PEPPERL FUCHS LB7004A-254846 Universal Input/Output Instructions

June 13, 2024
Pepperl Fuchs

PEPPERL FUCHS LB7004A-254846 Universal InputOutput

PEPPERL FUCHS LB7004A-254846 Universal InputOutput

Introduction

  • 4-channel
  • Analog input, digital input, analog output, digital output
  • Installation in Zone 2 or safe area
  • Supply circuit 21.5 V (4 mA)
  • HART communication via field bus or service bus
  • Simulation mode for service operations (forcing)
  • Line fault detection (LFD): one LED per channel
  • Permanently self-monitoring
  • Module can be exchanged under voltage

Symbol

Function

The device is a configurable universal module. Each channel can operate in the following modes:

  • As an analog input (AI) it feeds 2-wire transmitters.
  • As an analog output (AO) it can drive proportional valves, I/P converters, or local indicators.
  • As a digital input (DI) it reads dry contacts.
  • As a digital output (DO) it can drive solenoids, sounders, or LED.

A combination of analog and digital I/O is possible.
Channel LEDs indicate the status of each channel. White LEDs indicate whether AI, AO, DI, DO are selected.
The signals are galvanically isolated from the bus and the power supply.

Connection

Connection

Zone 2

Technical Data

Slots

Occupied slots| | 1
Supply
Connection| | backplane bus
Rated voltage| Ur| 12 V DC , only in connection with the power supplies LB9*
Power dissipation| | 2.15 W
Power consumption| | 3.3 W
Internal bus**
Connection| | backplane bus

