YELLOW JACKET 95760 RecoverXLT Oil Less Universal Refrigerant Recovery System Instruction Manual
- June 2, 2024
- YELLOW JACKET
Table of Contents
- YELLOW JACKET 95760 RecoverXLT Oil Less Universal Refrigerant Recovery
- General Safety Instructions
- Care and Maintenance
- RecoverXLT® Operating Guide
- Push-Pull Liquid Recovery
- RECOVERY TIPS AND TECHNIQUES
- Recovering R-410A High Pressure Gas
- Troubleshooting Guide
- TECHNICAL DATA
- REPLACEMENT PARTS
- IMPORTANT NOTICE TO PURCHASER
- WARRANTY INFORMATION
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
YELLOW JACKET 95760 RecoverXLT Oil Less Universal Refrigerant Recovery
System
(For serial numbers 22120038 and higher)
English, Spanish, French and German manuals available at:
https://yellowjacket.com/product/recover-xlt/
General Safety Instructions
- Know your equipment. Read and understand the operation manual and the labels affixed to this unit. Learn the applications and limitations, as well as the specific potential hazards of the RecoverXLT®.
- Use the correct hoses. Use only hoses designed for handling of refrigerants. The hose should be the minimum length required for each job and equipped with a shut-off device (such as the compact ball valve) at the end to reduce the likelihood of refrigerant leaks to the atmosphere. For best performance we recommend using 3/8” hoses. YELLOW JACKET® hoses are made for almost every type of refrigerant. See your local distributor for more information.
- Ground all equipment. Plug the RecoverXLT® into a properly grounded receptacle using the appropriate plug.
- If the power cord is damaged, it must be replaced by a cord assembly available from the manufacturer or distributor where purchased.
- Do not pressure test with compressed air. Some mixtures of air and refrigerant have been shown to be combustible at elevated pressures.
- Avoid dangerous environments. To keep operator exposure to a minimum, use the RecoverXLT® only in areas with sufficient ventilation. Recovery should always be performed in well ventilated areas. Use the RecoverXLT® only in locations where mechanical ventilation which provides at least four air changes per hour is present, or place the unit 18” above the floor during use. The RecoverXLT® should not be used near open containers of gasoline or any other flammable liquid. Do not allow refrigerants to come in contact with open flame. Refrigerant decomposition in flame results in phosgene gas. Breathing phosgene gas can be fatal.
- Always wear safety goggles and gloves. Personal protective equipment should be worn to protect operator from frostbite.
- Use caution when connecting or disconnecting. Improper usage may result in refrigerant burns (frostbite). If a major leak occurs, proceed immediately to a well ventilated area.
- Disconnect recovery machine from power before servicing. An electrical shock hazard is present when the unit is disassembled.
- Repair damaged parts. Do not operate the RecoverXLT® if there is a defective part. Repair the unit to proper operating conditions before further use.
- Use recommended accessories. Follow the instructions that accompany all accessories. Improper use may damage equipment or create a hazard.
- Use the RecoverXLT® only with the proper refrigerants. (See specifications for a complete list of compatible refrigerants.)
- Operate th e RecoverXLT® within the design parameters only. The RecoverXLT® was designed to operate within a temperature range of 40o F (4o C) to 120oF (49oC). Do not operate in a wet location.
Caution: All refrigerant hoses, recovery tanks, refrigerant lines, other
vessels containing refrigerants and the RecoverXLT® should be handled as if
under high pressure. When opening a tank containing refrigerant, open valves
slowly to prevent release of refrigerant, especially if the valves might be
damaged.
To prevent the risk of fire DO NOT use an extension cord longer than 25’ (7.6
m) and a minimum of 16 AWG (1.276 mm2).
Care and Maintenance
Auto Purge Instructions
Purging or evacuating the RecoverXLT® is one of the simplest and most
important functions. Reduce the risk of cross contamination and prolong the
life of the RecoverXLT® by purging after every service.
Note: The purge process must be done before disconnecting the discharge
hose from the RecoverXLT®.
