CP Electronics EBMPIR-MB-DD Mini PIR Detector for Luminaire Integration Batten Mount Installation Guide
- June 13, 2024
- CP electronics
Table of Contents
CP Electronics EBMPIR-MB-DD Mini PIR Detector for Luminaire Integration
Batten Mount Installation Guide
DALI/DSI digital dimming, miniature, luminaire mounted, PIR, presence detector
Warning
This device should be installed by a qualified electrician in accordance with
the latest edition of the IEE wiring regulations.
Dimensions (mm)
Downloads and Videos
****
cpelectronics.co.uk/cp/938
Detection pattern
high sensitivity low
Walk across
**Height** |
**Range Diameter** |
---|---|
9m | 14m |
7m | 13m |
5m | 11m |
3m | 8m |
Walk towards”
Height | Range Diameter |
---|---|
9m | 7m |
7m | 7m |
5m | 7m |
3m | 5m |
Walk towards & walk across explained
Wiring
Dimming outputs
Basic insulation only. Although low voltage, this is not an SELV output and
should be treated as if mains potential. Use mains rated wiring.
Key
- Neutral
- Live
- 10A circuit protection if required
Standard luminaire fitting
Cut mounting hole
Mounting without key
Mounting with key. Note: Key to be at the top of the sensor
Wire in plugs & connect to detector
Key
- M20 nut
- IP spacer
Lynda
- M20 nut
- IP spacer
IP luminaire fitting
Wire in plugs & connect to detector
Key
- M20 nut
- 5° washer (optional)
- Silicone washer
- IP spacer
- Note: Use the 5° spacers where the luminaire has a draft angle.
- Ensure that the silicone washer and/or IP spacer are used to maintain IP rating.
Default Settings
Time out: 20 minutes.
LUX on level: 9
LUX off level: 9
Sensitivity: 9
Detection: Presence
Adjustments can be made using the optional UHS5 or UNLCDHS handsets.
Technical Data
Part code | EBMPIR-MB-DD |
---|---|
Weight | 0.100kg |
Supply voltage AC | 230 VAC +/- 10% |
Supply frequency | 50Hz |
Power consumption parasitic | 516mW |
Max load: | |
Incandescent lighting | N/A |
Fluorescent lighting | N/A |
Compact fluorescent lighting | N/A |
LED lighting | N/A |
Cable specification | 1m 1/1.13 solid core cable 105ºC |
Number of drivers/ ballasts | Up to 4 |
SON lighting | Switch loads via a contactor |
Working temperature range | -10 to 35°C |
Humidity | 5 to 95% noncondensing |
Material (casing) | Flame retardant ABS/PC |
Insulation class | 2 |
IP rating | 65 |
Compliance | EMC-2014/30/EU LVD-2014/35/EU |
Testing
Presence Detection
-
Power up the sensor. The load should come on immediately.
-
Vacate the room or remain very still and wait for the load to switch off (this should take less than 20 minutes).
-
Enter the room or make some movement and check that the load switches on.
Accessories & associated products
Part Number | Description |
---|---|
UHS5 | Compact, programming/commissioning handset |
UHS7 | Compact, user handset |
UNLCDHS | Universal LCD IR handset/commissioning handset |
CP |
Electronics A Business unit of Legrand Electric Limited, Brent Crescent,
London NW10 7XR, UK t. +44 (0)333 900 0671 enquiry@cpelectronics.co.uk|
FM 45789 EMS 534520 OHS 642036
energy services and technology association
---|---|---
www.cpelectronics.co.uk|