VIESSMANN VITODENS 222-F Gas Condensing Boiler Instruction Manual

June 13, 2024
VIESSMANN

VITODENS 222-F Gas Condensing Boiler

Product Information

The Vitodens 222-F is a gas condensing storage combi boiler with
a 3.5 inch black/white screen. It has a power range of 1.9 to 32 kW
and is available in both natural gas and LPG versions. The product
is manufactured by VIESMANN and the model number is 5593275 GB. The
user manual is valid until March 2023.

Product Usage Instructions

Safety Instructions

  • Follow these safety instructions closely to prevent accidents
    and material losses.

  • Danger: This symbol warns against the risk of injury.

  • Please note: This symbol warns against the risk of material
    losses and environmental pollution.

  • Details identified by the word “Note” contain additional
    information.

Target Group

These instructions are exclusively intended for qualified
contractors. Work on gas installations may only be carried out by a
registered gas fitter. Work on electrical equipment may only be
carried out by a qualified electrician. The system must be
commissioned by the system installer or a qualified person
authorized by the installer.

Regulations to be Observed

When working on the system, the following regulations must be
observed:

  • National installation regulations
  • Statutory regulations for the prevention of accidents
  • Statutory regulations for environmental protection
  • Codes of practice of the relevant trade associations
  • Relevant country-specific safety regulations

Safety Instructions for Working on the System

When working on the system, please follow these safety
instructions:

  • Where gas is used as the fuel, close the main gas shut-off
    valve and safeguard it against unintentional reopening.

  • Isolate the system from the power supply by removing the
    separate fuse or using a mains isolator, and ensure it is no longer
    live.

  • Safeguard the system against reconnection.

  • Wear suitable personal protective equipment when carrying out
    any work.

Safety Instructions (Continued)

Additional safety instructions for working on the system:

  • Danger: Hot surfaces and fluids can lead to burns or scalding.
    Before maintenance and service work, switch OFF the appliance and
    let it cool down. Never touch hot surfaces on the boiler, burner,
    flue system, or pipework.

  • Please note: Spare and wearing parts that have not been tested
    together with the system can compromise its function. Installing
    non-authorized components and making non-approved modifications or
    conversions can compromise safety and may invalidate the
    warranty.

  • Please note: Electronic assemblies can be damaged by
    electrostatic discharge. Prior to commencing work, touch earthed
    objects such as heating or water pipes to discharge static
    loads.

  • Please note: Repairing components that fulfill a safety
    function can compromise the safe operation of the system. Replace
    faulty components only with genuine Viessmann spare parts.

Safety Instructions for Operating the System

If you smell gas:

  • Danger: Escaping gas can lead to explosions which may result in
    serious injury.

  • Do not smoke. Prevent naked flames and sparks.

  • Never switch lights or electrical appliances on or off.

  • Close the gas shut-off valve.

  • Open windows and doors.

  • Evacuate any people from the danger zone.

  • Notify your gas or electricity supply utility from outside the
    building.

  • Have the power supply to the building shut off from a safe
    place (outside the building).

Installation and service instructions
for contractors
Vitodens 222-F Type B2TF, 1.9 to 32 kW Gas condensing storage combi boiler with 3.5 inch black/white screen Natural gas and LPG version

VIESMANN

VITODENS 222-F

5593275 GB 3/2023

Please keep safe.

Safety instructions Safety instructions

Please follow these safety instructions closely to prevent accidents and material losses.

Safety instructions explained
Danger This symbol warns against the risk of injury.
! Please note This symbol warns against the risk of material losses and environmental pollution.

Note Details identified by the word “Note” contain additional information.

Target group
These instructions are exclusively intended for qualified contractors.

Work on gas installations may only be carried out by a registered gas fitter.
Work on electrical equipment may only be carried out by a qualified electrician.
The system must be commissioned by the system installer or a qualified person authorised by the installer.

Regulations to be observed

National installation regulations Statutory regulations for the prevention
of accidents Statutory regulations for environmental
protection

Codes of practice of the relevant trade associations
Relevant country-specific safety regulations

Safety instructions for working on the system

Working on the system
Where gas is used as the fuel, close the main gas shut-off valve and safeguard it against unintentional reopening.
Isolate the system from the power supply, e.g. by removing the separate fuse or by means of a mains isolator, and check that it is no longer live.

Safeguard the system against reconnection.
Wear suitable personal protective equipment when carrying out any work.

5593275

2

Safety instructions (cont.)

Safety instructions

Danger

Auxiliary components, spare and

Hot surfaces and fluids can lead to wearing parts

burns or scalding.
! Before maintenance and service work, switch OFF the appliance and let it cool down. Never touch hot surfaces on the
boiler, burner, flue system or pipework.

Please note Spare and wearing parts that have not been tested together with the system can compromise its function. Installing non-authorised components and making non-approved modifications or conversions can

! Please note Electronic assemblies can be dam-

compromise safety and may invalidate our warranty.

aged by electrostatic discharge.

For replacements, use only original

Prior to commencing work, touch

spare parts supplied or approved by

earthed objects such as heating or

Viessmann.

water pipes to discharge static

loads.

Repair work

! Please note Repairing components that fulfil a safety function can compromise the safe operation of the system. Replace faulty components only with genuine Viessmann spare parts.

5593275

3

Safety instructions Safety instructions (cont.)

Safety instructions for operating the system

If you smell gas

Condensate

Danger Escaping gas can lead to explosions which may result in serious injury. Do not smoke. Prevent naked
flames and sparks. Never switch lights or electrical appliances on or off. Close the gas shut-off valve. Open windows and doors. Evacuate any people from the danger zone. Notify your gas or electricity supply utility from outside the building. Have the power supply to the building shut off from a safe place (outside the building).
If you smell flue gas
Danger Flue gas can lead to life threatening poisoning. Shut down the heating system. Ventilate the installation site. Close doors to living spaces to
prevent flue gases from spreading.
What to do if water escapes from the appliance
Danger If water escapes from the appliance there is a risk of electrocution. Switch OFF the heating system at the external isolator (e.g. fuse box, domestic distribution board).
Danger If water escapes from the appliance there is a risk of scalding. Never touch hot heating water.

Danger Contact with condensate can be harmful to health. Never let condensate touch your skin or eyes and do not swallow it.
Flue systems and combustion air
Ensure that flue systems are clear and cannot be sealed, for instance due to accumulation of condensate or other external causes. Ensure an adequate supply of combustion air. Inform system users that subsequent modifications to the building characteristics are not permissible (e.g. cable/pipework routing, cladding or partitions).
Danger Leaking or blocked flue systems, or an inadequate supply of combustion air can cause life threatening poisoning from carbon monoxide in the flue gas. Ensure the flue system is in good working order. Vents for supplying combustion air must be non-sealable.
Extractors
Operating appliances that extract air to the outside (extractor hoods, extractors, air conditioning units, central vacuum cleaning systems, etc.) can create negative pressure. If the boiler is operated at the same time, this can lead to a reverse flow of flue gas.

5593275

4

Safety instructions (cont.)
Danger The simultaneous operation of the boiler and appliances that exhausts air to the outside can result in life threatening poisoning due to a reverse flow of flue gas. Fit an interlock circuit or take suitable steps to ensure an adequate supply of combustion air.

Safety instructions

5593275

5

Index Index

1. Information
2. Preparing for installation 3. Installation sequence
4. Commissioning, inspection, maintenance
5. System configuration (parameters)
6. Diagnosis and service checks
7. Troubleshooting 6

Disposal of packaging …………………………………………………………………. 8 Symbols ……………………………………………………………………………………. 8 Intended use ……………………………………………………………………………… 8 Product information …………………………………………………………………….. 9 Vitodens 222-F, type B2TF ……………………………………………………….. 9 System examples ………………………………………………………………………. 9 Maintenance parts and spare parts ………………………………………………. 9 Viessmann Partnershop …………………………………………………………… 9 Viessmann spare part app ………………………………………………………… 9
Handling ……………………………………………………………………………………. 11 Siting in recesses ……………………………………………………………………….. 11 Relocating the ON/OFF switch and electrical connections (if necessary) …………………………………………………………………………………………. 11 Preparing for boiler installation …………………………………………………….. 12 Safety assembly to DIN 1988 and EN 806 ………………………………….. 15
Siting the boiler ………………………………………………………………………….. 16 Type plate ………………………………………………………………………………. 16 Removing the front panel …………………………………………………………….. 17 Connections on the heating water and DHW sides …………………………. 18 DHW circulation connection (potable water) ……………………………….. 18 Filling the trap with water …………………………………………………………….. 18 Flue gas connection ……………………………………………………………………. 19 Gas connection ………………………………………………………………………….. 20 Electrical connections …………………………………………………………………. 21 Opening the HMU wiring chamber …………………………………………….. 21 On-site connections on the heat management unit ………………………. 22 Outside temperature sensor ! …………………………………………………. 23 Connecting low loss header sensor ) ………………………………………. 23 Connecting the circulation pump to P2 ……………………………………….. 24 Floating switching contact connection ………………………………………… 24 Checking the CAN bus terminator switch setting …………………………. 24 Power supply for accessories at plug lH/aBH (230 V ~) ………………… 25 Power supply fÖ ……………………………………………………………………… 27 WiFi operational reliability and system requirements ……………………. 27 Routing connecting cables/leads ……………………………………………….. 28 Closing the wiring chamber …………………………………………………………. 28 Fitting the front panel and programming unit ………………………………….. 29
Steps – commissioning, inspection and maintenance ………………………. 30
Calling up parameters …………………………………………………………………. 64 General …………………………………………………………………………………….. 64 Boiler ………………………………………………………………………………………… 66 DHW ………………………………………………………………………………………… 68 Heating circuit 1, Heating circuit 2, Heating circuit 3, Heating circuit 4 .. 71 Energy saving functions (setting only via software tool) ………………… 77 Frost protection configuration (setting only via software tool) ………… 79 Subscriber numbers of connected extensions ………………………………… 80
Service menu …………………………………………………………………………….. 82 Calling up the service menu ……………………………………………………… 82 Diagnosis ………………………………………………………………………………….. 82 Checking operating data …………………………………………………………… 82 Checking outputs (actuator test) …………………………………………………… 83
Fault display on the programming unit …………………………………………… 85 Calling up fault messages ………………………………………………………… 85

5593275

Index (cont.)

Index

8. Function description
9. Connection and wiring diagram
10. Commissioning/service reports
11. Specification 12. Disposal 13. Ordering individual parts 14. Certificates 15. Keyword index

Acknowledging the fault display ………………………………………………… 85 Calling up acknowledged fault messages …………………………………… 85 Calling up fault messages from the fault memory (message history) . 86 Deleting the message list …………………………………………………………. 86 Overview of electronics modules ………………………………………………….. 87 Fault messages …………………………………………………………………………. 87 Further messages ………………………………………………………………………. 110 Service messages …………………………………………………………………… 110 Status messages …………………………………………………………………….. 110 Warning messages ………………………………………………………………….. 111 Information ……………………………………………………………………………… 111 Repairs …………………………………………………………………………………….. 112 Shutting down the boiler …………………………………………………………… 112 Draining the boiler on the heating water side ………………………………. 113 Status/checking/diagnosing the internal circulation pump ……………… 113 Checking the temperature sensors …………………………………………….. 115 Information on replacing the HMU heat management unit and
BCU burner control unit ……………………………………………………………. 117 Checking the plate heat exchanger ……………………………………………. 118 Removing the hydraulic unit and return pipe ……………………………….. 119 Replacing the power cable ……………………………………………………….. 120 Checking the fuse ……………………………………………………………………. 121
Control functions …………………………………………………………………………122 Heating mode …………………………………………………………………………. 122 Venting program ……………………………………………………………………… 122 Filling program ………………………………………………………………………… 122 Heating curve …………………………………………………………………………. 122 Screed drying …………………………………………………………………………. 124 Raising the reduced room temperature ………………………………………. 126 DHW heating …………………………………………………………………………….. 127 Heating the DHW loading cylinder from cold ……………………………….. 127 Reheating when DHW is drawn off ……………………………………………..127 Increased DHW hygiene ……………………………………………………………128 External heating circuit hook-up (if installed) ………………………………….. 128
HMU heat management unit …………………………………………………………129 BCU burner control unit ………………………………………………………………. 131
…………………………………………………………………………………………………. 132
Specification ……………………………………………………………………………… 133 Electronic combustion control unit ………………………………………………… 137
Final decommissioning and disposal …………………………………………….. 138
Ordering individual parts for accessories ………………………………………..139
Declaration of conformity …………………………………………………………….. 140 Manufacturer’s certificate according to the 1st BImSchV [Germany] …. 140
…………………………………………………………………………………………………. 141

5593275

7

Information

Information Disposal of packaging
Please dispose of packaging waste in line with statutory regulations.

Symbols

Symbol

Meaning
Reference to other document containing further information

Step in a diagram: The numbers correspond to the order in

which the steps are carried out.

Warning of material losses and environmental pollution

Live electrical area

Pay particular attention.

The steps in connection with commissioning, inspection and maintenance are found in the “Commissioning, inspection and maintenance” section and identified as follows:
Symbol Meaning Steps required during commissioning
Not required during commissioning
Steps required during inspection
Not required during inspection
Steps required during maintenance
Not required during maintenance

Component must audibly click into place. or
Acoustic signal
Fit new component. or
In conjunction with a tool: Clean the surface.
Dispose of component correctly.

Dispose of component at a suitable collec-
tion point. Do not dispose of component in domestic waste.

Intended use

The appliance is intended solely for installation and operation in sealed unvented heating systems that comply with EN 12828, with due attention paid to CECS 215-2017 and the associated installation, service and operating instructions. It is only designed for heating up heating water that is of potable water quality.
Intended use presupposes that a fixed installation in conjunction with permissible, system-specific components has been carried out.

The appliance is intended exclusively for domestic or semi-domestic use; even users who have not had any instruction are able to operate the appliance safely.
Commercial or industrial usage for a purpose other than heating the building or DHW shall be deemed inappropriate.
Any usage beyond this must be approved by the manufacturer in each individual case.

8

5593275

Information

Intended use (cont.)
Incorrect usage or operation of the appliance (e.g. the appliance being opened by the system user) is prohibited and will result in an exclusion of liability. Incorrect usage also occurs if the components in the heating system are modified from their intended use (e.g. if the flue gas and ventilation air paths are sealed).