-
The Low Pressure Switch will shut the unit off and the Status Indicator LED will illuminate SOLID RED indicating Recovery Complete when the unit reaches 10”Hg vacuum.
After the unit stops, rotate the selector valve clockwise to OFF to equalize then to PURGE. Start the unit using the momentary switch.
Note: The low side gauge should read an increase in suction pressure, indicating the refrigerant that was trapped in the machine. -
Wait until the Low Pressure Switch again stops the unit at the appropriate vacuum.
-
Close the valve on the recovery tank and unplug the RecoverXLT® from power.
Restart Procedure
If the recovery unit was stopped during operation, it may be necessary to
balance the internal pressures before the unit will start.
To balance the internal pressure:
- Rotate selector clockwise to the OFF position. Allow pressures to balance.
- Start the recovery machine using the momentary switch
- Turn the selector valve counter-clockwise to the previous RECOVER position.
Suction Filter
The RecoverXLT® is equipped with a built-in particulate strainer located
behind the suction port. Unscrew the suction port by using a 11/16 wrench to
unscrew the hex head port to remove. This prevents contaminants, copper
shavings, carbon, and other foreign objects from making their way to the
RecoverXLT® compressor and causing permanent damage. Like a filter drier, this
strainer MUST be cleaned or replaced often. Failure to do this can cause the
strainer to become too clogged for refrigerant to flow freely. A sure sign
that the straining device is clogged is the freezing of the suction port and
the filter cover. Before replacing, check the condition of the o-ring. Replace
if necessary.
Note: Make sure to use a strainer in the RecoverXLT® for every job!
Filter strainers and O-rings are available from your supplier.
Filter Strainer and O-Ring – Part #95457
RecoverXLT® Operating Guide
Direct Liquid/Vapor Recovery
The RecoverXLT® is used to pull liquid or vapor refrigerant directly out of
the system and transfer it into a recovery cylinder. Liquid recovery is
accomplished by connecting to the high pressure system discharge service port
(Liquid Port) side of the system being serviced. Vapor recovery can be done by
connecting to the system suction service port (low pressure) side of the
system. Because the RecoverXLT® is capable of recovering direct liquid, it is
best to first recover all of the liquid, followed by the vapor. This will make
your job easier and faster. Refer to the following instructions and the above
diagram:
-
Know the type and quantity of refrigerant present before servicing any system.
-
Turn off power to the system being serviced. Turn the selector knob to off.
-
Connect your manifold to the system being serviced. High Side to liquid port and Low Side to vapor port as shown in diagram on page 4.
-
Connect the Utility port of your manifold to the 1/4” SUCTION port of the RecoverXLT®.
-
Connect one hose from the recovery cylinder
(liquid side) to the 1/4” DISCHARGE port of the RecoverXLT®.
Note: Be sure to connect hose ends with shut-off to suction and discharge ports of recovery machine (for best performance use 3/8” hoses.) -
Purge all hoses of non-condensables before recovering refrigerant into recovery cylinder.
-
Open the liquid valve on the recovery tank.
-
Start the RecoverXLT® using the momentary switch.
-
Turn the selector VALVE on the RecoverXLT® to either the LIQUID or VAPOR position.
-
Open the Utility and either High Side or Low Side valves on the manifold. Remember it is more efficient to recover the liquid refrigerant first.
Caution: do not over-pressure low side gauge. -
The RecoverXLT® will continue to recover until it reaches and sustains 10”Hg vacuum at which point the LOW PRESSURE SWITCH stops the unit and the Status Indicator LED illuminates SOLID RED indicating Recovery Complete.
-
Turn the selector valve clockwise to OFF. Start the unit using the momentary switch. Turn se-lector valve to PURGE position.
-
When the unit again stops and the Status Indica-tor LED illuminates SOLID RED indicating Recovery Complete, the recovery and purge cycles are complete.
Note: If the machine is not recovering, refer to the troubleshooting guide on page 7. Restart procedures are on the side of the machine and below.
