PEPPERL FUCHS KFD2-UFC-Ex1.D Frequency Converter with Trip Values Instruction Manual
- June 4, 2024
- Pepperl Fuchs
Table of Contents
PEPPERL FUCHS KFD2-UFC-Ex1.D Frequency Converter with Trip Values
Frequency Converter with Trip Values
KFD2-UFC-Ex1.D
- 1-channel isolated barrier
- 24 V DC supply (Power Rail)
- Input for NAMUR sensors or dry contacts
- Input frequency 1 MHz … 5 kHz
- Current output 0/4 mA … 20 mA
- Relay contact and transistor output
- Start-up override
- Line fault detection (LFD)
- Up to SIL 2 acc. to IEC 61508/IEC 61511
Function
- This isolated barrier is used for intrinsic safety applications.
- The device is a universal frequency converter that changes a digital input signal into a proportional free adjustable 0/4 mA … 20 mA analog output signal and functions as a switch amplifier and a trip alarm.
- The functions of the switch outputs (2 relay outputs and 1 potential free transistor output) are easily adjustable [trip value display (min/max alarm), serially switched output, pulse divider output, error signal output].
- The device is easily configured by the use of keypad or with the PACTware configuration software.
- A fault is signalized by LEDs acc. to NAMUR NE44 and a separate collective error message output.
- For additional information, refer to the manual and www.pepperl-fuchs.com.
Connection
Technical Data
General specifications
Signal type
Digital Input
Functional safety related parameters
Safety Integrity Level (SIL)
SIL 2
Supply
Connection
terminals 23+, 24- or power feed module/Power Rail
Rated voltage| Ur| 20 … 30 V DC
Rated current| Ir| approx. 100 mA
Power dissipation/power consumption| | ≤ 2 W / 2.2 W
Interface
Programming interface| | programming socket
Input
Connection side| | field side
Connection| | Input I: intrinsically safe: terminals 1+, 3-
Input II: non-intrinsically safe: terminals 13+, 14-
Input I
sensor acc. to EN 60947-5-6 (NAMUR) or mechanical contact
Pulse duration >
50 µs
Input frequency| | 0.001 … 5000 Hz
Line fault detection| | breakage I ≤ 0.15 mA; short-circuit I > 6.5 mA
Input II
startup override: 1 … 1000 s, adjustable in steps of 1 s
Active/Passive I >
4 mA (for min. 100 ms) / I < 1.5 mA
Open circuit voltage/short-circuit current| | 18 V / 5 mA
Output
Connection side| | control side
Connection| | output I: terminals 10, 11, 12
output II: terminals 16, 17, 18
outout III: terminasl 19+, 20-
output IV: terminals 8+, 7-
Output I, II
signal, relay
Contact loading 253 V
AC / 2 A / cos φ ≥ 0.7 ; 40 V DC / 2 A
Mechanical life| | 5 x 107 switching cycles
Energized/De-energized delay| | approx. 20 ms / approx. 20 ms
Output III
electronic output, passive
Contact loading 40 V
DC
Signal level| | 1-signal: (L+) – 2.5 V (50 mA, short-circuit/overload proof)
0-signal: switched off (off-state current ≤ 10 µA)
Output IV| | analog
Current range 0
… 20 mA or 4 … 20 mA
Open loop voltage max. 24
V DC
Load| | max. 650 Ω
Fault signal| | downscale I ≤ 3.6 mA , upscale ≥ 21.5 mA (acc. NAMUR NE43)
Collective error message Power
Rail
Transfer characteristics
Input I| |
Measurement range| | 0.001 … 5000 Hz
Resolution
0.1 % of the measurement value , ≥ 0.001 Hz
Accuracy
0.1 % of the measurement value , > 0.001 Hz
Measuring time| | < 100 ms
Influence of ambient temperature| | 0.003 %/K (30 ppm)
Output I, II
Response delay ≤
200 ms
Output IV| |
Resolution| | < 10 µA
Accuracy <
20 µA
Influence of ambient temperature 0.005 %/K (50
ppm)
Galvanic isolation
Input I/other circuits
reinforced insulation according to IEC/EN 61010-1, rated insulation voltage
300 Veff
Output I, II/other circuits| | reinforced insulation according to IEC/EN
61010-1, rated insulation voltage 300 Veff
Mutual output I, II, III| | reinforced insulation according to IEC/EN
61010-1, rated insulation voltage 300 Veff
Output III/power supply and collective error basic insulation
according to IEC/EN 61010-1, rated insulation voltage 50 Veff