Information

Product information

Vitodens 222-F, type B2TF
Gas condensing storage combi boiler with Inox-Radial heat exchanger and the following integrated components: Modulating MatriX Plus burner for natural gas and
LPG DHW loading cylinder, 100 l capacity Hydraulics with 3-way diverter valve and variable
speed high efficiency circulation pump Weather-compensated control unit Diaphragm expansion vessel (18 l capacity)

The selected gas category in the delivered condition and the associated nominal gas pressure are given on the boiler type plate. The type plate also shows the other gas types and pressures with which the boiler can be operated. A conversion within the stated natural gas groups is not required. For conversion to LPG (without conversion kit), see “Commissioning, inspection and maintenance”. The Vitodens 222-F may only be delivered to the countries specified on the type plate. For deliveries to other countries, approved contractors must arrange individual approval on their own initiative and in accordance with the law of the country in question.

System examples

System examples with hydraulic and electrical connection diagrams and function descriptions are available to help setting up the heating system.

Detailed information regarding system examples: www.viessmann-schemes.com

Maintenance parts and spare parts
Maintenance parts and spare parts can be identified and ordered directly online.
Viessmann Partnershop Login: https://shop.viessmann.com/

Viessmann spare part app www.viessmann.com/etapp
9

5593275

Information

Information Maintenance parts and spare parts (cont.)
10

5593275

5593275
Installation

Handling

!

Please note Prevent damage to the appliance during han-

dling.

Never set the appliance down on its front or

sides, or apply any load to these surfaces. If

possible, leave the boiler on the pallet during

handling.

Preparing for installation

Siting in recesses

In the delivered condition, the ON/OFF switch and the electrical connections are located on the left-hand side of the appliance. The condensate drain can be routed out of either the right-hand or left-hand side of the appliance.

When installing in recesses, ensure that accessibility is guaranteed (recommended wall clearance 100 mm). Otherwise relocate the ON/OFF switch and electrical connections. The ON/OFF switch can be relocated to the right-hand side or the top. The electrical connections can be relocated to the right-hand side.

Relocating the ON/OFF switch and electrical connections (if necessary)

82. 3.

5. 4.
Fig. 1
11

Installation
5593275

Preparing for installation Relocating the ON/OFF switch and electrical… (cont.)

Open the electrical wiring chamber of the HMU. Disconnect the cable of the ON/OFF switch and remove. See electrical connections.
1. Unclip the ON/OFF switch from the frame.
2. Remove the ON/OFF switch with the cable.
3. Clip the ON/OFF switch into the corresponding opening at the top or on the right-hand side. Reconnect the cable in the HMU wiring chamber and relieve strain.

4. Release plug of electrical connections by turning it a quarter turn.
5. Insert plug into the opening on the right-hand side and secure in place by turning it a quarter turn.
Note From 09/2021, the plug for the electrical connections is inside the appliance.

Preparing for boiler installation

Use a connection set ­ available as an accessory ­ to make the connections on the gas and water sides. The following overview shows sample connection sets for surface mounting, with connection to the top or side.

Preparing connections on site: Connection set installation instructions

Attaching accessories Before final siting, attach all of the accessories that are to be mounted from the back of the boiler (e.g. connection set). First fit the connection set for the DHW circulation pump.

Note Fit safety equipment in accordance with the national regulations.

!

Please note To prevent appliance damage,

connect all pipework free of load and torque

stress.

12

Preparing for boiler installation (cont.)

470 410 398
362

K 100

50

DE
F C
B A

A B
C F
D E

1056

1111

1221

1276

1440

1452

1488

1503

1563

Preparing for installation
50 Ø 100 Ø 60
G H 46

Installation

1400 1166

1001

946

600 735

330

220

D

55

E

50 206
595

A

B

F

C

67

600
Fig. 2
A Heating flow R ¾ B DHW R ½ C Gas connection R ½ D Cold water R ½ E Heating return R ¾ F DHW circulation R ½ (separate accessories) G Plug for electrical accessories
Note Depending on the version, the plug is inside the appliance.

H Condensate drain to the side K Area for electrical cables (on-site junction box)
Note All height dimensions have a tolerance of +15 mm on account of the adjustable feet.

13

5593275

Installation

20 >3°

Preparing for installation Preparing for boiler installation (cont.)
L
M N
Fig. 3

1. Prepare the connections on the heating water side. Thoroughly flush the heating system.

Note Should an additional expansion vessel be required on site, connect this vessel in the heating return.

2. Prepare the connections on the DHW side. Install the safety assembly (accessories or on-site provision) in accordance with EN 806 [or local regulations] in the cold water supply. See the following chapter. Recommendation: Install the safety valve above the DHW cylinder to protect it against contamination, scaling and high temperatures. c: According to W3 “Principles for creating potable water installations”, safety valves must be drained directly via a visible unrestricted drain or via a short outlet line to the drain network.

Note Do not connect the DHW cylinder safety valve to hose L. Do not change the position of hose L (used for ventilation).

3. Route condensate hose M to side opening H (see diagram on page 13). Connect condensate hose with a fall to the on-site waste water pipe or trap.

Note The on-site waste water pipe must have min.
Ø 40 mm to allow inflow with no risk of backing up. Keep the drainage route from the appliance as short as possible. Do not connect the drain hose directly to the onsite waste water pipe. To prevent bacterial contamination from the drain network, observe a minimum clearance of 20 mm (see diagram).

!

Please note The drain hose is used to route away any

hot water discharged from the safety valve.

Lay and secure the drain hose in a way that

prevents any risk of scalding.

Note Route the onward drain line inside the building as far as possible. If the onward drain line is routed outside the building: Use a min. Ø 30 mm line. Protect the line from frost. Keep the line as short as possible.

5593275

14

5593275
Installation

Preparing for boiler installation (cont.)

Preparing for installation

4. Prepare gas connection to TRGI [or local regulations].
5. Prepare the electrical connections. The appliance is delivered fitted with a power cable (approx. 1.5 m long). Power supply: 230 V, 50 Hz, fuse rating max. 16 A Note Connect the power cable to the electricity supply using a fixed connection. Accessory cables: 0.75 mm2 flexible PVC cable with required number of cores for external connections.
Note Route external pipes through guide N.

Safety assembly to DIN 1988 and EN 806

A B
D E F GH D

DHL M D N K

K
C O
Fig. 4
A Safety assembly to DIN 1988 and EN 806 (accessories for connection sets for flush mounting)
B Safety valve C Visible discharge pipe outlet point D Shut-off valve E Flow regulating valve (installation recommended) F Pressure gauge connector G Non- return valve

H Drain outlet K Cold water L Drinking water filter M Pressure reducer to DIN 1988-2, Dec. 1988 issue N Non-return valve/pipe separator O Cold water connection at connection set (accesso-
ries)

15

Installation sequence Siting the boiler

Installation
5593275

  1. Fig. 5

Type plate
Note The type plate is attached to cover panel A in the appliance. See page 42.
Additional type plate with access code (QR code) marked with “i”
The type plate of the heat generator contains extensive product information and an appliance-specific QR code marked with “i” for direct access to product-specific information and product registration on the internet. The QR code contains the credentials for the registration and product information portal, and the 16-digit serial number.
16

Attaching the additional type plate
1. Take the additional type plate from the documentation supplied with the boiler. Note The documentation with the additional type plate and QR code marked with “i” can be found on top of the appliance.

5593275
Installation

Siting the boiler (cont.)
2. In consultation with the system user, affix the additional type plate to the outside of the appliance. The additional type plate must be visible to the flue gas inspector. Affix another QR code to the installation and service instructions.
Removing the front panel

  1. Fig. 6

Installation sequence

17

Installation
5593275

Installation sequence Connections on the heating water and DHW sides

AB

CD E

E

A

D

B

C

C

B

D

A

E

Fig. 7 Shown with connection sets for surface mounting (accessories)
A Heating flow R ¾ B DHW R ½ C DHW circulation R ½ (separate accessories)

D Cold water R ½ E Heating return R ¾

DHW circulation connection (potable water)
DHW circulation connection with DHW circulation pump connection set (accessories)

Separate installation instructions

Filling the trap with water
Note If there is a risk of frost, only fill the trap just before commissioning.

Pour at least 0.3 l of water into the flue gas connection.

Danger During commissioning, flue gas may escape from the condensate drain. Always fill the trap with water before commissioning.

Fig. 8 18

5593275
Installation

Flue gas connection

Installation sequence

Connect the flue gas/ventilation air pipe. Flue system installation instructions

Note The “System certification” and “Skoberne GmbH flue system” labels enclosed with the technical documentation may only be used in conjunction with the Viessmann flue system made by Skoberne.

Connecting several Vitodens to a shared flue system

Installation instructions for back draught safety device

If connecting multiple Vitodens to a common flue system at positive pressure using routing types C10, C11, C13, C14: Install a back draught safety device (accessories) in the flue gas connection and the mixing shaft of the burner on each boiler. Installing the back draught safety devices:

Converting the control unit for use with a shared flue system: In the commissioning assistant, select the “Multiple
connections” setting under “Flue system type”.

Do not carry out commissioning until the following conditions are met: Free passage through the flue gas pipes. Flue system with positive pressure is gas- tight. Inspection port covers checked for secure and tight
seating. Apertures for ensuring sufficient combustion air sup-
ply are open and cannot be closed off. Note In open flue operation, install a rodent guard grille on the supply air aperture. Applicable regulations on installing and commissioning flue systems have been followed. Visual inspection of the flue gas connection. Note The use of lubricant prevents the gasket from shifting when the flue pipe is installed. When using a straight flue pipe, check that the inner ventilation air pipe is correctly fitted.

Danger Leaking or blocked flue systems or an insufficient supply of combustion air cause life threatening poisoning due to carbon monoxide in the flue gas. Ensure the flue system is in good working order. Vents for interconnected combustion air supply must be non-closable in open flue operation. Prevent condensate drainage via a wind protector.

19

Installation sequence Gas connection
A

Installation
5593275

A

A

Fig. 9

1. If the gas connection has not been fitted previously, seal gas shut-off valve A to the gas connection. When carrying out any work on gas connection fittings, counterhold with a suitable tool. Never transfer any forces to the internal components.

3. Purge the gas line.

Information on operation with LPG Install an external safety solenoid valve if the boiler is installed below ground level. An EM-EA1 extension (accessories) is required to connect the safety solenoid valve.

2. Check for leaks.

Danger Escaping gas leads to a risk of explosion. Check all connections on the gas side (also inside the appliance) for tightness.

Note Only use suitable and approved leak detection agents (EN 14291) and devices for the tightness test. Leak detection agents with unsuitable constituents (e.g. nitrides, sulphides) can cause material damage. Remove residues of the leak detection agent after testing.

!

Please note Excessive test pressure will damage the

boiler and gas solenoid valve.

Max. test pressure 150 mbar (15 kPa). If a

higher pressure is required for leak tests,

disconnect the boiler and the gas solenoid

valve from the main supply pipe (undo the

fitting).

20

Electrical connections

Opening the HMU wiring chamber

!

Please note Electronic assemblies can be damaged by elec-

trostatic discharge.

Prior to commencing any work, touch earthed

objects, such as heating or water pipes to dis-

charge static loads.

1. 2. 2x

Installation sequence

5593275
Installation

Fig. 10 Note For further information on the connections, see the following chapters.

M

M

1~ 1~

AB

65432 1 C
65432 1

40

156 156 P1 P2

96

Fig. 11
Connections to 230 V~ plugs fÖ Power supply lH 230 V input, floating
Output 230 V aBH Switched power outlet

74 5 1

91 91

P1 Cylinder loading pump (connected in the delivered condition)
21

Installation
5593275

Installation sequence Electrical connections (cont.)

P2 230 V parametrisable output:
DHW circulation pump or heating circuit pump for
heating circuit without mixer (in systems with low
loss header) A BCU burner control unit power supply (connected
in the delivered condition) B Power supply for accessories C Plug located externally on the right or left-hand
side of the appliance (see also following diagram)
Note Depending on the version, the plug is inside the appliance.

Connections to extra low voltage (ELV) plugs ! Outside temperature sensor
Terminals 1 and 2 on plug C % Cylinder temperature sensor (connected in the
delivered condition) jF PlusBus
Terminals 5 and 6 on plug C lA CAN bus
Information on connecting accessories When connecting accessories observe the separate installation instructions provided with them.

On-site connections on the heat management unit

65432 1 C
65432 1

Fig. 12
C Plug located externally on the right or left-hand side of the appliance (supplied separately)
Required plugs are supplied in separate packaging. Provide strain relief for cables in the wiring chamber of the HMU heat management unit using cable ties.

22

Electrical connections (cont.)

From 09/2021, plug for electrical connections

inside the appliance

Installation sequence
2.

5593275
Installation

65432 1 C
65432 1

Fig. 13

Route the plug with power cable (required plugs are supplied in separate packaging) through the cable guide on the back of the appliance.

  1. Fig. 14 Use cable ties to apply strain relief to cables in the heat management unit wiring chamber. Note Insert the cable ties with body-bound rivet (packaged separately) into the mounting plate on the plug.

Outside temperature sensor !
Fitting location for outside temperature sensor
North or north-westerly wall, 2 to 2.5 m above ground level; in multi storey buildings, in the upper half of the second floor
Not above windows, doors or vents

Not immediately below balconies or gutters Never render over
Outside temperature sensor connection
2-core lead, length up to 35 m with a cross-section of 1.5 mm2

Connecting low loss header sensor )
The low loss header sensor is connected to accessory extension EM-P1 or EM-M1/MX (ADIO electronics module).

Installation instructions for extension EM-P1 or EM-M1/MX

23

Installation
5593275

Installation sequence Electrical connections (cont.)

Connecting the circulation pump to P2

M 1~

A

Information on priority of connection options: If heating circuit pump for heating circuit without
mixer A1 is installed: Then connect DHW circulation pump to an EM-P1 extension (accessories). If no heating circuit pump for heating circuit without mixer A1 is connected: Connect DHW circulation pump to output P2.