Liquid or Vapor Recovery Diagram
Push-Pull Liquid Recovery
The Push-Pull Liquid Recovery mode is used for transferring large volumes of liquid refrigerant. The RecoverXLT® “pulls” vapor from the recovery cylinder and produces high pressure discharge gas that “pushes” liquid out of the HVAC system and into the recovery cylinder. The auto purge feature makes the reconfiguration to vapor recovery easier and faster to do. Some HVAC systems will not allow for the push-pull recovery method. If any of the following conditions apply, do not use push-pull method, but follow the instructions page 4 for RecoverXLT®.
- System contains less than 10 pounds of refrigerant.
- System is a heat pump or other unit with a reversing valve.
- System has an accumulator between the service ports used in liquid recovery.
- The refrigerant system does not allow for the formation of a solid column of liquid.
For push-pull recovery, a sight glass is monitored during recovery. When liquid is no longer visible, stop recovery and finish recovering using the VAPOR recovery process for RecoverXLT® as described on page 4. When push-pull recovery is complete, a small amount of refrigerant remains in the system. For complete recovery, the system must be pulled into a vacuum as required by EPA standards.
This process requires the following equipment:
- An extra hose for the push-pull recovery.
- A recovery cylinder with about 5 lbs. of refrigerant.
- A sight glass (Note: Make sure sight glass is rated for the pressure of the refrigerant being recovered).
Follow these steps:
- Turn off power to the system to be serviced.
- Hook up the RecoverXLT®, the system to be recovered, and the recovery tank as shown in the diagram above.
- Purge all hoses of non-condensables before recovering refrigerant into recovery cylinder.
- Open valves on the recovery tank.
- Turn the selector valve to VAPOR position.
- Start the RecoverXLT® using the momentary switch.
- Monitor the sight glass. When the passing liquid is no longer visible through the sight glass, the push-pull method of recovery is complete.
- Close the VAPOR valve on the recovery tank and let the recovery continue.
- Turn the selector valve clockwise to the PURGE position and follow procedures for purging the RecoverXLT®.
- Close LIQUID valve on recovery tank.
- Reconnect the hoses per the procedure for the RecoverXLT® vapor recovery instructions.
- Rotate the selector valve to the VAPOR position.
- Continue recovery until the unit stops or reaches the appropriate level of vacuum.
Note: See page 4 for a detailed set of instructions on Vapor Recovery.
Push-Pull Recovery Diagram
RECOVERY TIPS AND TECHNIQUES
- To assure t h e fastest and quickest recovery possible, use the shortest hoses possible and avoid hoses with Schrader depressors.
- Know what kind and the amount of refrigerant that is going to be recovered. This is critical to avoid contamination and know how much refrigerant will be recovered. The first job of the day usually means a fresh, empty tank and no cause for worry about over – filling. However, the last job of the day means there is already liquid in the tank and over-filling can be a concern. Over-filling a recovery cylinder can have disastrous results.
- Refrigerant responds to heat. Therefore, a significant increase in the speed of the recovery process will be obtained if a heat gun is used, specifically to any spots where liquid may have accumulated.
- Always try to recover liquid first. This is the preferred method of recovery for the RecoverXLT®, which pumps liquid 5 to 7 times faster in standard liquid mode than vapor.
- If recovering large amounts of refrigerant (20 lbs or more), the push-pull method is recom-mended. (Note: This process requires the hoses to be switched before recovery of the remaining vapor.)
- Recovery can often be speeded up by simultaneous recovery from both the high and low side of the system. Attach short hoses to both the high and low side of the system and join them with a BRUTE II® Manifold or Y connector to the hose going to the Suction Port of the RecoverXLT®.
- Protect the RecoverXLT® by keeping the built-in suction filter IN THE MACHINE. Failure to use the suction filter in the RecoverXLT® will void the warranty.
- Recovery machines are not vacuum pumps. For proper evacuation, use a YELLOW JACKET® SuperEvac® vacuum pump. To speed up the evacuation process, use the SuperEvac™ vacuum pump and a core removal tool (Part #18975). For more information contact your YELLOW JACKET® wholesaler.
