PEPPERL FUCHS KFD2-UT2-Ex1 Universal Temperature Converter Instruction Manual

June 13, 2024
Pepperl Fuchs

PEPPERL FUCHS logo Instruction Manual

Marking

Universal Temperature Converter
KFD2-UT2-Ex1, KFD2-UT2-Ex1-1, KFD2-UT2-Ex2, KFD2-UT2-Ex2-1

ATEX certificate: CESI 04 ATEX 143
ATEX marking:
1 II (1)G [Ex ia Ga] IIC
1 II (1)D [Ex ia Da] IIIC
1 I (M1) [Ex ia Ma] I
ATEX certificate: TÜV 02 ATEX 1797 X
ATEX marking: 1 II 3G Ex nA II T4
IECEx certificate: IECEx TUN 07.0003
IECEx marking:
[Ex ia Ga] IIC
[Ex ia Da] IIIC
[Ex ia Ma] I
IECEx certificate: IECEx CML 16.0126X
IECEx marking: Ex nA IIC T4 Gc
Pepperl+Fuchs Group
Lilienthalstraße 200, 68307 Mannheim, Germany
Internet: www.pepperl-fuchs.com

Target Group, Personnel

Responsibility for planning, assembly, commissioning, operation, maintenance, and dismounting lies with the plant operator.
The personnel must be appropriately trained and qualified in order to carry out mounting, installation, commissioning, operation, maintenance, and dismounting of the device. The trained and qualified personnel must have read and understood the instruction manual.
Prior to using the product make yourself familiar with it. Read the instruction manual carefully.

Reference to Further Documentation

Observe laws, standards, and directives applicable to the intended use and the operating location.
The corresponding datasheets, manuals, declarations of conformity, EUtype examination certificates, certificates, and control drawings if applicable supplement this document. You can find this information under www.pepperl- fuchs.com.
For specific device information such as the year of construction, scan the QR code on the device. As an alternative, enter the serial number in the serial number search at www.pepperl-fuchs.com.

Intended Use

The device is only approved for appropriate and intended use. Ignoring these instructions will void any warranty and absolve the manufacturer from any liability.
The device is used in control and instrumentation technology (C&I technology) for the galvanic isolation of signals such as 20 mA and 10 V standard signals or alternatively for adapting or standardizing signals.
The device has intrinsically safe circuits that are used for operating intrinsically safe field devices in hazardous areas.
Use the device only within the specified ambient and operating conditions. The device is designed for mounting on a 35 mm DIN mounting rail according to EN 60715.
Only use the device stationary.
The device is an associated apparatus according to IEC/EN 60079-11.
The device is an electrical apparatus for hazardous areas of Zone 2.

Improper Use

Protection of the personnel and the plant is not ensured if the device is not used according to its intended use.
The device is not suitable for isolating signals in power installations unless this is noted separately in the corresponding datasheet.

Mounting and Installation

Do not mount a damaged or polluted device.
Mount the device in a way that the device is protected against mechanical hazard. Mount the device in a surrounding enclosure for example.
Do not mount the device in the dust hazardous area.
The device fulfills a degree of protection IP20 according to IEC/EN 60529.
The device must be installed and operated only in a controlled environment that ensures a pollution degree 2 (or better) according to IEC/EN 60664-1.
If used in areas with higher pollution degree, the device needs to be protected accordingly.
The device must be installed and operated only in an environment of overvoltage category II (or better) according to IEC/EN 60664-1.
The device may be installed in a corrosive atmosphere according to ISAS71.04-1985, severity level G3.
Only connect supplies that provide protection against electric shock to power feed modules (e. g. SELV or PELV).
Observe the installation instructions according to IEC/EN 60079-14.
If you are using the Power Rail, supply the Power Rail only via the corresponding power feed modules or power supplies. Do not supply the Power Rail via isolators.
Requirements for Cables and Connection Lines
Observe the permissible core cross section of the conductor.
When using stranded conductors, crimp wire end ferrules on the conductor ends.
Use only one conductor per terminal.
When installing the conductors the insulation must reach up to the terminal.
Observe the tightening torque of the terminal screws.
Requirements for Usage as Associated Apparatus
If circuits with type of protection Ex i are operated with non-intrinsically safe circuits, they must no longer be used as circuits with type of protection Ex i.
Intrinsically safe circuits of associated apparatus can be led into hazardous areas. Observe the compliance of the separation distances to all non- intrinsically safe circuits according to IEC/EN 60079-14.
Observe the compliance of the separation distances between two adjacent intrinsically safe circuits according to IEC/EN 60079-14.
Observe the maximum values of the device, when connecting the device to intrinsically safe apparatus.
When connecting intrinsically safe devices with intrinsically safe circuits of associated apparatus, observe the maximum peak values with regard to explosion protection (verification of intrinsic safety). Observe the standards IEC/EN 60079-14 or IEC/EN 60079-25.
If more channels of one device are connected in parallel, ensure the parallel connection is made directly at the terminals of the device. When verifying the intrinsic safety, observe the maximum values for the parallel connection.
Requirements for Equipment Protection Level Gc
The device must be installed and operated only in surrounding enclosures that

  • comply with the requirements for surrounding enclosures according to IEC/EN 60079-0,
  • are rated with the degree of protection IP54 according to IEC/EN 60529.

Connection or disconnection of energized non-intrinsically safe circuits is only permitted in the absence of a potentially explosive atmosphere.
Provide a transient protection. Ensure that the peak value of the transient protection does not exceed 140 % of the rated voltage.
Only use the programming socket in the absence of a potentially explosive atmosphere.

Operation, Maintenance, Repair

Do not repair, modify, or manipulate the device.
If there is a defect, always replace the device with an original device.
Requirements for Equipment Protection Level Gc
Connection or disconnection of energized non-intrinsically safe circuits is only permitted in the absence of a potentially explosive atmosphere.
Only use the programming socket in the absence of a potentially explosive atmosphere.

Delivery, Transport, Disposal

Check the packaging and contents for damage.
Check if you have received every item and if the items received are the ones you ordered.
Always store and transport the device in the original packaging.
Store the device in a clean and dry environment. The permitted ambient conditions must be considered, see datasheet.
The device, built-in components, packaging, and any batteries contained within must be disposed in compliance with the applicable laws and guidelines of the respective country.

DOCT-5471A / 2023-01PEPPERL FUCHS logo

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Pepperl Fuchs User Manuals

Related Manuals