Pepperl Fuchs FB6208C Digital Output With Shutdown Input Instructions
- June 13, 2024
- Pepperl Fuchs
Table of Contents
Digital Output with Shutdown Input FB6208C
- 8-channel
- Outputs Ex ib
- Installation in suitable enclosures in Zone 1
- Module can be exchanged under voltage (hot swap)
- Galvanic group isolation
- Line fault detection (LFD)
- Positive or negative logic selectable
- Simulation mode for service operations (forcing)
- Permanently self-monitoring
- Output with watchdog
- Output with bus-independent safety shutdown
Function
The device features 8 independent channels.
The device can be used to drive low power solenoids, sounders, or LEDs.
Open and short-circuit line faults are detected.
The outputs are galvanically isolated from the bus and the power supply.
The outputs can be switched off via a contact. This can be used for bus-
independent safety applications.
Connection
Technical Data
Slots
Occupied slots| | 2
Functional safety related parameters
Safety Integrity Level (SIL)| | SIL 2
Performance level (PL)| | PL d
Supply
Connection| | backplane bus
Rated voltage| Ur| 12 V DC , only in connection with the power supplies FB92**
Power dissipation| | 2.35 W
Power consumption| | 2.35 W
Internal bus
Connection| | backplane bus
Interface| | manufacturer-specific bus to standard com unit
Digital output
Number of channels| | 8
Suitable field devices
Field device| | Solenoid Valve
Field device [2]| | audible alarm
Field device [3]| | visual alarm
Connection| | channel I: 1+, 2-; channel II: 3+, 4-; channel III: 5+, 6-;
channel IV: 7+, 8-; channel V: 9+, 10-; channel VI: 11+, 12-; channel VII:
13+, 14-; channel VIII: 15+, 16-
Current limit
| Imax| 5.2 mA
Open loop voltage
| Us| 21.6 V
Line fault detection| | can be switched on/off for each channel via
configuration tool
Test current| | 0.33 mA
Short-circuit| | < 300 Ω
Open-circuit| | > 50 kΩ
Response time| | 20 ms (depending on bus cycle time)
Watchdog| | within 0.5 s the device goes in safe state, e.g. after loss of
communication
Indicators/settings
LED indication| | LED green: supply
LED red: line fault , communication error red flashing
Coding| | optional mechanical coding via front socket
Directive conformity
Electromagnetic compatibility| |
Directive 2014/30/EU| | EN 61326-1:2013
Conformity
Electromagnetic compatibility| | NE 21
Degree of protection| | IEC 60529
Environmental test| | EN 60068-2-14
Shock resistance| | EN 60068-2-27
Vibration resistance| | EN 60068-2-6
Damaging gas| | EN 60068-2-42
Relative humidity| | EN 60068-2-78
Ambient conditions
Ambient temperature| | -20 … 60 °C (-4 … 140 °F)
Storage temperature| | -25 … 85 °C (-13 … 185 °F)
Relative humidity| | 95 % non-condensing
Shock resistance| | shock type I, shock duration 11 ms, shock amplitude 15 g,
number of shocks 18
ibration reistance| | frequency range 10 … 150 Hz; transition frequency: 57.56
Hz, amplitude/acceleration ± 0.075 mm/1 g; 10 cycles
frequency range 5 … 100 Hz; transition frequency: 13.2 Hz
mplitude/acceleration ± 1 mm/0.7 g; 90 minutes at each resonance
Damaging gas| | designed for operation in environmental conditions acc. to
ISA-S71.04-1985, severity level G3
Mechanical specifications
Degree of protection| | IP20 (module) , a separate housing is required acc. to
the system description
Connection| | removable front connector with screw flange (accessory)
wiring connection via spring terminals (0.14… 1.5 mm2) or screw terminals
(0.08…. 1.5 mm2)
Mass| | approx. 750 g
Dimensions| | 57 x 107 x 132 mm (2.2 x 4.2 x 5.2 inch)
Data for application in connection with hazardous areas
EU-type examination certificate| | PTB 97 ATEX 1074 U
Marking| | 1 II 2 G Ex d [ib] IIC Gb
1 II (2) D [Ex ib Db] IIIC
Output
Voltage| Uo| 30 V
Current| Io| 13.5 mA
Power| Po| 404 mW (characteristic curve rectangular type)
Galvanic isolation
Output/power supply, internal bus| | safe electrical isolation acc. to EN
60079-11, voltage peak value 375 V
Directive conformity
Directive 2014/34/EU| | EN IEC 60079-0:2018+AC:2020 EN 60079-1:2014
EN 60079-11:2012
International approvals
ATEX approval| | PTB 97 ATEX 1075 ; PTB 97 ATEX 1074 U
General information
System information| | The module has to be mounted in appropriate backplanes
and housings (FB92**) in Zone 1, 2, 21, 22 or outside hazardous areas (gas or
dust). Here, observe the corresponding EC-type examination certificate.
Supplementary information| | EC-Type Examination Certificate, Statement of
Conformity, Declaration of Conformity,
Attestation of Conformity and instructions have to be observed where
applicable. For
information see www.pepperl-fuchs.com.
Assembly
Accessories
FB9224* | Field Unit |
---|---|
FB9225* | Redundancy Field Unit |
FB9248* | Field Unit |
Refer to “General Notes Relating to Pepperl+Fuchs Product Information”.
Release date: 2022-07-06
Date of issue: 2022-07-06
Filename: 542157_eng.pdf
Pepperl+Fuchs Group
www.pepperl-fuchs.com
USA: +1 330 486 0002
pa-info@us.pepperl-fuchs.com
Germany: +49 621 776 2222
pa-info@de.pepperl-fuchs.com
Singapore: +65 6779 9091
pa-info@sg.pepperl-fuchs.com