Recovering R-410A High Pressure Gas
IMPORTANT!!! Some equipment should not be used with this refrigerant.
Take time to read the safety instructions that came with the device you are
servicing as well as any material that came with your refrigerant.
WARNING!!! USE ONLY D.O.T. RECOVERY CYLINDERS APPROVED FOR R-410A.
Overfilling the tank may cause it to rupture!
The RecoverXLT® will recover R-410A provided the following instructions are followed:
- Set-up for recovery as per diagram on page 4 for normal recovery or page 5 for push-pull recovery.
- Follow the operating procedures for your model.
- Continue recovery until the Low Pressure Switch has shut the unit off and lamp indicates Recovery Complete.
- Purge the machine (see page 3 for more details).
Technical Support: Call 800-769-8370 for additional information.
Troubleshooting Guide
Condition | Possible Problem | Possible Solution |
---|---|---|
**** Unit will not turn ON | Unit not properly plugged in or no power at power | |
source | Check power cord to ensure properly plugged into power source and IEC |
inlet
Defective Power Switch or PCB| Replace defective electrical component
Recovery process is slow| Clogged Filter| Check INLET port filter, clean
or replace
Valve core on system being recovered not fully depressed| Check core depressor
on connecting hoses
Compressor seals are worn| Rebuild compressor, replace piston seal
Unit does not pull a vacuum| Loose hose connections on Inlet Side|
Tighten hose connections
Compressor seals are worn| Rebuild compressor, replace piston seal
Hoses are not tight| Tighten hoses
Leak in HVAC/R system| Find and repair leak in system
Unit running sluggish| Low voltage to unit| Check power supply
Unit runs but shuts off after short time| Restriction on discharge side
tripping the high pressure switch| Check for restrictions
- Tank valves
- Schrader cores
Selector valve in correct position
Vacuum switch won’t reset| Switch needs to reset| Pressurize inlet port
RED LED Code| Fault Indicated| Possible Solution
---|---|---
2 Flashes| Optional Tank Over- fill Sensor has been activated| Tank
overfill sensor has activated, recovery tank is full and needs to be replaced.
Tank overfill sensor cord not connected. Either connect to a recovery tank
equipped with overfill sensor or install a shorting plug on the end of the
Tank Overfill Sensor cord.
3 Flashes| High Pressure Switch has been activated| Pressure on
the discharge of the unit exceeded 517 PSIG. Check to make sure all valves in
the discharge pathway are open. Once corrected, the pressure switch will
reset.
Excessive pressure in recovery tank. Replace recovery tank.
4 Flashes| **** Motor Overload| Let cool down for 15 minutes and
restart.
Compressor Mechanism is jammed. Repair will be required to fix the compressor
mechanism.
5 Flashes| Low Voltage Detected| Check to see if power source is in the range
of the nameplate rating.
6 Flashes| High Voltage Detected| Check to see if power source is in the range
of the nameplate rating.
- If the attached power cord is damaged (95215) it must be replaced by the manufacturer or its author-ized service center in order to avoid hazard.
TECHNICAL DATA
- UL Certified Rates to ARI Standard 740-2016
RecoverXLT ®| R- 12| R- 134a| R- 22| R-
500| R- 502| R- 410A
---|---|---|---|---|---|---
Vapor lbs./min| .37| .37| .37| .37| .66| .42
Liquid lbs./min| 1.98| 1.98| 1.98| 1.98| 2.65| 1.68
Push-Pull lbs./min| 12.81| 12.81| 12.81| 12.81| 12.9| 11.6
Vacuum Level| 15 inHg| 15 inHg| 15 inHg| 15 inHg| 15 inHg| 15 inHg
Other Refrigerants – The RecoverXLT® is approved for use with other refrigerants which have not been certified for a particular recovery rate including, but not limited to: R-1234YF, R-22, R-32, R-134a, R-401A, R401B, R-402A, R-402B, R-404A, R-406A, R-407A, R-407B, R-407C, R-407D, R-408A, R-409A, R-410A, R-411A, R-411B R-454B, R-500 and R-502.
