PEPPERL FUCHS KFD2-UFC-Ex1.D Frequency Converter with Trip Values Instruction Manual

June 4, 2024
Pepperl Fuchs

PEPPERL FUCHS KFD2-UFC-Ex1.D Frequency Converter with Trip Values

PEPPERL FUCHS KFD2-UFC-Ex1.D Frequency Converter with Trip Values product-
img..

Frequency Converter with Trip Values

KFD2-UFC-Ex1.D

  • 1-channel isolated barrier
  • 24 V DC supply (Power Rail)
  • Input for NAMUR sensors or dry contacts
  • Input frequency 1 MHz … 5 kHz
  • Current output 0/4 mA … 20 mA
  • Relay contact and transistor output
  • Start-up override
  • Line fault detection (LFD)
  • Up to SIL 2 acc. to IEC 61508/IEC 61511

Function

  • This isolated barrier is used for intrinsic safety applications.
  • The device is a universal frequency converter that changes a digital input signal into a proportional free adjustable 0/4 mA … 20 mA analog output signal and functions as a switch amplifier and a trip alarm.
  • The functions of the switch outputs (2 relay outputs and 1 potential free transistor output) are easily adjustable [trip value display (min/max alarm), serially switched output, pulse divider output, error signal output].
  • The device is easily configured by the use of keypad or with the PACTware configuration software.
  • A fault is signalized by LEDs acc. to NAMUR NE44 and a separate collective error message output.
  • For additional information, refer to the manual and www.pepperl-fuchs.com.

Connection

PEPPERL FUCHS KFD2-UFC-Ex1.D Frequency Converter with Trip
Values fig \(1\)

Technical Data

General specifications

Signal type Digital Input
Functional safety related parameters
Safety Integrity Level (SIL) SIL 2
Supply
Connection terminals 23+, 24- or power feed module/Power Rail
Rated voltage| Ur| 20 … 30 V DC
Rated current| Ir| approx. 100 mA
Power dissipation/power consumption|  | ≤ 2 W / 2.2 W
Interface

Programming interface|  | programming socket
Input
Connection side|  | field side
Connection|  | Input I: intrinsically safe: terminals 1+, 3-

Input II: non-intrinsically safe: terminals 13+, 14-

Input I sensor acc. to EN 60947-5-6 (NAMUR) or mechanical contact
Pulse duration                                                              > 50 µs
Input frequency|  | 0.001 … 5000 Hz
Line fault detection|  | breakage I ≤ 0.15 mA; short-circuit I > 6.5 mA
Input II startup override: 1 … 1000 s, adjustable in steps of 1 s
Active/Passive                                                            I > 4 mA (for min. 100 ms) / I < 1.5 mA
Open circuit voltage/short-circuit current|  | 18 V / 5 mA
Output
Connection side|  | control side
Connection|  | output I: terminals 10, 11, 12

output II: terminals 16, 17, 18

outout III: terminasl 19+, 20-

output IV: terminals 8+, 7-

Output I, II signal, relay
Contact loading                                                         253 V AC / 2 A / cos φ ≥ 0.7 ; 40 V DC / 2 A
Mechanical life|  | 5 x 107 switching cycles
Energized/De-energized delay|  | approx. 20 ms / approx. 20 ms
Output III electronic output, passive
Contact loading                                                         40 V DC
Signal level|  | 1-signal: (L+) – 2.5 V (50 mA, short-circuit/overload proof) 0-signal: switched off (off-state current ≤ 10 µA)
Output IV|  | analog
Current range                                                               0 … 20 mA or 4 … 20 mA
Open loop voltage                                                     max. 24 V DC
Load|  | max. 650 Ω
Fault signal|  | downscale I ≤ 3.6 mA , upscale ≥ 21.5 mA (acc. NAMUR NE43)
Collective error message                                             Power Rail
Transfer characteristics
Input I|  |
Measurement range|  | 0.001 … 5000 Hz
Resolution 0.1 % of the measurement value , ≥ 0.001 Hz
Accuracy 0.1 % of the measurement value , > 0.001 Hz
Measuring time|  | < 100 ms
Influence of ambient temperature|  | 0.003 %/K (30 ppm)
Output I, II
Response delay                                                            ≤ 200 ms
Output IV|  |
Resolution|  | < 10 µA
Accuracy                                                                     < 20 µA
Influence of ambient temperature                              0.005 %/K (50 ppm)
Galvanic isolation
Input I/other circuits reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Output I, II/other circuits|  | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Mutual output I, II, III|  | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Output III/power supply and collective error              basic insulation according to IEC/EN 61010-1, rated insulation voltage 50 Veff
Output III/start-up override basic insulation according to IEC/EN 61010-1, rated insulation voltage 50 Veff
Output III/IV|  | basic insulation according to IEC/EN 61010-1, rated insulation voltage 50 Veff
Output IV/power supply and collective error|  | functional insulation acc. to IEC 62103, rated insulation voltage 50 Veff
Start-up override/power supply and collective error|  | functional insulation acc. to IEC 62103, rated insulation voltage 50 Veff
---|---|---
Interface/power supply and collective error|  | functional insulation acc. to IEC 62103, rated insulation voltage 50 Veff
Interface/output III basic insulation according to IEC/EN 61010-1, rated insulation voltage 50 Veff
Indicators/settings
Display elements|  | LEDs , display
Control elements|  | Control panel
Configuration via operating buttons