B
Fig. 15
A Circulation pump B Plug P2 on HMU heat management unit
Possible functions: Heating circuit pump for heating circuit without mixer
A1 in connection with low loss header and heating circuits with mixer Heating circuit pump for heating circuit without mixer A1, without low loss header and with no other heating circuits (max. 1 heating circuit in the system). DHW circulation pump Connect DHW circulation pumps with standalone functions directly to the 230 V supply.

The function is selected in the commissioning assistant by selecting the connected component.

Specification Rated current
Rated voltage

1 A 230 V ~

Floating switching contact connection

Connection at plug lH
One of the following functions can be connected: External demand External blocking DHW circulation pump external demand (pushbutton
function, pump runs for 5 min). Not for Vitodens 222-W. Room temperature controller (room thermostat) In conjunction with operating mode Continuous operation with room temperature controller (not for Vitodens 3xx) For external heating circuit hook-up (if installed), see chapter “External heating circuit hook-up”. Not for Vitodens 3xx.

A
1 L ? N lH
Fig. 16 A Floating contact Assigning functions in the commissioning assistant

See commissioning assistant in “Commissioning”.

Checking the CAN bus terminator switch setting
The CAN bus resistor is switched using switch A in the wiring chamber.

24

5593275
Installation

Electrical connections (cont.)

Installation sequence

ON

1

91 91

A
Fig. 17

If the device is not integrated into a CAN bus sys-

tem: Switch A must not be set to “ON”.

If the device is integrated into a CAN bus system and

is located at the beginning or end of this system (not

in the middle) of the CAN bus system (connected to only one plug lA): Set switch A to “ON”.

A

C

C

ON

91 91

B

B

Fig. 18

A Heat generator / HMU heat management unit

B CAN bus cable

C CAN bus other subscribers

If the device is integrated into a CAN bus system and

is not located at the beginning or end of the CAN bus system (both plugs lA connected): Do not set

switch A to “ON”.

C

A

C

B
Fig. 19

ON 91 91
B

Power supply for accessories at plug lH/aBH (230 V ~)

When positioned in wet rooms, accessories outside the wet area must not be connected to the power supply at the HMU heat management unit. If the boiler is not sited in a wet room, the power supply for accessories can be connected directly to the HMU heat management unit. This connection is switched directly with the ON/OFF switch of the appliance.

If the total system current exceeds 6 A, connect one or more extensions directly to the mains supply via an ON/OFF switch (see next chapter).

25

Installation

Installation sequence Electrical connections (cont.)

Power supply and PlusBus connection of accessories

Power supply of all accessories at the HMU heat management unit

A

B

C

D

74 40 96/156 74 74 40A 40 74 74 40A 40 74 74 40A 40

E
Fig. 20

Some accessories with direct power supply

A

B

C

D

74 40 96/156 74 74 40A 40 74 74 40A 40 74 74 40A 40

E
Fig. 21

A

HMU heat management unit, heat generator

B

Mixer extension kit (ADIO electronics module)

C

Mixer extension kit (ADIO electronics module)

D

EM-EA1 extension (DIO electronics module)

and/or EM-S1 extension (ADIO or SDIO/

SM1A electronics module)

PlusBus system length max. 50 m for 0.34 mm2 cable cross-section and unshielded cable. If the current flowing to the connected working parts (e.g. circulation pumps) is higher than the fuse rating of the relevant accessory, only use the output concerned to control an on-site relay.

Accessories
EM-M1, EM-MX mixer extension kit EM-EA1 extension EM-S1 extension (not for Vitodens 222-F, 222-W and 333-F)

Internal fuse protection 2 A
2 A 2 A

E

ON/OFF switch

Mains input

fÖA Power outlet

jF

PlusBus

lH/aBH Power outlet on HMU heat management unit

Danger Incorrect wiring can lead to serious injury from electrical current and result in appliance damage. Route extra low voltage (ELV) leads < 42 V
separately from cables > 42 V/230 V~. Only strip the minimum of insulation from
cables as close as possible to the terminals and bundle tightly to the corresponding terminals. Secure cables with cable ties.

5593275

26

Electrical connections (cont.)

Installation sequence

5593275
Installation

Power supply fÖ

Danger Incorrectly executed electrical installations can result in injuries from electrical current and damage to the appliance.
Connect the power supply and implement all safety measures (e.g. RCD circuit) in accordance with the following regulations: IEC 60364-4-41 IEEE Wiring Regulation; BS 7671:2018 Connection conditions of the local grid opera-
tor
Install an isolator in the power cable to provide omnipolar separation from the mains for all active conductors, corresponding to overvoltage category III (3 mm) for complete isolation. The isolator must be fitted in the permanent electrical installation, in line with installation requirements. We also recommend installing a pulse current-sensitive RCD (RCD class A ).
Connect the power cable to the electricity supply using a fixed connection.

If the power supply to the appliance is connected with a flexible power cable, ensure that the live conductors are pulled taut before the earth conductor in the event of strain relief failure. The length of the earth conductor wire will depend on the design.
Max. fuse rating 16 A.
Danger The absence of system component earthing can lead to serious injury from electric current if an electrical fault occurs. The appliance and pipework must be connected to the equipotential bonding of the building.

WiFi operational reliability and system requirements

WiFi router system requirement WiFi router with activated WiFi:
The WiFi router must be protected by a sufficiently secure WPA2 password. The WiFi router must always have the latest firmware update. Do not use unencrypted connections between the heat generator and the WiFi router. Internet connection with high availability: Flat rate (flat rate tariff without restriction on time or data volume) Dynamic IP addressing (DHCP, delivered condition) in the network (WiFi): Have this checked on site by an IT expert prior to commissioning. Arrange for set up if required. Set routing and security parameters in the IP network (LAN). Enable the following ports for direct outgoing connections: ­ Port 80 ­ Port 123 ­ Port 443 ­ Port 8883 Have this checked on site by an IT expert prior to commissioning. Set up enabling if required.

Wireless signal range of WiFi connection
The range of wireless signals may be reduced by walls, ceilings and interior fixtures. These weaken the wireless signal, causing poor reception due to the following circumstances. On their way between transmitter and receiver, wire-
less signals are damped, e.g. by air or when penetrating walls. Wireless signals are reflected by metallic objects, e.g. reinforcements embedded in walls, metal foil of thermal insulation and thermal glazing with metallised thermal vapour deposit. Wireless signals are isolated by service ducts and lift shafts. Wireless signals are disrupted by devices that also operate with high frequency signals. Maintain a distance of at least 2 m from these devices: ­ Computers ­ Audio and video systems ­ Devices with active WiFi connection ­ Electronic transformers ­ Pre-ballasts Install the heat generator as close as possible to the WiFi router to ensure a good WiFi connection. The signal strength can be displayed on the programming unit: See operating instructions.

Note The WiFi signal strength can be increased with commercially available WiFi repeaters.

27

Installation
5593275

Installation sequence Electrical connections (cont.)
Angle of penetration
The reception quality remains best if radio signals hit the walls vertically. Depending on the angle of penetration, the effective wall thickness changes and so does the extent to which the electromagnetic waves are damped.
Flat (unfavourable) angle of penetration
A

Ideal angle of penetration
A
C B

C
Fig. 23
B
A WiFi router B Heat generator C Wall

Fig. 22
A WiFi router B Heat generator C Wall

Routing connecting cables/leads

!

Please note If connecting cables/leads come into contact

with hot components, they will be damaged.

When routing and securing cables/leads on site,

ensure that the maximum permissible tempera-

tures for these cables/leads are not exceeded.

Closing the wiring chamber

3. 2. 2x

Fig. 24 28

Fitting the front panel and programming unit
1. 2.
A
Fig. 25 Lightguide A at the bottom

Installation sequence

5593275
Installation

29

Commissioning, inspection, maintenance Steps – commissioning, inspection and maintenance
Commissioning steps Inspection steps Maintenance steps

Page

···

··

·

·

·

·

·

·

···

·

·

·

···

···

·

·

·

·

·

··

··

··

·

··

··

··

·

·

·

·

·

··

·

···

···

···

·

·

···

···

30

1. Filling the trap with water…………………………………………………………………………………….. 32 2. Removing the front panels…………………………………………………………………………………… 32 3. Moving the programming unit to the maintenance position…………………………………… 32 4. Commissioning the system………………………………………………………………………………….. 33 5. Filling the heating system……………………………………………………………………………………. 37 6. Venting the boiler………………………………………………………………………………………………… 39 7. Venting the heating system………………………………………………………………………………….. 39 8. Filling the DHW cylinder on the DHW side……………………………………………………………. 40 9. Checking the connections on the heating water and DHW sides…………………………… 40 10. Naming the heating circuits…………………………………………………………………………………. 40 11. Checking the gas type…………………………………………………………………………………………. 41 12. Converting the gas type (only for operation with LPG)………………………………………….. 41 13. Checking the static pressure and supply pressure……………………………………………….. 42 14. Function sequence and possible faults………………………………………………………………… 43 15. Setting the max. heating output……………………………………………………………………………. 44 16. Activating screed drying……………………………………………………………………………………… 44 17. Adjusting the pump rate of the integral circulation pump……………………………………… 45 18. Checking the balanced flue system for leaks (annular gap check)…………………………. 47 19. Removing the burner…………………………………………………………………………………………… 48 20. Checking the burner gasket and burner gauze assembly………………………………………. 49 21. Checking and adjusting the ignition and ionisation electrodes……………………………… 50 22. Checking the back draught safety devices……………………………………………………………. 50 23. Cleaning the heating surfaces……………………………………………………………………………… 51 24. Checking the condensate drain and cleaning the trap…………………………………………… 52 25. Installing the burner…………………………………………………………………………………………….. 53 26. Checking the neutralising system (if installed) 27. Checking the anode connection and anode earth current with an anode tester……… 54 28. Draining the boiler on the DHW side…………………………………………………………………….. 55 29. Cleaning the loading cylinder………………………………………………………………………………. 56 30. Checking and replacing the protective magnesium anode (if necessary)………………. 57 31. Re-assembling and filling the loading cylinder……………………………………………………… 58 32. Checking the diaphragm expansion vessel and system pressure………………………….. 59 33. Checking the pre-charge pressure and the DHW expansion vessel (if installed)…….. 60 34. Checking the safety valve function 35. Checking the electrical connections for firm seating 36. Checking gas equipment for leaks at operating pressure……………………………………… 60 37. Checking the combustion quality…………………………………………………………………………. 60 38. Checking the flue system for unrestricted flow and leaks 39. Checking the external LPG safety valve (if installed)

5593275

Commissioning, inspection, maintenance Steps – commissioning, inspection and… (cont.)

Commissioning steps Inspection steps Maintenance steps

Page

· ·
· ··· ·

40. Matching the control unit to the heating system…………………………………………………… 62 41. Adjusting heating curves…………………………………………………………………………………….. 62 42. Calling up and resetting the maintenance display…………………………………………………. 62 43. Fitting the front panel………………………………………………………………………………………….. 63 44. Instructing the system user…………………………………………………………………………………. 63

5593275

31

Commissioning, inspection, maintenance Filling the trap with water

!

Please note Only commission the appliance with a fully filled

trap.

Check that the trap has been filled with water.

Pour at least 0.3 l of water into the flue gas connection.

!

Please note During commissioning, flue gas may escape

from the condensate drain.

Always fill the trap with water before commis-

sioning.

Fig. 26
Removing the front panels
See page 17, steps 1 to 5
Moving the programming unit to the maintenance position
To carry out various maintenance jobs, move the programming unit downwards.

5593275

32

Commissioning, inspection, maintenance Moving the programming unit to the maintenance… (cont.)
1. 2.

  1. Fig. 27

Commissioning the system

Commissioning assistant

1. Open the gas shut-off valve.

Commissioning via software tool

2. If the appliance has not been switched on yet: Turn on the ON/OFF switch. The commissioning assistant starts automatically. If the appliance has already been switched on: See chapter “Calling up the commissioning assistant at a later point”.

Note Apps for commissioning and service are available for iOS and Android devices.

3. For further steps, see commissioning assistant in the following overview.
Note Once the commissioning assistant has finished, run an actuator test to check that the actuators are connected correctly and working properly.
Note Depending on the type of heat generator, connected accessories and other settings, not all menu points will be displayed and not all functions are available. See the technical guide or hydraulic scheme browser.

The appliance automatically switches on the WiFi access point.
1. Open the gas shut-off valve.
2. and OK should be pressed simultaneously for approx. 4 s.
3. Use / to select “Connect with software tool” and confirm with OK.
4. Follow the instructions in the app.

33

5593275

Commissioning, inspection, maintenance Commissioning the system (cont.)

Commissioning assistant Explanations and references sequence

Commissioning

Language

With programming unit

If commissioning is to be carried out at the programming unit of the heat generator.

Trade fair mode Off On

Only for demonstration purposes. Do not select for normal heating mode.

Units Temperature Length Pressure

Select the required units of measurement (e.g. °C or °F)

Date Format

Time Format Time changeover

System pressure

Set value Area

Select the set system pressure, e.g. 1.5 bar. Select the range within which the system pressure can fluctuate around the set value, e.g. +/-0.5 bar. Example: If the value falls below the set range for a certain period of time (set value [1.5 bar] – range [0.5 bar] = 1.0 bar), fault message F.74 or warning message A.11 is displayed.

Filling Venting

Filling: See chapters “Filling the heating system” and “Venting the heating system”.

Gas type

If operating with LPG, switch to “LPG”

Flue system

Single connection

Only one heat generator is connected to the flue system (factory setting).

Multiple connections

Several heat generators are connected to the flue system at positive pressure (only suitable for systems that run on natural gas).

After confirmation with OK, an automatic test of the flue gas temperature sensor is carried out. See the following chapter.

Building type

Detached house

One shared holiday program and time program for DHW heating

Apartment building

Holiday program is set separately (room temperature-dependent operation not possible)

Continue in the commissioning assistant with Yes or end commissioning with No.

Operating mode

Weather-compensated The outside temperature sensor must be connected.

Constant mode

Operation with constant flow temperature

Room temperature-dependent

A room temperature controller/room thermostat (accessories) must be connected to plug 96. Only one heating circuit without mixer in the system (only available for detached houses).

5593275

34

Commissioning the system (cont.)