Output III/start-up override
basic insulation according to IEC/EN 61010-1, rated insulation voltage 50 Veff
Output III/IV| | basic insulation according to IEC/EN 61010-1, rated
insulation voltage 50 Veff
Output IV/power supply and collective error| | functional insulation acc. to
IEC 62103, rated insulation voltage 50 Veff
Start-up override/power supply and collective error| | functional insulation
acc. to IEC 62103, rated insulation voltage 50 Veff
---|---|---
Interface/power supply and collective error| | functional insulation acc. to
IEC 62103, rated insulation voltage 50 Veff
Interface/output III
basic insulation according to IEC/EN 61010-1, rated insulation voltage 50 Veff
Indicators/settings
Display elements| | LEDs , display
Control elements| | Control panel
Configuration
via operating buttons
via PACTware
Labeling
space for labeling at the front
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EU| | EN 61326-1:2013 (industrial locations)
Low voltage| |
Directive 2014/35/EU EN
61010-1:2010
Conformity
Electromagnetic compatibility| | NE 21:2006
Degree of protection| | IEC 60529:2001
Input
EN 60947-5-6:2000
Ambient conditions
Ambient temperature| | -20 … 60 °C (-4 … 140 °F)
Mechanical specifications
Degree of protection| | IP20
Connection| | screw terminals
Mass
300 g
Dimensions
40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) (W x H x D) , housing type C2
Mounting| | on 35 mm DIN mounting rail acc. to EN 60715:2001
Data for application in connection with hazardous areas
EU-type examination certificate| | TÜV 99 ATEX 1471
Marking| | 1 II (1)G [Ex ia Ga] IIC
1 II (1)D [Ex ia Da] IIIC
1 I (M1) [Ex ia Ma] I
Supply
Maximum safe voltage Um 40 V DC
(Attention! Um is no rated voltage.)
Input I| | terminals 1+, 3-: Ex ia
Voltage Uo| | 10.1 V
Current Io
13.5 mA
Power Po 34
mW (linear characteristic)
Input II| | terminals 13+, 14- non-intrinsically safe
Maximum safe voltage Um| | 40 V (Attention! The rated voltage can be lower.)
Output I, II
terminals 10, 11, 12; 16, 17, 18 non-intrinsically safe
Maximum safe voltage Um 253 V
(Attention! The rated voltage can be lower.)
Contact loading| | 253 V AC/2 A/cos φ > 0.7; 40 V DC/2 A resistive load
Output III| | terminals 19+, 20- non-intrinsically safe
Maximum safe voltage Um Um 40 V (Attention!
Um is no rated voltage.)
Output IV
terminals 8+, 7- non-intrinsically safe
Maximum safe voltage| Um| 40 V DC (Attention! Um is no rated voltage.)
Interface| | RS 232
Maximum safe voltage Um 40 V
(Attention! Um is no rated voltage.)
Certificate
TÜV 02 ATEX 1885 X
Marking| | 1 II 3G Ex nA nC IIC T4 Gc
Output I, II| |
Contact loading 50 V
AC/2 A/cos φ > 0.7; 40 V DC/2 A resistive load
Galvanic isolation
Input I/other circuits| | safe electrical isolation acc. to IEC/EN 60079-11,
voltage peak value 375 V
---|---|---
Directive conformity| |
Directive 2014/34/EU EN
60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010
International approvals
FM approval| |
Control drawing| | 16-538FM-12
UL approval
E223772
IECEx approval
IECEx certificate| | IECEx TUN 04.0007 IECEx TSA 18.0007X
IECEx marking| | [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I Ex ec nC IIC
T4 Gc
General information
Supplementary information Observe the
certificates, declarations of conformity, instruction manuals, and manuals
where applicable. For information see www.pepperl-fuchs.com.
Assembly
Matching System Components
Accessories
Characteristic Curve
Maximum Switching Power of Output Contacts
Refer to “General Notes Relating to Pepperl+Fuchs Product Information”.
- Pepperl+Fuchs Group www.pepperl-fuchs.com
- USA: +1 330 486 0002 pa-info@us.pepperl-fuchs.com
- Germany: +49 621 776 2222 pa-info@de.pepperl-fuchs.com
- Singapore: +65 6779 9091 pa-info@sg.pepperl-fuchs.com
- Release date: 2022-01-10
- Date of issue: 2022-01-10
Read User Manual Online (PDF format)