via PACTware

Labeling space for labeling at the front
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EU|  | EN 61326-1:2013 (industrial locations)
Low voltage|  |
Directive 2014/35/EU                                                    EN 61010-1:2010
Conformity
Electromagnetic compatibility|  | NE 21:2006
Degree of protection|  | IEC 60529:2001
Input EN 60947-5-6:2000
Ambient conditions
Ambient temperature|  | -20 … 60 °C (-4 … 140 °F)
Mechanical specifications
Degree of protection|  | IP20
Connection|  | screw terminals
Mass 300 g
Dimensions 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) (W x H x D) , housing type C2
Mounting|  | on 35 mm DIN mounting rail acc. to EN 60715:2001
Data for application in connection with hazardous areas
EU-type examination certificate|  | TÜV 99 ATEX 1471
Marking|  | 1 II (1)G [Ex ia Ga] IIC

1 II (1)D [Ex ia Da] IIIC

1 I (M1) [Ex ia Ma] I

Supply
Maximum safe voltage                                        Um        40 V DC (Attention! Um is no rated voltage.)
Input I|  | terminals 1+, 3-: Ex ia
Voltage Uo|  | 10.1 V
Current Io 13.5 mA
Power Po                                                                    34 mW (linear characteristic)
Input II|  | terminals 13+, 14- non-intrinsically safe
Maximum safe voltage Um|  | 40 V (Attention! The rated voltage can be lower.)
Output I, II terminals 10, 11, 12; 16, 17, 18 non-intrinsically safe
Maximum safe voltage                                        Um        253 V (Attention! The rated voltage can be lower.)
Contact loading|  | 253 V AC/2 A/cos φ > 0.7; 40 V DC/2 A resistive load
Output III|  | terminals 19+, 20- non-intrinsically safe
Maximum safe voltage Um                             Um        40 V (Attention! Um is no rated voltage.)
Output IV terminals 8+, 7- non-intrinsically safe
Maximum safe voltage| Um| 40 V DC (Attention! Um is no rated voltage.)
Interface|  | RS 232
Maximum safe voltage                                        Um        40 V (Attention! Um is no rated voltage.)
Certificate TÜV 02 ATEX 1885 X
Marking|  | 1 II 3G Ex nA nC IIC T4 Gc
Output I, II|  |
Contact loading                                                         50 V AC/2 A/cos φ > 0.7; 40 V DC/2 A resistive load
Galvanic isolation
Input I/other circuits|  | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
---|---|---
Directive conformity|  |
Directive 2014/34/EU                                                    EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010
International approvals
FM approval|  |
Control drawing|  | 16-538FM-12
UL approval E223772
IECEx approval
IECEx certificate|  | IECEx TUN 04.0007 IECEx TSA 18.0007X
IECEx marking|  | [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I Ex ec nC IIC T4 Gc
General information
Supplementary information                                          Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.

Assembly

PEPPERL FUCHS KFD2-UFC-Ex1.D Frequency Converter with Trip
Values fig \(2\)

Matching System Components

PEPPERL FUCHS KFD2-UFC-Ex1.D Frequency
Converter with Trip Values fig \(3\)PEPPERL FUCHS KFD2-UFC-Ex1.D Frequency
Converter with Trip Values fig \(4\)

Accessories

PEPPERL FUCHS KFD2-UFC-Ex1.D Frequency Converter with Trip
Values fig \(5\)

Characteristic Curve

Maximum Switching Power of Output ContactsPEPPERL FUCHS KFD2-UFC-Ex1.D
Frequency Converter with Trip Values fig \(6\)