Commissioning, inspection, maintenance

Commissioning assistant sequence System scheme
Heating circuit 1
Heating circuit 2, 3, 4 DHW Not installed Cylinder with one sensor Cylinder with one sensor
and DHW circulation pump DHW comfort function Loading cylinder with one sensor Loading cylinder with one sensor and DHW circulation pump Loading cylinder with 2 sensors Loading cylinder with 2 sensors and DHW circulation pump

Explanations and references
Heating circuit without mixer or heating circuit without mixer with external hook-up or Heating circuit without mixer with pump (without low loss header and without further heating circuits, max. 1 heating circuit in the system) for e.g. fixed value control station. Heating circuits with mixer or heating circuit with mixer with external hook-up Settings for DHW heating according to the system components System without DHW heating System with DHW cylinder with 1 cylinder temperature sensor System with DHW cylinder with 1 DHW cylinder temperature sensor and DHW circulation pump
Only for gas condensing combi boilers (not adjustable) Gas condensing storage combi boiler with integral loading cylinder
Gas condensing storage combi boiler with integral loading cylinder and DHW circulation pump
Gas condensing storage combi boiler or gas/solar condensing storage combi boiler with integral loading cylinder Gas condensing storage combi boiler or gas/solar condensing storage combi boiler with integral loading cylinder and DHW circulation pump
Note DHW circulation pump not possible with Vitodens 222-W.

Low loss header/buffer cyl- Settings for the consumer circuits according to the system components inder

Not installed

There is no low loss header or heating water buffer cylinder in the system.

Low loss header, heating System with low loss header, without DHW heating only

DHW heating upstream DHW heating with e.g. separate DHW cylinder connected upstream of the low

of low loss header

loss header

DHW heating down-

DHW heating with e.g. separate DHW cylinder connected downstream of the

stream of low loss head- low loss header

er

Buffer cylinder, heating System with heating water buffer cylinder, without DHW heating only

DHW heating upstream DHW heating with e.g. separate DHW cylinder connected upstream of the

of buffer cylinder

heating water buffer cylinder

DHW heating down-

DHW heating with e.g. separate DHW cylinder connected downstream of the

stream of buffer cylinder heating water buffer cylinder

Solar Note Not for Vitodens 222-W, type B2LF and Vitodens 222-F, type B2SF

Solar thermal system connected to heat generator via solar extension (ADIO, SDIO/SM1A electronics module) Setting subject to the design of the solar thermal system
Solar extension installation and service instructions

5593275

35

Commissioning, inspection, maintenance Commissioning the system (cont.)

Commissioning assistant Explanations and references sequence

No solar function With DHW heating

With central heating backup

Only adjustable for SDIO/SM1A electronics module (not for Vitodens 242-F)

With 2nd cylinder preheating

Only adjustable for SDIO/SM1A electronics module (not for Vitodens 242-F)

With thermostat function Only adjustable for SDIO/SM1A electronics module (not for Vitodens 242-F)

Plug 96

Function selection if a contact has been connected to plug 96 of the HMU heat management unit

No function

External demand, DHW Pushbutton function, DHW circulation pump runs for 5 min. circulation pump

External demand

Heat generator demand with adjustable set flow temperature (parameter 528.0) and set primary circuit pump speed (parameter 1100.2)

External blocking

EM-EA1 (DIO) function

If an EM-EA1 extension (DIO electronics module) is connected as a function extension Selection of the connected function according to the table in the installation instructions for the EM-EA1 extension

Remote control

Set the type of remote control and subscriber no. as assignment to the respective heating circuit. Up to 3 heating circuits can be assigned to one remote control unit. It is not possible for several remote control units to act on one heating circuit.

Maintenance

Interval in burner hours run Interval adjustable in steps of 100 h. until next maintenance

Interval until next maintenance

Interval adjustable to 3, 6, 12, 18 or 24 months.

The system carries out a restart.

Automatic flue gas sensor check
The display shows: “Testing, flue gas temperature sensor” and “Enabled, please wait …”. If the flue gas temperature sensor is not positioned correctly, fault message F.416 appears on the display. For further details regarding the flue gas temperature sensor test, see “Repairs”. If fault message F.416 appears, reposition the flue gas temperature sensor in the flue gas connection. Check for leaks on the flue gas side.
Note The burner remains locked out until the test has been passed.
When the fault has been remedied, turn the ON/OFF switch off and back on again. Confirm the message with OK.

Switching WiFi ON/OFF
The appliance is equipped with an integrated WiFi communication module with extended type plate. The internal communication module supports commissioning, maintenance and servicing with “ViGuide” online/the “ViGuide” app as well as operation via the “ViCare” app. The access details required for establishing a connection are recorded in the form of an access code with “WiFi symbol”. Three copies of this code are located on the front of the programming unit. Remove the access code label and for commissioning, affix one label to the space marked out on the type plate. Switch on the WiFi connection and establish a connection to the router. See also page 27. Activating the internet connection:
Operating instructions

36

5593275

Commissioning the system (cont.)

Commissioning, inspection, maintenance

Affix a further label here so you can find it again for use at a later time:
Fig. 28 Affix a label in the operating instructions. Calling up the commissioning assistant at a later point If you need to continue commissioning later, the commissioning assistant can be reactivated at any time.

Tap the following buttons:
1. and OK simultaneously for approx. 4 s, then release.
2. Use / to select “Basic settings”.
3. OK
4. Use / to select “Commissioning assistant”.
5. OK

Entering contact details
The system operator can call up contact details when required and notify the heating contractor.
1. and OK simultaneously for approx. 4 s, then release.

2. Use / to select “Connect with software tool”.
3. Follow the instructions on the programming unit display.

Filling the heating system

Fill water

As a heat transfer medium for DHW heating, the heating water must meet fluid category 3. This requirement is met if water of potable quality is used as heating water. For example, if additives are used, the additive manufacturer must specify which category the treated heating water comes under.

!

Please note Unsuitable fill water increases the level of

deposits and corrosion and may lead to appli-

ance damage.

Flush the heating system thoroughly before

filling.

Only use fill water of potable water quality.

Special antifreeze suitable for heating systems

can be added to the fill water. The antifreeze

manufacturer must verify its suitability.

Fill and top-up water with a water hardness

above 300 ppm must be softened, e.g. with a

small softening system for heating water.

5593275

37

Commissioning, inspection, maintenance Filling the heating system (cont.)
B A B D E
C

Fig. 29 Shown with the connections at the top

1. Check the pre-charge pressure of the expansion vessel.
2. Close the gas shut-off valve.
3. Connect the fill hose to boiler drain & fill valve A in the heating flow. Either on the side or top of the boiler depending on the connection set.
4. Open shut-off valves B on the heating water side.
5. Fit hose to air vent valve C. Route the hose into a suitable container or drain outlet.

6. Activate the filling function (see commissioning assistant or following chapter).
7. Fill the heating system via boiler drain & fill valve A. Minimum system pressure > 1.0 bar (0.1 MPa). Check the system pressure at pressure gauge D. Indicator must be in the green band.
Note Close air vent valve C and adjust system pressure at boiler drain & fill valve A.
8. Close boiler drain & fill valve A.

Activating the filling function
If the filling function is to be activated after commissioning.
Tap the following buttons:
1. and OK ­ press simultaneously for approx. 4 s, then release.
2. Use / to select “Basic settings”.
3. OK

4. Use / to select “Commissioning assistant”.
5. OK
6. / for “Next” and OK until “Filling” appears.
7. OK The filling function is activated. The display shows the system pressure. The filling function ends automatically after 20 min or when you tap OK.

38

5593275

Venting the boiler

Commissioning, inspection, maintenance

!

Please note To prevent appliance damage,

Do not vent the boiler via the safety valve on the

heating water side.

1. Close shut-off valves B on the heating water side.

2. Open air vent valve C and fill valve A in the heating flow. Vent (flush) under mains pressure until no more air noise is audible.

3. Close air vent valve C and fill valve A. At the same time, adjust operating pressure > 1.0 bar (0.1 MPa).
Note Call up the pressure indicator in the “System overview” menu point. See operating instructions.
4. Open shut-off valves B on the heating water side.
5. Remove drain hose from air vent valve C and keep safe.

Venting the heating system

A

Fig. 30

1. Check whether the air vent screw in quick-action air vent valve A of the heating circuit pump is open.
2. Close the gas shut-off valve. Switch the appliance on.

3. Activate venting function (see following steps).
4. Call up the pressure display with “System overview”. Check the system pressure.

Activating the venting function
If the venting function is to be activated after commissioning.
Tap the following buttons:
1. and OK ­ press simultaneously for approx. 4 s, then release.

2. Use 3. OK 4. Use 5. OK

/ to select “Basic settings”. / to select “Commissioning assistant”.

39

5593275

Commissioning, inspection, maintenance Venting the heating system (cont.)

6. / for “Next” and OK until “Venting” appears.

7. OK The venting function is activated. The display shows the system pressure. The venting function ends automatically after 20 min or when you tap OK.

Filling the DHW cylinder on the DHW side
1. The lever on the valve must be in position A.
2. Open the on-site DHW supply and a DHW draw-off point.
3. Once air stops coming out of the DHW draw-off point, the DHW cylinder is completely filled.
4. If there is still air in the cylinder loading circuit, it can be released via air vent screw D on the cylinder loading pump.

Fig. 31

A

C

B

D
Fig. 32

Checking the connections on the heating water and DHW sides

Danger There is a risk of electric shock from escaping

!

heating water or DHW.

When commissioning and after carrying out

maintenance work, check all water side connec-

tions for leaks.

Please note Leaking hydraulic connections lead to appliance damage. Check the internal and on-site hydraulic con-
nections for leaks. In the event of leaks, switch off the appliance
immediately. Drain the heating water. Check the seating of seal rings. Always replace displaced seal rings.

Naming the heating circuits

In the delivered condition, the heating circuits are designated “Heating circuit 1”, “Heating circuit 2”, “Heating circuit 3” and “Heating circuit 4”. If the system user prefers, the heating circuits can be renamed to suit the specific system.

To enter names for heating circuits: Operating instructions

5593275

40

Checking the gas type

Commissioning, inspection, maintenance

The boiler is equipped with an electronic combustion controller that adjusts the burner for optimum combustion in accordance with the prevailing gas quality. For operation with natural gas, no adjustment is
therefore required across the entire Wobbe index range. The boiler can be operated within the Wobbe index range 9.5 to 15.2 kWh/m3 (34.2 to 54.7 MJ/m3). For operation with LPG, the gas type needs to be changed on the control unit (see following chapter).

1. Determine the gas type and Wobbe index by asking your local gas supply utility or LPG supplier.
2. Record the gas type in the service report.

Converting the gas type (only for operation with LPG)

1. To change the gas type on the control unit, see “Commissioning the system with the commissioning assistant”
Note No mechanical adjustments are made to the gas solenoid valve.

2. Affix label “G31” (supplied with the technical documentation) adjacent to the type plate on the out-
side of the appliance.

5593275

41

Commissioning, inspection, maintenance Checking the static pressure and supply pressure
C

B
A
Fig. 33
A Cover panel B Test connector C Type plate

Danger CO formation as a result of incorrect burner adjustment can have serious health implications. Carry out a CO test before and after work on gas appliances.
Operation with LPG Purge the LPG tank twice on commissioning/replacement. Vent the tank and gas connection line thoroughly after purging.
01. Close the gas shut-off valve.
02. Undo clips and remove cover panel A.
03. Undo screw in test connector B on the gas train, but do not remove it. Connect the pressure gauge.
04. Open the gas shut-off valve.

07. Check the supply (flow) pressure. For set values, see the following table.
Note Use a suitable measuring device with a resolution of at least 0.1 mbar (0.01 kPa) to check the supply pressure.
08. Record the actual value in the report. Implement measures as indicated in the table below.
09. Shut down the boiler. Close the gas shut-off valve.
10. Remove the pressure gauge. Tighten the screw in test connector B.
11. Open the gas shut-off valve and start the appliance.

05. Test the static pressure and record it in the report. Max. 57.5 mbar (5.75 kPa).
06. Start the boiler.

Danger Gas escaping from the test connector leads
to a risk of explosion. Check gas tightness at test connector B.

Note During commissioning, the appliance can enter a fault state if there are airlocks in the gas line. Reset the appliance after approx. 5 s (see operating instructions).

12. Fit cover panel A.

42

5593275

Commissioning, inspection, maintenance Checking the static pressure and supply pressure (cont.)

Supply pressure (flow pressure)

For natural gas

For LPG

< 13 mbar (1.3 kPa)

< 25 mbar (2.5 kPa)

13 to 25 mbar (1.3 to 2.5 kPa)

25 mbar (2.5 kPa)

25 to 57.5 mbar (2.5 to 5.75 kPa)

57.5 mbar (5.75 kPa)

Measures
Do not start the boiler. Notify the gas supply utility or LPG supplier. Start the boiler.
Install a separate gas pressure governor upstream of the system. Set the pre- charge pressure to 20 mbar (2.0 kPa) for natural gas and 50 mbar (5.0 kPa) for LPG. Notify the gas supply utility or LPG supplier.

Function sequence and possible faults

Control unit issues a heat demand

Display No

Measure
Increase set value. Ensure heat transfer.

Yes

Fan starts

No Fault F.59, F.457

Ignition

Yes No Fault F.359

Yes Gas train opens
Yes Ionisation current builds

No Fault F.357 No Fault F.369, F.380

Yes Burner in operation

No Shuts down below the set boiler water temperature and restarts immediately.

Check connection cables on fan. Check power supply on fan.
Check ignition module (control voltage 230 V across plugs “X18.1” and “X18.3” on the burner control units). Check the gas supply.
Check the gas supply pressure.
Check distance of ionisation electrode on burner gauze assembly. Purge the gas line.
Check the flue system for tightness (flue gas recirculation). Check gas flow pressure.

5593275

43

Commissioning, inspection, maintenance Function sequence and possible faults (cont.)

Yes
Automatic calibration of the combustion controller

Fault F.62, F.373 No
Fault F.346, F.377

Ensure adequate heat transfer. Reset device.
Check gap between ionisation electrode and burner gauze assembly. Check flue system. Remove flue gas recirculation if required. Reset device.
Operating instructions

For further details regarding faults, see page “Troubleshooting”.