Compressor: | 1.25 HP 2 Cylinder Oil-less Reciprocating, Air Cooled |
---|---|
Power Source: | 100-240VAC 1ph 50/60Hz |
Amperage: | 12.0 amps |
Motor Type: | Variable Speed Brushless DC, 1200-3000 RPM |
Size: | Height: |
Width: | 19.25” |
Depth: | 12.50” |
Weight: | 26.7 lbs. |
Wiring Diagrams
REPLACEMENT PARTS
RecoverXLT® Parts
Part # | Description | Part # | Description |
---|---|---|---|
95156 | 12A Breaker | 95575 | XLT Compressor ONLY |
95210 | Strain Relief | 95215 | Power Cord |
95573 | Momentary Rocker Switch | 95451 | Gauge High |
95217 | Rubber Feet | 95452 | Gauge Low |
95444 | Case Front | 95453 | Manifold Assembly |
95445 | Case Back | 95515 | Discharge Port |
95446 | Case Half | 95522 | Suction Port |
95447 | Cord Wrap | 95563 | Condenser Assembly |
95449 | Grommet | 93394 | Cap |
95574 | LED Housing w/Mounting Nut | 95576 | PCBA for XLT Compressor |
RecoverXLT® w/TOS Parts Only
Part # | Description |
---|---|
95248 | Umbilical Cord Overfill Sensor |
95188 | Shorting Cap for Umbilical Cord |
IMPORTANT NOTICE TO PURCHASER
Check for da m age immediately. Prior to shipment, all YELLOW JACKET® RecoverXLT® Refrigerant Recovery Systems are completely tested and inspected to assure compliance with Ritchie Engineering factory specifications. If the recovery system carton is damaged, check contents immediately. Note damage on shipper’s Bill of Lading and have shipper sign statement. Notify carrier immediately of the damage to arrange inspection of the recovery system and packaging. The CARRIER ALONE is responsible for handling and settling your claim. Ritchie Engineering Company, Inc. will cooperate in assessing damage if the recovery system is re-turned to the factory prepaid.
Carton contents include:
- RecoverXLT® Refrigerant Recovery System
- Owner’s manual
To validate warranty, mail registration card within 10 days.
WARRANTY INFORMATION
Ritchie Engineering Company, Inc. guarantees YELLOW JACKET® products to be
free of defective material and workmanship which could affect the life of the
product when used for the purpose for which it was designed. Warranty does not
cover items that have been altered, abused or returned solely in need of field
service
maintenance. YELLOW JACKET® recovery products (UPC 957xx) are covered by a one
year warranty for parts and labor. The 115V recovery products (UPC 95760 and
95762) have an extended three year compressor warranty. The warranty also
allows for a one year over-the-counter exchange, when applicable. To receive
this over-the-counter exchange, call Ritchie Engineering Customer Service at
800-769-8370 and get the required
authorization number. Failure to get the required authorization number could
result in a denial of the over-the-counter exchange. The following exceptions
will not be covered under this warranty: Recovery products that have been
altered, misused, or improperly maintained.
The following must be done before returning unit:
- Call our technical service personnel at 800-769-8370 to assess if the problem can be resolved over the phone.
- Obtain an SRO number from Ritchie Engineering Company, Inc. for the return of the product.
- Fax a copy of the original invoice to 800-322-8684.
Note: All units must be shipped to the Bloomington, MN plant for repair.
If at any time after the warranty period you have problems with your YELLOW
JACKET® recovery unit, call our technical service department for help in
selecting the correct replacement parts, or to arrange for its repair at
reasonable costs.
YELLOW JACKET® Products Division Ritchie Engineering Co., Inc.
10950 Hampshire Avenue South Bloomington, MN 55438
- e-mail: custserv@yellowjacket.com
- Email: www.yellowjacket.com
- Phone: 800-769-8370
- Int’l Phone: 952-943-1333
- Fax: 800-322-8684
- Int’l Fax: 952-943-1605
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>