 seconds, bleb appears in the display. If
you confirm with SET, the BLE reset is carried out, the PIN is deleted and the
delivery status is restored.
Set the time relay with the MODE and SET buttons: Pressing the MODE
button selects the LCD element to be changed. The element currently being
accessed fl ashes. Pressing the SET button changes the element being accessed.
This can be the function, time frame, time T1 or time T2 (TI, TP, IA, EAW, ARV
and ARV+ only). Each entry is terminated with the MODE key. After setting the
time with MODE, no element fl ashes anymore – the time relay is ready for
operation. Press the MODE key again to restart the input cycle. All the
entered parameters are retained if they are not changed using SET. 25 sec.
after the last operation and if the component still fl ashes the input cycle
is automatically terminated and the previously made changes lapse.
Functions of the LC display:
If the ON or OFF function was selected, no time is dis played, only ON and OFF
and a contact symbol in the correct position. On all other functions, the set
time, the function code and the contact symbol are shown in the correct
position (open or closed). The clock symbol fl ashes while the set time is
elapsing and the remaining time is shown.
Safety in the event of a power failure:
The set parameters are stored in an EEPROM and are therefore immediately
available again when the power supply is restored after a power failure.
Typical connection
Description of functions
AV+ = Function same as AV. However, after an interruption the elapsed time is stored.
ARV+ = Same function as ARV, but after an interruption of the operate delay
the elapsed time is stored.
ES = With control impulses from 50 ms the make contact switches to and fro.
SRV = With control impulses from 50ms the make contact switches to and fro. In
the contact position 15-18, the device switches automatically to the rest
position 15-16 on delay time-out.
ESV = Function same as SRV. Additionally with switch-off early warning:
approx. 30 sec. before time-out the lighting starts flickering 3 times at
gradually shorter time intervals.
ER = As long as the control contact is closed the make contact reverts from
15-16 to 15-18.
- The maximum load can be used starting at a delay time or clock cycle of 5 minutes. The maximum load will be reduced for shorter times as follows: up to 2 seconds 15%, up to 2 minutes 30%, up to 5 minutes 60%.
Technical data
Supply voltage and control voltage DC | 12..230 V UC |
---|---|
Rated switching capacity | 10 A/250 V AC |
The strain relief clamps of the terminals must be closed, that means the
screws must be tightened for testing the function of the device. The terminals
are open ex works.
Manuals and documents in further languages:
http://eltako.com/redirect/MFZ12DBT-UC
Frequency | 2,4 GHz |
---|---|
Transmit power | max. 1 mW |
Hereby, Eltako GmbH declares that the radio equipment type MFZ12DBT-UC is in
compliance with Directive 2014/53/EU.
The full text of the EU declaration of conformity can be accessed via the QR
code or the internet address under ‘Documents’.
Must be kept for later use!
We recommend the housing for operating instructions GBA14.
Eltako GmbH
D-70736 Fellbach
Technical Support English:
+49 711 943 500 25v
technical-support@eltako.de
eltako.com
04/2023 Subject to change without notice.