Setting the max. heating output

A limit can be set on the maximum heating output for heating mode. The limit is set via the modulation range.
Note The flow rate must be checked before the max. heating output can be adjusted. Ensure adequate heat transfer.
Tap the following buttons:
1. and OK ­ press simultaneously for approx. 4 s, then release.
2. Use / to select “System configuration”.

3. OK
4. Use / to select “Boiler”.
5. OK
6. Use / to select parameter 596.0 “Maximum heating output”.
7. OK
8. Use / to set the required value in % of rated heating output. Delivered condition 100 %.
9. OK

Activating screed drying
Screed drying
6 different temperature profiles can be set for screed drying: Preset temperature profiles can be adjusted via parameter 897.0 “Screed drying” in the General group. For further details, see “Function description”.

Note Screed drying applies to all connected heating circuits simultaneously. With a combi boiler, DHW heating is not possible during screed drying. With a system boiler or storage combi boiler, after 30 minutes DHW heating is suspended for an hour (parameter 1087.1) in order to run the screed drying program.

5593275

44

Commissioning, inspection, maintenance Adjusting the pump rate of the integral circulation pump

The pump speed and consequently the pump rate are regulated subject to the outside temperature and the switching times for heating mode or reduced mode. The minimum and maximum speeds for heating mode can be matched to the existing heating system at the control unit.
100
Max

Speed in %

Min

+30

+20

-20

-30

Outside temperature in °C

Fig. 34

Setting (%) in the heating circuit 1 group: Min. speed: Parameter 1102.0 Max. speed: Parameter 1102.1

In the delivered condition, the minimum pump rate and the maximum pump rate are set to the following values: Note The minimum speed of 60 % is not undershot, in order to ensure the required flow rate via the internal overflow valve. Having the minimum pump rate set to 40 % ensures that the pump works more energy efficiently in weather-compensated mode.

Rated heating output Speed settings in the

in kW

delivered condition in %

Min. pump Max. pump

rate

rate

11

40

60

19

40

70

25

40

85

32

40

100

In conjunction with a low loss header, heating water

buffer cylinder and heating circuits with mixer, the

internal circulation pump runs at a constant speed.

Speed setting (%): Parameter 1100.2 in the Boiler

group

5593275

45

Commissioning, inspection, maintenance Adjusting the pump rate of the integral… (cont.)

Residual head of integral circulation pump

700 70 650 65 E

600 60 D
550 55

500 50 450 45 C

400 40 350 35 B 300 30 250 25 A

200 20 150 15
F 100 10 50 5

0 0 0 100 200 300 400 500 600 700 800 900 1000 1100 1200 1300 1400 Flow rate in l/h
Fig. 35
F Upper operational limit (integral bypass opens)

Curve A B C D E

Pump rate of circulation pump

60 % 70 % 80 % 90 % 100 %

Residual head mbar kPa
5593275

46

Commissioning, inspection, maintenance Checking the balanced flue system for leaks (annular gap check)
A

Fig. 36 A Combustion air aperture (ventilation air)

For balanced flue systems tested together with the heat generator, there is no requirement for a tightness test (overpressure test) during commissioning by the flue gas inspector. In this case, we recommend that a simple tightness test is carried out during system commissioning. For this, check the CO2 or O2 concentration in the combustion air at the annular gap of the balanced flue pipe. If the CO2 concentration is less than 0.2 % or the O2 concentration is greater than 20.6 %, the flue pipe is deemed to be sufficiently gas-tight.

If actual CO2 values are greater or O2 values are lower, then pressure test the flue pipe with a static pressure of 200 Pa.

!

Please note If the test port is not sealed, combustion air is

drawn in from the room.

After the tightness test, re-seal the test port with

the plug.

5593275

47

Commissioning, inspection, maintenance Removing the burner

4x G

D

E

C

B

F
A
Fig. 37

1. Turn off the ON/OFF switch.
2. Close the gas shut-off valve and safeguard against reopening.
3. Release the clips and remove the cover panel.
4. Disconnect cables and leads from: Fan motor A Adaptor, CAN bus fan Ionisation electrode B Ignition unit C Earth D

5. Undo gas supply pipe fitting E. 6. Detach Venturi extension F from fan unit. 7. Undo 4 screws G and remove the burner.
Note Cover gas connection E so that no small parts can fall into it.

5593275

48

Commissioning, inspection, maintenance Checking the burner gasket and burner gauze assembly

D E

F G

C

A

B

CH

Fig. 38

Check burner gauze assembly D, electrodes B, thermal insulation ring F and gasket G for damage. Only
remove and replace components if they are damaged
or worn.

6. Insert thermal insulation ring F and burner gauze assembly D with gasket E. Observe correct installation position. Align the tab as per the diagram.

Note If replacing the burner gauze assembly, also replace the gauze assembly gasket and the fixing screw.
1. Disconnect plug with ignition electrode leads from ignition unit A.
2. Remove electrodes B.
3. Undo Torx screw C. Hold onto burner gauze assembly D when undoing the screw.
4. Remove burner gauze assembly D with gasket E and thermal insulation ring F. Check components for damage.
5. Install new burner gasket G. Observe correct installation position. Align the tab as per the diagram.

7. Align the hole in burner gauze assembly D with burner door pin H.

!

Please note Incorrect positioning of the burner gauze

assembly on the burner door will cause

damage to the burner door.

Insert the burner door pin into the hole in the

burner gauze assembly.

Secure burner gauze assembly D and gasket E with Torx screw C. Tighten screws as tightly as necessary and ensure that the components are undamaged and are functioning correctly throughout service life. Observe torque settings if a torque wrench is available. Torque: 3.0 Nm.

8. Check thermal insulation ring F for firm seating.

49

5593275

Commissioning, inspection, maintenance
Checking the burner gasket and burner gauze… (cont.)
9. Fit electrodes B. Check clearances, see following chapter. Tighten screws as tightly as necessary and ensure that the components are undamaged and are functioning correctly throughout service life. Observe torque settings if a torque wrench is available. Torque: 4.5 Nm.
Checking and adjusting the ignition and ionisation electrodes

6.5

+1 0

A

5+30 A

10 ±0.5 B

4+00.5

Fig. 39
A Ignition electrodes B Ionisation electrode

1. Check the electrodes for wear and contamination.
2. Clean the electrodes with a small brush (not a wire brush) or sandpaper.

3. Check the electrode gaps. If the gaps are not as specified or the electrodes are damaged, replace the electrodes and gaskets and adjust them as required. Tighten screws as tightly as necessary and ensure that the components are undamaged and are functioning correctly throughout service life. Observe torque settings if a torque wrench is available. Tighten the electrode fixing screws to a torque of 4.5 Nm.

Checking the back draught safety devices
Only for multiple connections to a flue system or multi boiler systems with a flue gas cascade.

5593275

50

Commissioning, inspection, maintenance Checking the back draught safety devices (cont.)

Back draught safety device in the mixing shaft of the burner

Back draught safety device in the flue gas connection

A

B

Fig. 41

A
Fig. 40 1. Undo 2 screws and remove fan A.

1. Remove the balanced flue system.
Note If the balanced flue system cannot be removed, clean and check the back draught safety device via the inspection cover.
2. Check back draught safety device A for dirt, ease of movement and function.

2. Remove back draught safety device B.

3. Refit the balanced flue system.

3. Check the damper and gasket for dirt and damage. Replace if necessary.
4. Refit back draught safety device B.

4. Pour a small amount of water through the inspection port to ensure the back draught safety device
is working.

Note Observe correct installation position.

5. Refit fan A and secure with 2 screws. Tighten screws as tightly as necessary and ensure that the components are undamaged and are functioning correctly throughout service life. Observe torque settings if a torque wrench is available. Torque: 4.0 Nm

Cleaning the heating surfaces

!

! Please note
Scratches to the surfaces of the heat exchanger

Please note Prevent damage due to cleaning water.

that come into contact with hot gas can result in

Cover electronic components with suitable

corrosion damage. Brushing can cause deposits

watertight material.

to become lodged in the gaps between the coils.

Never use brushes to clean the heating surfaces.

Note Discolouration on the heat exchanger surface is a normal sign of use. It has no bearing on the function and

service life of the heat exchanger.

The use of chemical cleaning agents is not required.

51

5593275

Commissioning, inspection, maintenance Cleaning the heating surfaces (cont.)

A Fig. 42

1. Use a vacuum cleaner to remove combustion residues from heating surface A of the heat exchanger.
2. Flush heating surface A with water.
3. Check condensate drain. Clean the trap: See the following chapter.
4. Check the thermal insulation mat (if installed) in the heat exchanger for damage, replace if necessary.

Checking the condensate drain and cleaning the trap

!

Please note Prevent damage due to condensate.

Cover electronic components with suitable

watertight material.

2. 4. 3.

Fig. 43

1. Pivot the HMU heat management unit forwards.

2. Undo the hose retainer. Remove the supply hose.

!

Please note Do not undo using a sharp object. This can

damage the condensate hose.

The hose retainer is detachable.

52

3. Undo hose clip and pull off drain hose.
4. Release trap from retaining clip. Hold trap as straight as possible and remove. Ensure that no condensate runs out.
5. Clean the trap.

5593275

Commissioning, inspection, maintenance Checking the condensate drain and cleaning the… (cont.)

6. Refit the trap.
7. Refit the hoses. Secure the drain hose with the hose clip and attach the supply hose with the retainer.
8. Check that connections on the trap and the heat exchanger are seated correctly.

9. Flush the heating surface again with min. 0.3 l of water. This will also fill the trap with water.

!

Please note If the trap is not filled with water, flue gas

can escape.

Only start the appliance when the trap has

been filled.

Note Route the drain hose without any bends and with a constant fall.

Danger Risk of electric shock from escaping condensate and risk of poisoning from escaping flue gas. Check the connections for leaks and check that the trap is seated correctly.

Installing the burner

4x G

D

E

C

B

F A
Fig. 44
1. If necessary, move the programming unit.

53

5593275

Commissioning, inspection, maintenance Installing the burner (cont.)

2. Insert the burner and tighten screws G diagonally. Tighten the screws as much as necessary to ensure that the components are not damaged and function correctly throughout their service life. Observe torque settings if a torque wrench is available. Torque: 6.5 Nm
Note Before installation, check burner gasket for damage.
3. Attach Venturi extension F to fan unit.
4. Fit gas supply pipe E with a new gasket. Tighten the screws as much as necessary to ensure that the components are not damaged and function correctly throughout their service life. Observe torque settings if a torque wrench is available. Torque: 30 Nm

5. Check the gas connections for leaks.
Danger Escaping gas leads to a risk of explosion. Check the fitting for gas tightness.
6. Connect the cables/leads: Fan motor A Connect CAN bus fan to adaptor. Ionisation electrode B Ignition unit C Earth D
7. Fit cover panel.

Checking the neutralising system (if installed)

Ctehsetecrking the anode connection and anode earth current with an anode
Check that the earth cable is connected to the protective magnesium anode.
Note We recommend checking the function of the protective magnesium anode annually. This function test can be carried out without interrupting operation, by measuring the earth current with an anode tester.

5593275

54

Commissioning, inspection, maintenance Checking the anode connection and anode earth… (cont.)

A

CB

Fig. 45 1. Remove cover A (two-part design up to 26 kW). 2. Remove earth cable B from tab C.

3. Connect tester (up to 5 mA) in series between tab C and earth cable B. If the current measures > 0.3 mA the protective magnesium anode is OK. If the current measures < 0.3 mA or if there is no current at all, inspect the protective magnesium anode visually (see page 57).

Draining the boiler on the DHW side
1. Shut off the DHW supply upstream of the appliance.

5593275

55

Commissioning, inspection, maintenance Draining the boiler on the DHW side (cont.)

2. Connect the hose to the drain valve and route it into a suitable container or drain outlet.

Note Ensure adequate ventilation in the DHW pipework.

3. Turn the drain valve from lever position A (opera-

tional) to lever position B or C as required.

Lever position B: The DHW circuit in the appli-

ance excluding the DHW cylinder is drained via

the cold water connection.

Lever position C: The DHW circuit in the appli-

ance and the DHW cylinder are drained via the

hot water connection.

A

C

The cold water connection remains filled.

B
Fig. 46

Cleaning the loading cylinder
Note According to EN 806, a visual inspection and (if necessary) cleaning must be carried out no later than 2 years after commissioning, and as required thereafter.

5593275

56

Cleaning the loading cylinder (cont.)

Commissioning, inspection, maintenance

1. 8x
2.

  1. Fig. 47

1. Drain the loading cylinder.

2. Remove flange cover A.

3. Disconnect the loading cylinder from the pipework to prevent contamination from entering the pipe-
work.

4. Remove loose deposits with a pressure cleaner. Use a chemical cleaning agent to remove hard deposits that cannot be removed with a pressure cleaner.

!

Please note Do not damage the cylinder:

Only use plastic cleaning equipment to

clean the inside.

Never use cleaning agents containing

hydrochloric acid.

5. Thoroughly flush the loading cylinder after cleaning.

Checking and replacing the protective magnesium anode (if necessary)
Visual inspection of protective magnesium anode. If the anode has degraded to between 10 and 15 mm Ø, we recommend replacing the magnesium protective anode.

57

5593275

Commissioning, inspection, maintenance Re-assembling and filling the loading cylinder

D C E

B A

Fig. 48
1. Reconnect the loading cylinder to the pipework.
2. Insert new gasket A underneath flange cover B.
3. Fit flange cover B and tighten 8 screws D with a maximum torque of 25 Nm.

4. Push earth cable C onto the tab. 5. Fit cover E (two-part design up to 26 kW). 6. Fill the loading cylinder with potable water.

5593275

58

Commissioning, inspection, maintenance Checking the diaphragm expansion vessel and system pressure

A

Fig. 49 A Diaphragm expansion vessel valve

Note The expansion vessel can lose some of its charge pressure over time. If the boiler heats up, the pressure rises to 2 or 3 bar (0.2 or 0.3 MPa). The safety valve may also respond and discharge the excess pressure. Therefore check the expansion vessel pre-charge pressure annually.
Check whether the installed expansion vessel is adequate for the system water volume. Carry out this test on a cold system.
1. Drain the system until “0” is shown on the pressure indicator.
2. If the pre-charge pressure of the expansion vessel is lower than the static system pressure: Top up with nitrogen at the valve of the diaphragm expansion vessel until the pre-charge pressure is 0.1 to 0.2 bar (10 to 20 kPa) higher than the static system pressure.