Technical Data

Interface manufacturer-specific bus to standard com unit

Analog input
Number of channels| 4
Suitable field devices
Field device| pressure converter
Field device [2]| flow converter
Field device [3]| level converter
Field device [4]| Temperature Converter
Field device interface
Connection| 2-wire transmitter
Connection| terminals 1+, 2-; 3+, 4-; 5+, 6-; 7+, 8-
Transmitter supply voltage| min. 15 V at 20 mA ; 21.5 V at 4 mA
Input resistance| 15 Ω
Line fault detection| can be switched on/off for each channel via configuration tool , configurable via configuration tool
Short-circuit| factory setting: > 21 mA Can be parameterized in the range 0 … 22 mA
Open-circuit| factory setting: < 3.6 mA Can be parameterized in the range 0 … 22 mA
HART communication| yes
HART secondary variable| yes
Analog output
Number of channels| 4
Suitable field devices
Field device| Proportional Valve
Field device [2]| I/P converters
Field device [3]| on-site display
Connection| terminals 1+, 2-; 3+, 4-; 5+, 6-; 7+, 8-
Current| 0 … 20 mA short-circuit protected
Line fault detection| can be switched on/off for each channel via configuration tool , configurable via configuration tool
Short-circuit| factory setting: < 50 Ω configurable between 0 … 26 mA
Open-circuit| deviation of preset output value > 0.5 mA
Load| max. 750 Ω at 20 mA
HART communication| yes
HART secondary variable| yes
Watchdog| output off 0.5 s after serious fault
Digital input
Number of channels| 4
Sensor interface
Connection [2]| volt-free contact
Connection| terminals 1+, 2-; 3+, 4-; 5+, 6-; 7+, 8-
Line fault detection| can be switched on/off for each channel via configuration tool
Connection| mechanical switch with additional resistors (see connection diagram)
Short-circuit| > 7 mA
Open-circuit| < 0.1 mA
Digital signals (active)
Switching point: ON| > 2.1 mA
Switching point: OFF| < 1.2 mA
Digital output
Number of channels| 4
Suitable field devices
Field device| Solenoid Valve
Field device [2]| audible alarm
Field device [3]| visual alarm
Connection| terminals 1+, 2-, 3+, 4-, 5+, 6-, 7+, 8-
Drive capability| | 12 V / 22 mA
---|---|---
Internal resistor| Ri| 385 Ω
Current limit| Imax| 22 mA
Open loop voltage| Us| min. 22.7 V
Line fault detection| | can be switched on/off for each channel via configuration tool
Test current| | 0.4 mA
Short-circuit| | < 50 Ω
Open-circuit| | < 0.2 mA
Transfer characteristics
Deviation
After calibration| | 0.1 % of the signal range at 20 °C (68 °F)
Influence of ambient temperature| | 0.01 %/K of the signal range
Refresh time| | approx. 100 ms (4 channels)
Indicators/settings
LED indication| | Power LED (P) green: supply Diagnostic LED (I) red: module fault , red flashing: communication error , white: fixed parameter set (parameters from com unit are ignored) , white flashing: requests parameters from com unit Status LED (1-4) red: line fault (lead breakage or short circuit) , yellow: state of digital I/O (0/1) Configuration LED (AI, AO, DI, DO) white: selected channel mode
Coding| | optional mechanical coding via front socket
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EU| | EN 61326-1:2013
Conformity
Electromagnetic compatibility| | NE 21:2007
Degree of protection| | IEC 60529:2000
Environmental test| | EN 60068-2-14:2009
Shock resistance| | EN 60068-2-27:2009
Vibration resistance| | EN 60068-2-6:2008
Damaging gas| | EN 60068-2-42:2003
Relative humidity| | EN 60068-2-78:2001
Ambient conditions
Ambient temperature| | -40 … 60 °C (-40 … 140 °F) , 70 °C (non-Ex)
Storage temperature| | -40 … 85 °C (-40 … 185 °F)
Relative humidity| | 95 % non-condensing
Shock resistance| | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18
Vibration resistance| | frequency range 10 … 150 Hz; transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g; 10 cycles frequency range 5 … 100 Hz; transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g; 90 minutes at each resonance
Damaging gas| | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3
Mechanical specifications
Degree of protection| | IP20 (module) , mounted on backplane
Connection| | removable front connector with screw flange (accessory) wiring connection via spring terminals (0.14….. 1.5 mm2) or screw terminals (0.08… 1.5 mm2)
Mass| | approx. 100 g
Dimensions| | 16 x 100 x 102 mm (0.63 x 3.9 x 4 inch)
Data for application in connection with hazardous areas
Certificate| | BVS 12 ATEX E 115 X
Marking| | 1 II 3 G Ex nA [ic] IIC T4 Gc
Galvanic isolation
Rated voltage| Um| 250 V field circuits to control and supply circuits
Input/power supply, internal bus| | safe electrical isolation acc. to EN 60079-11, voltage peak value 375 V
Output/power supply, internal bus| | safe electrical isolation acc. to EN 60079-11, voltage peak value 375 V
---|---|---
Directive conformity| |
Directive 2014/34/EU
EN IEC 60079-0:2018+AC:2020 EN 60079-11:2012 EN 60079-15:2010
International approvals
ATEX approval| | BVS 12 ATEX E 115 X
IECEx approval| | BVS 11.0068X
Approved for Ex nAc [ic] IIC T4
General information
System information| | The module has to be mounted in appropriate backplanes (LB9***) in Zone 2 or outside hazardous areas. Here, observe the corresponding declaration of conformity. For use in hazardous areas (e. g. Zone 2 or Zone 22) the module must be installed in an appropriate enclosure.
Supplementary information| | EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www .pepperl-fuchs.com.

Assembly

Front view

Assembly

Customers Support

Refer to “General Notes Relating to Pepperl+Fuchs Product Information”.

Pepperl+Fuchs Group
www.pepperl-fuchs.com
USA: +1 330 486 0002
pa-info@us.pepperl-fuchs.com
Germany: +49 621 776 2222
pa-info@de.pepperl-fuchs.com
Singapore: +65 6779 9091
pa-info@sg.pepperl-fuchs.com

Logo

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Pepperl Fuchs User Manuals

Related Manuals