Pepperl Fuchs FB4202B2 HART Output Isolator Instruction Manual
- June 9, 2024
- Pepperl Fuchs
Table of Contents
BPepperl Fuchs FB4202B2 HART Output Isolator Instruction Manual
Features
- 1-channel
- Output Ex ia
- Installation in suitable enclosures in Zone 1
- Module can be exchanged under voltage (hot swap)
- Analog output module for 0/4 mA … 20 mA
- HART communication via field bus or service bus
- Simulation mode for service operations (forcing)
- Line fault detection (LFD)
- Permanently self-monitoring
Function
The device drives positioners, proportional valves, I/P converters, or local
indicators.
Open and short-circuit line faults are detected.
The output is galvanically isolated from the bus and the power supply.
Connection
Technical Data
Slots
- Occupied slots 1
Supply
- Connection: backplane bus
- Rated voltage: Ur 12 V DC , only in connection with the power supplies FB92**
- Power dissipation: 0.8 W
- Power consumption: 0.95 W
Internal bus
- Connection: backplane bus
- Interface: manufacturer-specific bus to standard com unit
Analog output
- Number of channels: 1
Suitable field devices
- Field device: Proportional Valve
- Field device [2]: I/P converters
- Field device [3]: on-site display
- Connection: channel I: 2/3+, 4/5-
- Current: 0 … 25 mA short-circuit protected
- Line fault detection: can be switched on/off for each channel via configuration tool , configurable via configuration tool
- Short-circuit: No
- Open-circuit: deviation of preset output value > 0.5 mA
- Load: 750 Ω max.
- HART communication: yes
- HART secondary variable: MODBUS: yes; all other bus systems: no
- Watchdog: within 0.5 s the device goes in safe state, e.g. after loss of communication
Transfer characteristics
Deviation
- After calibration: 0.1 % of the signal range at 20 °C (68 °F)
- Influence of ambient temperature: 0.1 %/10 K of the signal range
- Refresh time: 100 ms
Indicators/settings
-
LED indication:
Power LED (P) green: supply
Diagnostic LED (I) red: module fault , red flashing: communication error , white: fixed parameter set (parameters from com unit are ignored) , white flashing: requests parameters from com unit
Status LED (1) red: line fault (lead breakage or short circuit) -
Coding: optional mechanical coding via front socket
Directive conformity
- Electromagnetic compatibility
- Directive 2014/30/EU: EN 61326-1:2013
Conformity
- Electromagnetic compatibility: NE 21:2007
- Degree of protection: IEC 60529:2000
- Environmental test: EN 60068-2-14:2009
- Shock resistance: EN 60068-2-27:2009
- Vibration resistance: EN 60068-2-6:2008
- Damaging gas: EN 60068-2-42:2003
- Relative humidity: EN 60068-2-78:2001
Ambient conditions
-
Ambient temperature: -20 … 60 °C (-4 … 140 °F)
-
Storage temperature: -25 … 85 °C (-13 … 185 °F)
-
Relative humidity: 95 % non-condensing
-
Shock resistance: shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18
-
Vibration resistance:
frequency range 10 … 150 Hz; transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g; 10 cycles frequency range 5 … 100 Hz; transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g; 90 minutes at each resonance -
Damaging gas: designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3
Mechanical specifications
- Degree of protection: IP20 (module) , a separate housing is required acc. to the system description
- Connection: removable front connector with screw flange (accessory) wiring connection via spring terminals (0.14 … 1.5 mm2 ) or screw terminals (0.08 … 1.5 mm2)
- Mass: approx. 350 g
- Dimensions: 28 x 107 x 132 mm (1.1 x 4.2 x 5.2 inch)
Data for application in connection with hazardous areas
- EU-type examination certificate: BVS 12 ATEX E 015 X
- Marking
1 II 2(1) G Ex d [ia Ga] IIC T4 Gb
1 II (1) D [Ex ia Da] IIIC
Output
- Voltage: Uo 27 V
- Current: Io 87 mA
- Power: Po 575 mW (linear characteristic)
Galvanic isolation
- Output/power supply, internal bus: safe electrical isolation acc. to EN 60079-11:2007 , voltage peak value 375 V
Directive conformity
- Directive 2014/34/EU
EN IEC 60079-0:2018+AC:2020
EN 60079-1:2014
EN 60079-11:2012
International approvals
- ATEX approval: BVS 12 ATEX E 015 X
General information
-
System information
The module has to be mounted in appropriate backplanes and housings (FB92**) in Zone 1, 2, 21, 22 or outside hazardous areas (gas or dust). Here, observe the corresponding EC-type examination certificate. -
Supplementary information
EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.
Assembly
Refer to “General Notes Relating to Pepperl+Fuchs Product Information”
Pepperl+Fuchs Group
www.pepperl-fuchs.com
USA: +1 330 486 0002
pa-info@us.pepperl-fuchs.com
Germany: +49 621 776 2222
pa-info@de.pepperl-fuchs.com
Singapore: +65 6779 9091
pa-info@sg.pepperl-fuchs.com