3. Top up with water until the charge pressure of the cooled system is at least 1.0 bar (0.1 MPa), and is 0.1 to 0.2 bar (10 to 20 kPa) higher than the precharge pressure of the expansion vessel. Permiss. operating pressure: 3 bar (0.3 MPa)
Note The expansion vessel is supplied from the factory with a pre-charge pressure of 0.7 bar (70 kPa). Do not allow the pre-charge pressure to fall below this value (boiling noises). This also applies to single floor heating systems or attic heating centres (no static pressure). Top up with water until the charge pressure is 0.1 to 0.2 bar (10 to 20 kPa) above the pre-charge pressure.

59

5593275

Commissioning, inspection, maintenance Clehde) cking the pre-charge pressure and the DHW expansion vessel (if instal-

1. Check the static pressure of the DHW line downstream of the pressure reducer and adjust if
required. Set value: Max. 3.0 bar (0.3 MPa)

2. Close the on-site shut-off valve in the cold water line.
Relieve the water pressure.

3. Turn lever on valve to position B.

4. Check the pre-charge pressure of the DHW expansion vessel and adjust if required. Set value: Static
pressure minus 0.2 bar (20 kPa).

A

C

5. Turn lever on valve back to position A. Open the on-site shut-off valve in the cold water line.

B
Fig. 50

Checking the safety valve function

Checking the electrical connections for firm seating

Checking gas equipment for leaks at operating pressure

Danger Escaping gas leads to a risk of explosion. Check gas equipment (including inside the appliance) for gas tightness.

Note Only use suitable and approved leak detection agents (EN 14291) and devices for the leak test. Leak detection agents with unsuitable constituents (e.g. nitrides, sulphides) can cause material damage. Remove residues of the leak detection agent after testing.

Checking the combustion quality

The electronic combustion controller automatically ensures optimum combustion quality. During commissioning/maintenance, only the combustion values need to be checked. For this, measure the CO content and the CO2 or O2 content.

Note To prevent operating faults and damage, operate the appliance with uncontaminated combustion air.

Permissible CO content The CO content must be < 1000 ppm for all gas types.

5593275

60

Commissioning, inspection, maintenance Checking the combustion quality (cont.)

Permissible CO2 or O2 content

Operation with natural gas

Rated heating output (kW)

CO2 content (%)
Upper heating output

11

7.3 to 10.5

19

7.3 to 10.5

25

7.3 to 10.5

32

7.3 to 10.5

Lower heating output 7.5 to 10.5 7.5 to 10.5 7.5 to 10.5 7.5 to 10.5

O2 content (%) Upper heating output 2.1 to 7.9 2.1 to 7.9 2.1 to 7.9 2.1 to 7.9

Lower heating output 2.1 to 7.6 2.1 to 7.6 2.1 to 7.6 2.1 to 7.6

Operation with LPG CO2 content: 8.4 to 11.8 %
O2 content: 3.1 to 8.1 %

If the actual CO2 or O2 values lie outside their respec-

A

tive ranges, proceed as follows:

Check the balanced flue system for leaks; see

page 47.

Check ionisation electrode and connecting cable.

Note During commissioning, the combustion controller carries out an automatic calibration. Only measure the emissions approx. 50 s after the burner has started.

Fig. 51

1. Connect a flue gas analyser at flue gas port A on the boiler flue connection.

6. Adjust the upper heating output. See the following chapter.

2. Open the gas shut-off valve. Start the boiler. Create a heat demand.
3. Adjust the lower heating output. See the following chapter.

7. Check the CO2 content. If the actual value deviates from the permissible ranges by more than 1 %, implement steps listed above.
8. Enter the actual value into the report.

4. Check the CO2 content. If the actual value deviates from the permissible ranges, implement steps listed above.
5. Enter the actual value into the report.

9. Re-seal test port A.
Danger Escaping flue gas can damage your health. Check test port A for leaks.

Setting the upper/lower heating output Note Ensure adequate heat transfer.
Tap the following buttons: 01. and OK simultaneously for approx. 4 s, then
release.
02. Use / to select “Actuator test”.

03. OK 04. Use / to select the “Heating” group. 05. OK 06. Use / to set the max. value.
Primary circuit pump running at 100 %
61

5593275

Commissioning, inspection, maintenance Checking the combustion quality (cont.)

07. OK 08. 09. Use / to select the “Boiler” group. 10. OK 11. Use / to select the “Burner modulation
target”. 12. OK

13. Set the lower heating output: Select “Minimum heating output”. Confirm with “OK”. The burner now operates at the lower heating output.
14. Set the upper heating output: Select “Maximum heating output”. Confirm with “OK”. The burner now operates at the upper heating output.

Checking the flue system for unrestricted flow and leaks

Checking the external LPG safety valve (if installed)

Matching the control unit to the heating system

The control unit must be matched to the system equipment level. Set the parameters according to the accessories fitted:

Accessory installation instructions

Adjusting heating curves

Tap the following buttons: 01. (press for 3 sec if the display shows a house) 02. Use / to select “Settings”. 03. OK 04. Use / to select “Heating curve”. 05. OK 06. Use / to select “Heating circuit …” for the
required heating circuit.

07. OK 08. Use / to select “Slope” or “Level”. 09. OK 10. Use / to adjust the value according to the
system requirements.
11. OK to confirm

Calling up and resetting the maintenance display

Checking service messages 1. (press for 3 sec if the display shows a house) 2. Use / to select “Active messages”. 3. OK

4. Use / to select “Maintenance”.
5. OK Existing messages are displayed.

62

5593275

Commissioning, inspection, maintenance Calling up and resetting the maintenance display (cont.)

Service reset (after service has been carried out)
1. and OK simultaneously for approx. 4 s, then release.

2. Use / to select “Service messages reset”. 3. OK

Fitting the front panel

  1. Fig. 52

Instructing the system user

The system installer should hand the operating instructions to the system user and instruct the user in operating the system.

DHW hygiene
For optimum DHW hygiene, avoid DHW temperatures that are < 50 °C. For larger systems and systems with low water exchange, the temperature should not drop below < 60 °C.
Hygiene function
The DHW can be heated to a specified (higher) set DHW temperature for a period of one hour.

To activate the function, see the operating instructions. Inform the system user what DHW temperatures should be set and the risks associated with having a raised outlet temperature at the draw-off points.

63

5593275

System configuration (parameters) Calling up parameters

Parameters are split into the following groups: ­ “General” ­ “Boiler” ­ “DHW” (domestic hot water) ­ “Heating circuit 1/2/3/4” ­ “Solar”
Heating systems with one heating circuit without mixer and one or 2 heating circuits with mixer: Below, the heating circuit without mixer is designated “Heating circuit 1” and the heating circuits with mixer as “Heating circuit 2”, “Heating circuit 3” or “Heating circuit 4”. If the heating circuits have been renamed, the chosen designation appears.
Note The display and setting of some parameters is dependent on: Heat generator Connected accessories and the functions associated
with them

Tap the following buttons: 1. and OK simultaneously for approx. 4 s, then
release. 2. Use / to select “System configuration”. 3. OK 4. Use / to select the required group. 5. OK 6. Use / to select the parameter for adjust-
ment. See tables below. 7. OK 8. / for the required value. 9. OK

General

Note Parameter values in bold are factory settings.

508.0 “UTC time zone” Setting

2 ­24 to +24

Explanations
Setting of the UTC time zone in which the appliance is located.
The factory setting is UTC +1 h
Time difference adjustable from ­12 h to +12 h in increments of 0.5 h

528.0 “Set flow temperature for external demand” Setting
70 20 to 82

Explanations
Set flow temperature for external demand Set flow temperature in the delivered condition 70 °C Set flow temperature adjustable from 20 to 82 °C in 1 °C increments

896.0 “Display correction for outside temperature” Setting
0 ­10 to +10

Explanations Correction of measured outside temperature No correction Correction adjustable from ­10 to +10 K

Parameter
5593275

64

General (cont.)

System configuration (parameters)

897.0 “Screed drying” Setting Not active
Chart A Chart B Chart C Chart D Chart E Chart F

Explanations

0

Screed drying can be set in accordance with selecta-

ble temperature/time profiles. For individual profile

curves, see chapter “Function description”.

2

3

4

5

6

7

912.0 “Automatic summer/wintertime changeover”

Setting

No

0

Yes

1

Explanations Automatic changeover disabled Automatic changeover enabled

912.1 “Earliest day of changeover from winter to summertime”

Setting

Explanations

25

Changeover from 02:00 h to 03:00 h occurs on the

Sunday after or on this set date.

1 to 31

Day of changeover adjustable from 1st to 31st of the month

912.2 “Month of changeover from winter to summertime”

Setting

Explanations

3

Month of changeover: March

1 to 12

Month of changeover adjustable from January to December

912.3 “Earliest day of changeover from summer to wintertime”

Setting

Explanations

25

Changeover from 03:00 h to 02:00 h occurs on the

Sunday after or on this set date.

1 to 31

Day of changeover adjustable from 1st to 31st of the month

912.4 “Month of changeover from summer to wintertime”

Setting

Explanations

10

Month of changeover: October

1 to 12

Month of changeover adjustable from January to December

1098.4 “Gas volume correction factor” Setting

1.0000
0.7000 to 1.0000

Explanations Value is provided on the gas supplier’s bill. Used for gas consumption data.
Gas volume correction factor adjustable from 0.7000 to 1.0000 in increments of 0.0001.

5593275
Parameter

65

System configuration (parameters) General (cont.)

1098.5 “Calorific value” Setting

10.0000
5.0000 to 40.0000

Explanations Value is provided on the gas supplier’s bill. Used for gas consumption data.
Calorific value adjustable from 5.0000 to 40.0000 kWh/m3 in increments of 0.0001

1139.0 “Outside temperature limit for cancelling reduced set room temperature”

Setting

Explanations

Temperature limit for cancelling reduced set room temperature

­5

Temperature limit in the delivered condition ­5 °C

­61 to +10 Temperature limit adjustable from ­61 to +10 °C in 1 °C increments

1139.1 “Outside temperature limit for raising the reduced set room temperature to the standard set room temperature”

Setting

Explanations

Temperature limit for raising the reduced set room temperature (see function description)

­14

Temperature limit in the delivered condition ­14 °C

­60 to +10 Temperature limit adjustable from ­60 to +10 °C in 1 °C increments

1504.0 “Source for date and time” Setting

Local

0

1

Explanations
Selection of source for date and time The setting depends on the heat generator and accessories.
Factory setting: The date and time are adopted from the control unit.
Internet protocol (see parameter “508.0”)

Boiler

Note Parameter values in bold are factory settings.

521.0 “Time interval in burner hours until the next service”

Setting

Explanations

Number of burner hours to run until next service

0

0 to 25500 Burner hours until next service adjustable from 0 to 25500

Parameter
5593275

66

Boiler (cont.)

System configuration (parameters)

522.3 “Interval until the next service” Setting
0 1 2 3 4 5

Explanations Interval until the next service No interval selected 3 months 6 months 12 months 18 months 24 months

596.0 “Maximum heating output” Setting

100 0 to 100

Explanations
A limit can be set on the maximum heating output for heating mode. Heating output in the delivered condition 100 % Adjustable from 0 to 100 %

597.0 “Limit, max. heating output for DHW heating” Setting
100 0 to 100

Explanations
A limit can be set on the maximum heating output for DHW heating. Heating output in the delivered condition 100 % Adjustable from 0 to 100 %

1100.2 “Set speed of the primary circuit pump in heating mode”

Setting

Explanations

Target speed of internal circulation pump In heating operation With external demand With demand in conjunction with a low loss header

Factory settings defined by settings specific to the ap-

pliance

The setting range depends on the appliance

1240.0 “Operating mode of primary circuit pump” Setting

Explanations

1 7

1411.0 “Clear maintenance messages” Setting

No

0

Yes

1

“Automatic” Switched on regardless of current temperature level Shutdown in reduced mode (in conjunction with continuous operation or when no demand via room thermostat)
Explanations Clear maintenance messages once maintenance has been performed. Maintenance messages are active (if present). Clear maintenance messages once.

5593275
Parameter

67

System configuration (parameters) Boiler (cont.)

1432.1 “Residual head control of primary circuit pump”

Setting

Explanations

Residual head limit value for reducing pump speed of the internal circulation pump, in mbar

0

Internal circulation pump is controlled in line with the

outside temperature

1 to 255

Internal circulation pump is operated with constant residual head. Recommended setting: 120 mbar 1 step 1 mbar

1432.2 “Operating mode of primary circuit pump” Setting
0
1 to 20

Explanations
Internal circulation pump is operated with constant differential pressure.
Internal circulation pump is operated with rising differential pressure. Adjustable from 1 to 20 mbar

1503.0 “Minimum heating output” Setting

… 5 to 100

Explanations
A limit can be set on the minimum heating output for heating mode.
Delivered condition specified by settings specific to the appliance
Adjustable from 5 to 100 %

1606.0 “Minimum burner pause time” Setting
0 1

Explanations
The minimum burner pause time can be set subject to boiler load.
Fixed setting for minimum burner pause time
Delivered condition, integral method (see parameter 1606.4)

1606.4 “Integral threshold for burner switch-off” Setting
50 5 to 255

Explanations
Only effective if parameter 1606.0 has been set to 1. Factory setting 50 K x min Adjustable from 5 to 255 K x min The higher the value, the later the burner switches off.

DHW
Note Parameter values in bold are factory settings.

Parameter
5593275

68

DHW (cont.)

System configuration (parameters)

497.0 ” Operating mode of DHW circulation pump” Setting
0 4

Explanations DHW circulation pump: Time program Selected cycle (see parameter 497.3)

497.1 “DHW circulation pump for hygiene function” Setting

OFF

0

ON

1

Explanations
Activation criterion for the DHW circulation pump when the function “Increased DHW hygiene” is active
According to time program
Switched on if function “Increased DHW hygiene” is active

Danger High DHW temperatures may cause scalding. Where necessary implement on- site meas-
ures. E.g. install automatic thermostatic mixing valves in the DHW pipe. Inform the system operator. Admix cold water at the draw-off points.

497.2 “DHW circulation pump for DHW heating” Setting

OFF

0

ON

1

497.3 “Number of cycles DHW circulation pump” Setting

0 1 2 3 4 5

Explanations Activation criterion for DHW circulation pump According to time program ON during DHW heating to set cylinder temperature
Explanations Within the time phase, the DHW circulation pump is switched on cyclically for 5 min at a time. Number of switching cycles per hour: 1 switching cycle 2 switching cycles 3 switching cycles 4 switching cycles 5 switching cycles 6 switching cycles

5593275
Parameter

69

System configuration (parameters) DHW (cont.)
503.0 “Scald protection” Setting

OFF

0

ON

1

Explanations The adjustable water temperature is limited to a maximum value. Scald protection OFF
Danger Risk of injury due to increased DHW temperature. Inform the system user of the risk from the higher outlet temperature at the taps.
Scald protection ON (maximum DHW temperature 60 °C)
Note Even with the scald protection switched on, higher outlet temperatures may occur at the draw-off points in the following cases: With active hygiene function While the appliance is being calibrated

Parameter
5593275

1087.0 “Max. duration, DHW heating” Setting

240 0 1 to 240

Explanations
After a set period of time has elapsed, DHW heating ends even though the set DHW temperature has not yet been reached. Not adjustable on gas condensing combi boilers
Factory setting 240 min
No time limit for DHW heating
Duration of DHW heating adjustable from 1 to 240 min in 1 min increments

1087.1 “Min. delay until next DHW heating” Setting

Explanations
Minimum delay before DHW heating starts again, even though there is a demand.

Note Function becomes effective when the set “Max. duration, DHW heating” (1087.0) is exceeded.

60 60 to 240

Cannot be adjusted on gas condensing combi boilers
Delivered condition, delay of 60 min
Delay adjustable from 60 to 240 min in 1 min increments

1101.2 “Set speed of the primary circuit pump for DHW heating”

Setting

Explanations

Target speed of the internal circulation pump when operated as a DHW pump

Factory settings defined by settings specific to the ap-

pliance

The setting range depends on the appliance.

70

System configuration (parameters) Heating circuit 1, Heating circuit 2, Heating circuit 3, Heating circuit 4

Note Parameter values in bold are factory settings.

424.3 “Set flow temperature increased when switching from operation with reduced room temperature to

operation with standard/comfort room temperature, heating circuit 1”

Setting

Explanations

Set flow temperature increased when changing from operation at reduced room temperature to operation at standard room temperature or comfort room temperature. See also chapter “Function description”

0 K

0

Delivered condition increase 0 K

0 to 20

Temperature rise adjustable from 0 to 20 K

424.4 “Duration for set flow temperature increase, heating circuit 1”

Setting

Explanations

Duration for set flow temperature increase See also chapter “Function description”

60 min

60

Delivered condition 60 min

0 to 120 Temperature rise adjustable from 0 to 120 min

426.3 “Set flow temperature increased when switching from operation with reduced room temperature to

operation with standard/comfort room temperature, heating circuit 2”

Setting

Explanations

Set flow temperature increased when changing from operation at reduced room temperature to operation at standard room temperature or comfort room temperature. See also chapter “Function description”

0 K

0

Delivered condition increase 0 K

0 to 20

Temperature rise adjustable from 0 to 20 K

426.4 “Duration for set flow temperature increase, heating circuit 2”

Setting

Explanations

Duration for set flow temperature increase See also chapter “Function description”

60 min

60

Delivered condition 60 min

0 to 120 Temperature rise adjustable from 0 to 120 min

428.3 “Set flow temperature increased when switching from operation with reduced room temperature to operation with standard/comfort room temperature, heating circuit 3”

Setting

Explanations

Set flow temperature increased when changing from operation at reduced room temperature to operation at standard room temperature or comfort room temperature. See also chapter “Function description”

0 K

0

Delivered condition increase 0 K

0 to 20

Temperature rise adjustable from 0 to 20 K

5593275
Parameter

71

System configuration (parameters) Heating circuit 1, Heating circuit 2, Heating… (cont.)

Parameter
5593275

428.4 “Duration for set flow temperature increase, heating circuit 3”

Setting

Explanations

Duration for set flow temperature increase See also chapter “Function description”

60 min

60

Delivered condition 60 min

0 to 120 Temperature rise adjustable from 0 to 120 min

430.3 “Set flow temperature increased when switching from operation with reduced room temperature to

operation with standard/comfort room temperature, heating circuit 4”

Setting

Explanations

Set flow temperature increased when changing from operation at reduced room temperature to operation at standard room temperature or comfort room temperature. See also chapter “Function description”

0 K

0

Delivered condition increase 0 K

0 to 20

Temperature rise adjustable from 0 to 20 K

430.4 “Duration for set flow temperature increase, heating circuit 4”

Setting

Explanations

Duration for set flow temperature increase See also chapter “Function description”

60 min

60

Delivered condition 60 min

0 to 120 Temperature rise adjustable from 0 to 120 min

933.3 “Priority, DHW heating, heating circuit 1” Setting

Off

0

DHW

1

Explanations
Priority of DHW heating over the heating circuit No priority for DHW heating (only if the DHW cylinder is installed downstream of the low loss header) With DHW heating priority

933.6 “Operating mode of heating circuit 1” Setting
Weather-compensated without room tem- 4 perature hook-up Weather-compensated with room tempera- 7 ture hook-up

Explanations
Only adjust for systems with one heating circuit. Heating mode:
Weather-compensated without room temperature influence
Weather-compensated with room temperature influence (see also parameter 933.7)

933.7 “Room influence factor, heating circuit 1” Setting
8 0 to 64

Explanations
The higher the value, the greater the influence of the room temperature on the set flow temperature of the heating circuit (heating curve). Operation with room temperature hook-up must be set for the heating circuit (parameter 933.6). Only change the value for systems with one heating circuit. For a sample calculation, see chapter “Heating curve” in the “Function description”
Room influence factor
Room influence adjustable from 0 to 64

72

Heating circuit 1, Heating circuit 2, Heating… (cont.)

System configuration (parameters)

934.3 “Priority, DHW heating, heating circuit 2” Setting

OFF

0

DHW

1

934.5 “Differential temperature, heating circuit 2” Setting

8 K

8

0 to 20

934.6 “Operating mode of heating circuit 2” Setting

Weather-compensated without room tem- 4 perature hook-up
Weather-compensated with room tempera- 7 ture hook-up

934.7 “Room influence factor, heating circuit 2” Setting

8 0 to 64
935.3 “Priority, DHW heating, heating circuit 3” Setting

OFF

0

DHW

1

Explanations Priority of DHW heating over heating circuit pump and mixer No priority for DHW heating (only if the DHW cylinder is installed downstream of the low loss header) With DHW heating priority
Explanations The flow temperature of the heat generator is higher than the flow temperature of the heating circuit with mixer by an adjustable differential temperature. See also chapter “Function description”. Differential temperature in delivered condition 8 K Differential temperature adjustable from 0 to 20 K
Explanations Heating mode: Weather-compensated without room temperature influence Weather-compensated with room temperature influence See also parameter 934.7
Explanations The higher the value, the greater the influence of the room temperature on the set flow temperature of the heating circuit (heating curve). Operation with room temperature hook-up must be set for the heating circuit (parameter 934.6). Change value for heating circuit with mixer only. For a sample calculation, see chapter “Heating curve” in the “Function description” Room influence factor Room influence adjustable from 0 to 64
Explanations Priority of DHW heating over heating circuit pump and mixer No priority for DHW heating (only if the DHW cylinder is installed downstream of the low loss header) With DHW heating priority

5593275
Parameter

73

System configuration (parameters) Heating circuit 1, Heating circuit 2, Heating… (cont.)

935.5 “Differential temperature, heating circuit 3” Setting

8 K

8

0 to 20

935.6 “Operating mode of heating circuit 3” Setting

Weather-compensated without room tem- 4 perature hook-up
Weather-compensated with room tempera- 7 ture hook-up

935.7 “Room influence factor, heating circuit 3” Setting

8 0 to 64
936.3 “Priority, DHW heating, heating circuit 4” Setting

Off

0

DHW

1

936.5 “Differential temperature, heating circuit 4” Setting

8 K

8

0 to 20

Explanations The flow temperature of the heat generator is higher than the flow temperature of the heating circuit with mixer by an adjustable differential temperature. See also chapter “Function description”. Differential temperature in delivered condition 8 K Differential temperature adjustable from 0 to 20 K
Explanations Heating mode: Weather-compensated without room temperature influence Weather-compensated with room temperature influence See also parameter 935.7
Explanations The higher the value, the greater the influence of the room temperature on the set flow temperature of the heating circuit (heating curve). Operation with room temperature hook-up must be set for the heating circuit (parameter 935.6). Change value for heating circuit with mixer only. For a sample calculation, see chapter “Heating curve” in the “Function description” Room influence factor Room influence adjustable from 0 to 64
Explanations Priority of DHW heating over heating circuit pump and mixer No priority for DHW heating (only if the DHW cylinder is installed downstream of the low loss header) With DHW heating priority
Explanations The flow temperature of the heat generator is higher than the flow temperature of the heating circuit with mixer by an adjustable differential temperature. See also chapter “Function description”. Differential temperature in delivered condition 8 K Differential temperature adjustable from 0 to 20 K

Parameter
5593275

74

Heating circuit 1, Heating circuit 2, Heating… (cont.)

System configuration (parameters)

936.6 “Operating mode heating circuit 4” Setting
Weather-compensated without room tem- 4 perature hook-up Weather-compensated with room tempera- 7 ture hook-up

Explanations
See also parameter 936.7 Heating mode:
Weather-compensated without room temperature influence
Weather-compensated with room temperature influence

936.7 “Room influence factor, heating circuit 4” Setting
8 0 to 64

Explanations
The higher the value, the greater the influence of the room temperature on the set flow temperature of the heating circuit (heating curve). Operation with room temperature hook-up must be set for the heating circuit (parameter 936.6). Change value for heating circuit with mixer only. For a sample calculation, see chapter “Heating curve” in the “Function description”
Room influence factor
Room influence adjustable from 0 to 64

1102.0 “Min. speed of speed-controlled primary/heating circuit pump in standard mode, heating circuit 1”

Setting

Explanations

Minimum speed of the internal circulation pump in heating mode with standard room temperature

Delivered condition specified by settings specific to

the heat generator

Setting range depends on the appliance.

1102.1 “Max. speed of speed-controlled primary/heating circuit pump in standard mode, heating circuit 1”

Setting

Explanations

Maximum speed of the internal circulation pump in heating mode with standard room temperature

Delivered condition specified by settings specific to

the heat generator

Setting range depends on the appliance.

1192.0 “Minimum flow temperature limit, heating circuit 1”

Setting

Explanations

Minimum flow temperature limit for the heating circuit

20 °C

20

Min flow temperature 20 °C

1 to 90

Setting range limited by parameters, depending on appliance variant

1192.1 “Maximum flow temperature limit, heating circuit 1”

Setting

Explanations

Maximum flow temperature limit for the heating circuit

74 °C

74

Max. flow temperature 74 °C

10 to 100 Setting range limited by parameters, depending on appliance variant

5593275
Parameter

75

System configuration (parameters) Heating circuit 1, Heating circuit 2, Heating… (cont.)

1193.0 “Minimum flow temperature limit, heating circuit 2”

Setting

Explanations

Minimum flow temperature limit for the heating circuit

20 °C

20

Min flow temperature 20 °C

1 to 90

Setting range limited by parameters, depending on appliance variant

1193.1 “Maximum flow temperature limit, heating circuit 2”

Setting

Explanations

Maximum flow temperature limit for the heating circuit

74 °C

74

Max. flow temperature 74 °C

10 to 100 Setting range limited by parameters, depending on appliance variant

1194.0 “Minimum flow temperature limit, heating circuit 3”

Setting

Explanations

Minimum flow temperature limit for the heating circuit

20 °C

20

Min flow temperature 20 °C

1 to 90

Setting range limited by parameters, depending on appliance variant

1194.1 “Maximum flow temperature limit, heating circuit 3”

Setting

Explanations

Maximum flow temperature limit for the heating circuit

74 °C

74

Max. flow temperature 74 °C

10 to 100 Setting range limited by parameters, depending on appliance variant

1195.0 “Minimum flow temperature limit, heating circuit 4”

Setting

Explanations

Minimum flow temperature limit for the heating circuit

20 °C

20

Min flow temperature 20 °C

1 to 90

Setting range limited by parameters, depending on appliance variant

1195.1 “Maximum flow temperature limit, heating circuit 4”

Setting

Explanations

Maximum flow temperature limit for the heating circuit

74 °C

74

Max. flow temperature 74 °C

10 to 100 Setting range limited by parameters, depending on appliance variant

Parameter
5593275

76

Heating circuit 1, Heating circuit 2, Heating… (cont.)

System configuration (parameters)

1395.1 “Heating limit: Economy function, outside temperature, heating circuit 1”

Setting

Explanations

Heating circuit pump logic function (summer economy control): Heating circuit pump switches off when outside temperature is 1 K above selected value. Heating circuit pump switches back on when outside temperature is 1 K below selected value.

25 °C

25

Heating limit at outside temperature 25 °C

10 to 35 Heating limit adjustable from 10 to 35 °C

1396.1 “Heating limit: Economy function, outside temperature, heating circuit 2”

Setting

Explanations

Heating circuit pump logic function (summer economy control): Heating circuit pump switches off when outside temperature is 1 K above selected value. Heating circuit pump switches back on when outside temperature is 1 K below selected value.

25 °C

25

Heating limit at outside temperature 25 °C

10 to 35 Heating limit adjustable from 10 to 35 °C

1397.1 “Heating limit: Economy function, outside temperature, heating circuit 3”

Setting

Explanations

Heating circuit pump logic function (summer economy control): Heating circuit pump switches off when outside temperature is 1 K above selected value. Heating circuit pump switches back on when outside temperature is 1 K below selected value.

25 °C

25

Heating limit at outside temperature 25 °C

10 to 35 Heating limit adjustable from 10 to 35 °C

1398.1 “Heating limit: Economy function, outside temperature, heating circuit 4”

Setting

Explanations

Heating circuit pump logic function (summer economy control): Heating circuit pump switches off when outside temperature is 1 K above selected value. Heating circuit pump switches back on when outside temperature is 1 K below selected value.

25 °C

25

Heating limit at outside temperature 25 °C

10 to 35 Heating limit adjustable from 10 to 35 °C

Energy saving functions (setting only via software tool)

1791.0 “3-way valve target position” Setting
1. Heating 2. Central position 3. DHW

Explanations
The 3-way valve assumes the set position when there is no demand from heating operation or DHW heating.

5593275
Parameter

77

System configuration (parameters) Heating circuit 1, Heating circuit 2, Heating… (cont.)

2426.1 “Weather-compensated heating circuit pump logic for heating circuit 1” (only for weather-compen-

sated control units)

Setting

Explanations

Setting

If the outside temperature rises above the threshold

range -9 to value (set room temperature plus offset in K), the

+5 °C

heating circuit pump is switched off.

If the outside temperature falls below the threshold

value (set room temperature plus offset in K), the

heating circuit pump is switched on.

2426.3 “Room temperature-dependent heating circuit pump logic for heating circuit 1” (only for weather-

compensated control units with room temperature hook-up).

Setting

Explanations

Only activate this function for the heating circuit with mixer or if there is only one direct heating circuit in the system.

Setting

If the actual room temperature rises above the thresh-

range -2 to old value (set room temperature plus offset in K), the

+5 °C

heating circuit pump is switched off.

If the actual room temperature falls below the thresh-

old value (set room temperature plus offset in K), the

heating circuit pump is switched on.

2427.1 “Weather-compensated heating circuit pump logic for heating circuit 2” (only for weather-compensated control units).

Setting

Explanations

Setting

If the outside temperature rises above the threshold

range -9 to value (set room temperature plus offset in K), the

+5 °C

heating circuit pump is switched off.

If the outside temperature falls below the threshold

value (set room temperature plus offset in K), the

heating circuit pump is switched on.

2427.3 “Room temperature-dependent heating circuit pump logic for heating circuit 2” (only for weathercompensated control units with room temperature hook-up).

Setting

Explanations

Only activate this function for the heating circuit with mixer or if there is only one direct heating circuit in the system.

Setting

If the actual room temperature rises above the thresh-

range -2 to old value (set room temperature plus offset in K), the

+5 °C

heating circuit pump is switched off.

If the actual room temperature falls below the thresh-

old value (set room temperature plus offset in K), the

heating circuit pump is switched on.

2428.1 “Weather-compensated heating circuit pump logic for heating circuit 3” (only for weather-compen-

sated control units).

Setting

Explanations

Setting

If the outside temperature rises above the threshold

range -9 to value (set room temperature plus offset in K), the

+5 °C

heating circuit pump is switched off.

If the outside temperature falls below the threshold

value (set room temperature plus offset in K), the

heating circuit pump is switched on.

Parameter
5593275

78

Heating circuit 1, Heating circuit 2, Heating… (cont.)

System configuration (parameters)

2428.3 “Room temperature-dependent heating circuit pump logic for heating circuit 3” (only for weather-

compensated control units with room temperature hook-up).

Setting

Explanations

Only activate this function for the heating circuit with mixer or if there is only one direct heating circuit in the system.

Setting

If the actual room temperature rises above the thresh-

range -2 to old value (set room temperature plus offset in K), the

+5 °C

heating circuit pump is switched off.

If the actual room temperature falls below the thresh-

old value (set room temperature plus offset in K), the

heating circuit pump is switched on.

2429.1 “Weather-compensated heating circuit pump logic for heating circuit 4” (only for weather-compen-

sated control units).

Setting

Explanations

Setting

If the outside temperature rises above the threshold

range -9 to value (set room temperature plus offset in K), the

+5 °C

heating circuit pump is switched off.

If the outside temperature falls below the threshold

value (set room temperature plus offset in K), the

heating circuit pump is switched on.

2429.3 “Room temperature-dependent heating circuit pump logic for heating circuit 4” (only for weathercompensated control units with room temperature hook-up).

Setting

Explanations

Only activate this function for the heating circuit with mixer or if there is only one direct heating circuit in the system.

Setting

If the actual room temperature rises above the thresh-

range -2 to old value (set room temperature plus offset in K), the

+5 °C

heating circuit pump is switched off.

If the actual room temperature falls below the thresh-

old value (set room temperature plus offset in K), the

heating circuit pump is switched on.

Frost protection configuration (setting only via software tool)

2855.1 “Additional (passive) frost protection configuration, heating circuit 1”

Setting

Explanations

1

= 1 °C

Setting range: -9 °C to +3 °C If the outside temperature falls below the set outside temperature limit, the corresponding heating circuit pump switches on (applies only to weather-compensated operation).

2856.1 “Additional (passive) frost protection configuration, heating circuit 2”

Setting

Explanations

1

= 1 °C

Setting range: -9 °C to +3 °C If the outside temperature falls below the set outside temperature limit, the corresponding heating circuit pump switches on (applies only to weather-compensated operation).

5593275
Parameter

79

System configuration (parameters) Heating circuit 1, Heating circuit 2, Heating… (cont.)

2857.1 “Additional (passive) frost protection configuration, heating circuit 3”

Setting

Explanations

1

= 1 °C

Setting range: -9 °C to +3 °C If the outside temperature falls below the set outside temperature limit, the corresponding heating circuit pump switches on (applies only to weather-compensated operation).

2858.1 “Additional (passive) frost protection configuration, heating circuit 4”

Setting

Explanations

1

= 1 °C

Setting range: -9 °C to +3 °C If the outside temperature falls below the set outside temperature limit, the corresponding heating circuit pump switches on (applies only to weather-compensated operation).

Subscriber numbers of connected extensions
All extensions connected to the heat generator (except the SDIO/SM1A electronics module) must have a subscriber number. The subscriber number is set on rotary switch S1 at each extension.

Parameter
5593275

Fig. 53 80

Subscriber numbers of connected extensions (cont.)

System configuration (parameters)

Rotary switch S1 settings: EM-S1 extension (system with solar collectors): 0 EM-EA1 extension (max. 3 extensions in one sys-
tem) Consecutive no. (any sequence): 1 up to 3 EM-P1 extension ­ If no heating circuits with mixer are available in the
system: 1 ­ If heating circuits with mixer (EM-M1 or EM-MX
extensions) are present in the system: Always set subscriber number for EM-P1 extension to the consecutive number after EM-M1 or EM-MX extensions. EM-M1 or EM-MX extensions ­ Heating circuit 2 with mixer: Rotary switch on extension kit to 1 ­ Heating circuit 3 with mixer: Rotary switch on extension kit to 2

Note EM-EA1 extensions may have the same subscriber number as the EM-P1, EM-M1 or EM-MX extensions. The following table shows an example of how a system may be equipped.

Function
System with solar collectors Heating circuit 2 with mixer Heating circuit 3 with mixer Heating circuit 4 with mixer Heating circuit 1 without mixer (circulation pump downstream of low loss header) Function extensions (e.g.): Fault message input Fault message output Operating mode changeover

Electronics module ADIO ADIO ADIO ADIO ADIO

Extension
EM-S1 EM-M1/EM-MX EM-M1/EM-MX EM-M1/EM-MX EM-P1

DIO

EM-EA1

DIO

EM-EA1

DIO

EM-EA1

Setting Rotary switch S1 0 1 2 3 4
1 2 3

5593275
Parameter

81

Diagnosis and service checks Service menu

Calling up the service menu
Tap the following buttons:
1. and OK simultaneously for approx. 4 s, then release.
2. Select the required menu section, e.g. “Connect with software tool”.
Note Not all menu areas will be available, depending on the system equipment level.
Service menu overview

Note Tap ” ” to return to the “Service main menu”

Service Active messages Reset service messages Connect with software tool Diagnostics
General Burner Heating circuit 1 Heating circuit 2 Heating circuit 3 Heating circuit 4 DHW Solar WiFi

Actuator test System configuration Message history Basic settings
Factory settings Commissioning assistant

Recognised devices Exit trade fair mode

Diagnosis
5593275

Diagnosis

Checking operating data
Operating data can be checked in various areas. See “Diagnosis” in the service menu overview. Operating data on heating circuits with mixer can only be called up if such components are installed in the system.
82

Note If a called up sensor is faulty, “- – -” appears on the display.

Diagnosis (cont.)

Diagnosis and service checks

Calling up operating data
Tap the following buttons:
1. and OK ­ press simultaneously for approx. 4 s, then release.
2. Use / to select “Diagnosis”.

3. OK 4. Use / to select the required group. 5. OK 6. Select the required information with / .

5593275
Diagnosis

Checking outputs (actuator test)

Note When the actuator test is started, all actuators are initially disabled and valves moved to their central position.

06. OK
07. Use / below.

to select the actuator. See the table

Tap the following buttons:

08. OK

01. and OK simultaneously for approx. 4 s, then release.
02. “Actuator test”
03. OK

09. / for the required value. 10. OK
Note The function is active for 30 min.

04. OK to confirm the message.

11. Use to end the Actuator test.

05. Use / to select the required group.

The following actuator functions can be controlled subject to the system and appliance equipment level:

Display

Explanation

Boiler group

Fan speed

Set value

Burner fan speed in rpm (rotations/minute)

Burner modulation, set value

Off Minimum
heating output Maximum heating output Maximum DHW output

Modulation level (in accordance with specific heat generator settings)

3-way valve target posi- Heating

tion

Middle

3-way diverter valve set to heating mode 3-way diverter valve in central position (filling/draining)

DHW

3-way diverter valve set to DHW heating

Heating group

Primary circuit pump speed

Set value

Internal circulation pump speed in %

3-way valve target posi- Heating

tion

Middle

3-way diverter valve set to heating mode 3-way diverter valve in central position (filling/draining)

DHW

3-way diverter valve set to DHW heating

Heating circuit 1 pump Set value speed

Speed, heating circuit pump, heating circuit 1 without mixer in %

Heating circuit 2 pump Set value speed

Speed, heating circuit pump, heating circuit 2 with mixer in %

83

Diagnosis and service checks Checking outputs (actuator test) (cont.)

Display

Heating circuit 3 pump Set value speed

Heating circuit 4 pump Set value speed

Mixer, heating circuit 2 Open

Stop

Close

Mixer, heating circuit 3 Open

Stop

Close

Mixer, heating circuit 4 Open

Stop

Close

DHW group (domestic hot water)

Primary circuit pump, set speed

Set value

3-way valve target posi- Heating

tion

Middle

DHW

Cylinder loading pump On

Off

DHW circulation pump On

Off

Transfer pump hygiene On

function

Off

Circulation pump for cyl- On

inder heating

Off

Solar group

Solar circuit pump, set Set value speed

Transfer pump hygiene On

function

Off

Solar circulation pump On

Off

Solar 3-way valve, tar- Open

get position

Close

Stop

Explanation Speed, heating circuit pump, heating circuit 3 with mixer in % Speed, heating circuit pump, heating circuit 4 with mixer in % Output for “Mixer open” enabled (mixer extension kit) Current position is maintained Output for “Mixer close” enabled Output for “Mixer open” enabled (mixer extension kit) Current position is maintained Output for “Mixer close” enabled Output for “Mixer open” enabled (mixer extension kit) Current position is maintained Output for “Mixer close” enabled
Internal circulation pump in % 3-way diverter valve set to heating mode 3-way diverter valve in central position (filling/draining) 3-way diverter valve set to DHW heating
Speed, solar circuit pump in %

Diagnosis
5593275

84

Fault display on the programming unit

Troubleshooting

If there is a fault, the display shows “Burner fault” or “Active messages”.
Note If a central fault message facility is connected, this is switched on.

If “Connection error” appears on the display: Check connecting cable and plug between HMU heat management unit and HMI programming unit.

Calling up fault messages

Tap the following buttons:

5. OK

1. ” ” (press for 3 sec if the display shows a house)
2. / for: “Details”, if burner faults are present. “Active messages”, if further faults are present.

6. / for the required message For an explanation of the fault codes, see the following table.
7. OK

3. OK

8. ” ” for “Error”

4. / for “Error” to display all fault messages.

9. / to call up further messages

Acknowledging the fault display 1. ” ” (press for 3 sec if the display shows a house) 2. / for “Active message” 3. OK 4. / for “Error” to display all fault messages. 5. OK 6. / for “Acknowledge” to acknowledge all
fault messages. Note Service messages are also acknowledged.

Note Any connected central fault message facility is switched off. If an acknowledged fault is not remedied, the fault message will be redisplayed the following day at 07:00 h, and the fault message facility restarts.

Calling up acknowledged fault messages Tap the following buttons: 1. ” ” 2. / for “Active messages”. 3. OK 4. / for “Error”

5. OK
Note When troubleshooting, always observe the subscriber number of the component. Check the component displayed. Remedy fault if applicable. The subscriber number of the component depends on the position of rotary switch S1 on the corresponding extension module. The rotary switch position was set during installation. To identify the affected module, check the position of rotary switch S1 on the module if required.
The following is displayed: Date and time of the occurrence of the fault Fault code

5593275
Service

85

Troubleshooting Fault display on the programming unit (cont.)

Description of the fault

Subscriber number of the component on which the

fault has occurred:

PlusBus subscriber components

0

EM-S1 extension (ADIO electronics mod-

ule)

1 to 15 EM-M1, EM-MX and EM-P1 extensions

(ADIO electronics module)

17 to 31 EM-EA1 extension (DIO electronics mod-

ule)

32 to 47 Cylinder module, extensions (electronics

module M2IO)

48 to 63 Vitotrol 200-E

64

SDIO/SM1A electronics module

CAN BUS subscriber components

1 HMU heat management unit

50 BCU burner control unit

58 Communication module (TCU 200)

59 HMI programming unit

60 Fan unit

90 Gateway

Low power radio subscriber components

48 to 63 Vitotrol 300-E

Calling up fault messages from the fault memory (message history)

The 10 most recent faults (including those remedied) and service messages are saved and can be called up. Faults are sorted by date.
Tap the following buttons:
1. and OK simultaneously

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

VIESSMANN User Manuals

Related Manuals